| Plan Review Stops For Permit 01110213 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-13 |
Time |
08:27 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-11-13 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | *******************PROVSIO************** | | | | | | | | | PROVISO FROM REVIEW ON MASTER PERMIT 010 | | | 81498. | | | | | | 1.OVERFLOW PROTECTION REQUIRED BY | | | FLOAT SWITCH OR DRAIN TO CONSPICUOUS | | | LOCATION. | | | | | | 2.OUTSIDE AIR TO BE DUCTED TO VICINITY | | | OF RETURN AIR OF UNIT TO ASSURE | | | REQUIRED CFM OF OUTSIDE AIR. | | | | | | 3.PLEASE PROVIDE AS BUILT DRAWING | | | REFLECTING LOCATION OF OUTSIDE AIR | | | DUCT WORK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|