Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-13 Cont ID  
Sent By pkrauss Date 2001-11-13 Time 08:27 Rev Time 0.35
Received By pkrauss Date 2001-11-13 Time 08:27 Sent To  
Notes
2001-11-13 00:00:00*******************PROVSIO**************
  
  
 PROVISO FROM REVIEW ON MASTER PERMIT 010
 81498.
  
 1.OVERFLOW PROTECTION REQUIRED BY
 FLOAT SWITCH OR DRAIN TO CONSPICUOUS
 LOCATION.
  
 2.OUTSIDE AIR TO BE DUCTED TO VICINITY
 OF RETURN AIR OF UNIT TO ASSURE
 REQUIRED CFM OF OUTSIDE AIR.
  
 3.PLEASE PROVIDE AS BUILT DRAWING
 REFLECTING LOCATION OF OUTSIDE AIR
 DUCT WORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.