Plan Review Details - Permit 01110103
Plan Review Stops For Permit 01110103
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-20 Cont ID  
Sent By dpalmer Date 2001-12-20 Time 07:16 Rev Time 0.00
Received By dpalmer Date 2001-12-20 Time 07:01 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 21:21 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 21:21 Sent To  
Notes
2001-11-20 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT OUTLET IN
 GARAGE NEEDS TO BE GFI. 210-8
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 6)NOTE: PLEASE CLARIFY "ISLAND" SHOWN
 IN KITCHEN. PLEASE NOTE GFI OUTLET PER
 210-52-C-2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-26 Cont ID  
Sent By pkrauss Date 2001-11-26 Time 12:29 Rev Time 0.30
Received By pkrauss Date 2001-11-26 Time 12:29 Sent To  
Notes
2001-11-26 00:00:00APPROVED PER CONVERSATION WITH HAROLD ON
 11-26-01 ENERGY CALCS CALL FOR A 7.29
 SYSTEM.MANUAL J CALCS INDICATE OWNER
 IS INSTALLING TWO 3.5 TON UNITS.
  
 THIS STOP WAS NOT A REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-11-26 Cont ID  
Sent By hmoser Date 2001-11-10 Time 13:51 Rev Time 0.50
Received By pkrauss Date 2001-11-10 Time 13:51 Sent To  
Notes
2001-11-10 00:00:00PLAN DENIED
 ENERGY CALCS DO NOT MATCH PLANS
 OR MANUAL J.PLAN HAS 2 A/C UNITS
 ENERGY CALCS HAS 1 A/C UNIOT
 PLAN REVIEW BY HAROLD MOSER
 [561] 659-8096 EXT. 8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-11-08 Cont ID  
Sent By jleech Date 2001-11-08 Time 18:19 Rev Time 0.33
Received By jleech Date 2001-11-08 Time 18:19 Sent To  
Notes
2001-11-08 00:00:00PROVISO;
 REVISED RISER DIAGRAM REQUIRED BEFORE
 FINAL PLUMBING INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-12-22 Cont ID  
Sent By rmcdouga Date 2001-12-22 Time 10:59 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-22 00:00:00************BUILDING PROVISO************
  
 1) PROVIDE SOIL TEST PER CITY OF WPB
 AMENDMENTS TO 97 SBC SEC.1804.2.2. PRIOR
 TO FOOTING INSPECTION.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE FOLLOWING, PRIOR TO
 INSTALLING.
 - STRUCTURAL MULLIONS
 - FRENCH DOOR W/SIDELITES ASSEMBLY
 - ARCHED TOP (FRONT) DOOR
 - LARGE ARCHED TOP FIXED GLASS WINDOWS
 (5'-4"X 9'-0" AND 5'-8"X 8'-0")
  
 3) PROVIDE REVISED DRAWINGS INDICATING
 LOCATIONS, SIZES, REINFORCED FILLED
 CELLS ON BOTH SIDES OF OPENINGS AND
 LINTEL INFORMATION FOR 2 WINDOWS THAT
 WERE ADDED PER HISTORIC PRESERVATION
 DIVISION REQUIREMENTS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-12-12 Cont ID  
Sent By rmcdouga Date 2001-12-12 Time 10:58 Rev Time 6.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-12 00:00:00*************BUILDING UNSAT*************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE SOIL TEST PER CITY OF WPB
 AMENDMENTS TO 97 SBC SECT 1804.2.2.
  
 4) PROVIDE AT LEAST ONE BATHROOM ON THE
 FIRST FLOOR WITH A DOOR THAT HAS A 29"
 CLEAR OPENING AS REQUIRED BY 97 FLORIDA
 ACCESSIBILTY CODE.
  
 5) PROVIDE EGRESS WINDOW FOR FIRST FLOOR
 BEDROOM #2 PER 97 SBC SEC. 1005.4.
  
 6) PROVIDE EGRESS WINDOW FOR SECOND
 FLOOR BEDROOM #4 PER 97 SBC SEC. 1005.4.
  
 7) SAFETY GLAZING IS REQUIRED IN THE (3)
 MASTER BATHROOM WINDOWS PER 97 SBC SEC.
 2405.2.1(2) AND (3).
  
 8) PROVIDE ACCESS TO ATTIC SPACE PER
 97 SBC SEC. 2309.6.
  
 9) THE GUARDRAIL SYSTEM SHALL RESIST A
 200 LB. CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A ONE FOOT SQUARE AREA AT ANY
 POINT IN THE SYSTEM. 97 SBC 1608.2.2.3.
  
 10) PROVIDE STAIR RISER HEIGHT DIMENSION
 ON PLANS. INDICATE COMPLIANCE WITH 97
 SBC SEC. 1007.3, THE SUM OF TWO RISERS
 AND A TREAD, EXCLUSIVE OF NOSING, IS NOT
 LESS THAN 24" NOR MORE THAN 25".
  
 11) THE EMBOSSED SEAL, WET SIGNATURE AND
 DATE BY THE ENGINEER IS REQUIRED ON
 SHEETS 02,03,06,08,09 AND 10 OF THE
 PLANS WHICH HAVE HIS TITLE BLOCK.
  
 12) THE FOOTER SEC. ON SHEET 02 AT THE
 RIGHT SIDE OF THE STRUCTURE IS
 INCORRECTLY IDENTIFIED AS DETAIL #4 FOR
 A ONE STORY FOOTER AND SHOULD BE DETAIL
 #7 FOR A TWO STORY FOOTER.
  
 13) PROVIDE DETAILS OF SCUPPERS AND
 OVERFLOW SCUPPERS INDICATING SIZE AND
 LOCATION PER 97 SBC SEC. 1517.6.4.
  
 14) INDICATE THE LENGTH (MIN. EMBEDMENT)
 OF THE 5/8" DIA. ANCHOR BOLTS ON TYPICAL
 WALL SECTION ON SHEET 16. THE DRAWING
 APPEARS TO INDICATE WEDGE BOLTS. PLEASE
 CLARIFY.
  
 15) INDICATE THE LENGTH OF THE 5/8" DIA.
 ANCHOR BOLTS SPECIFIED FOR THE BASE OF
 THE STEEL COLUMNS IN THE COLUMN SCHEDULE
 ON SHEET 02.
  
 16) PROVIDE DETAIL TO CLARIFY THE
 ATTACHMENT OF GIRDER TRUSSES GT-10 AND
 GT-11 AT THE EXTERIOR WALLS. CLARIFY THE
 ANCHOR TAG INDICATED AT THE EXTERIOR
 WALLS FOR THESE GIRDERS. IS IT AN I OR
 THE NUMBER 1.
  
 17)INDICATE THE SPACING OF THE SPECIFIED
 FASTENERS FOR THE WINDOW AND DOOR BUCKS
 (5) & (6) ON SHEET 13.
  
 18) THE ENERGY CALCULATIONS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT.
  
 19) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS.
  
 20) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL MULLIONS
 - FRENCH DOORS WITH SIDELITES ASSEMBLY
 - 5'-4"X 9'-0" AND 5'-8"X 8'-0" FIXED
 GLASS ARCHED WINDOWS
 - ARCHED TOP (FRONT) DOOR
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 14:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***