Plan Review Details - Permit 01110060
Plan Review Stops For Permit 01110060
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-05-23 Cont ID  
Sent By hpiskura Date 2002-05-23 Time 13:42 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-23 00:00:00REVISION #2 DATED 3/14/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-29 Cont ID  
Sent By rbrown Date 2002-01-29 Time 10:49 Rev Time 0.00
Received By rbrown Date 2002-01-29 Time 10:49 Sent To  
Notes
2002-01-29 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 --PROVISO--
 FL ENERGY CODE 103.1.2BEFORE A
 BUILDING PERMIT CAN BE ISSUED, THE
 SUBMITTED ENERGY CODE COMPLIANCE FORMS
 SHALL BE SIGNED BY THE BUILDING OWNER,
 THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER.
  
 --PROVISO--
 IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-12-21 Cont ID  
Sent By rbrown Date 2001-12-21 Time 15:47 Rev Time 0.25
Received By rbrown Date 2001-12-21 Time 15:47 Sent To  
Notes
2001-12-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 WITH REFERENCE TO THE BUILDING PLAN
 REVIEW OF 12/18/01, THE COMMENTS HAVE
 NOT BEEN ADDRESSED BY THIS RESUBMITTAL.
 FOLLOWING FURTHER REVIEW OF THE PLANS,
 COMMENT (6) IS WITHDRAWN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-12-18 Cont ID  
Sent By rbrown Date 2001-12-18 Time 18:26 Rev Time 0.00
Received By rbrown Date 2001-12-18 Time 18:25 Sent To  
Notes
2001-12-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC*= STANDARD BUILD'G CODE (AMENDMENTS)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) SBC* 104.2.3NONE OF THE THREE SETS
 OF PLANS SUBMITTED HAVE ALL OF THE
 ARCHITECTURAL PLANS PROPERLY SEALED.AT
 LEAST ONE SET OF PLANS SHALL BE SIGNED
 AND SEALED.
  
 2) SBC 1012.1.2THE BOARD ROOM CAN
 ACCOMMODATE MORE THAN 50 OCCUPANTS.THE
 DOORS SHALL OPEN IN THE DIRECTION OF
 EGRESS.
  
 3) SBC 704.1.3.3.1IF THE WATER HEATER/
 BOILER EXCEEDS A HEAT INPUT CAPACITY OF
 200 000 BTUH OR A WATER TEMPERATURE OF
 210 DEGREES-F OR A NOMINAL WATER
 CAPACITY OF 120 GALLONS, IT SHALL BE
 SEPARATED FROM THE REST OF THE BUILDING
 BY 1-HOUR FIRE-RESISTANT CONSTRUCTION.
 CONFIRM WHETHER THIS IS APPLICABLE.
  
 4) SBC* 1503.1.3.2THE ABOVE-DECK ROOF
 INSULATION SHALL BE MECHANICALLY
 FASTENED.
  
 5) SBC 1503.1.5THE KITCHEN AIR INTAKE
 DUCT SHALL BE INSTALLED TO LEAVE AT
 LEAST 18" CLEARANCE FOR ACCESS TO THE
 ROOF COVERING.
  
 6) SBC 1403.2.1THE DECORATIVE CAST
 STONE PANELS (SHEET A5.2, DETAIL 1)
 SHALL BE NOT LESS THAN 1 5/8" THICK AND
 FIXED IN ACCORDANCE WITH SBC 1403.2.8.
  
 7) SBC* 1804.2.2SHEET S-3. FOUNDATION
 NOTE 1A REFERS TO A SOIL REPORT BY
 ARDAMAN AND ASSOCIATES.A SOIL REPORT
 SHALL BE SUBMITTED.
  
 8) FL ACC CODE 4.6.3THE TWO ACCESSIBLE
 PARKING SPACES SHALL EACH BE AT LEAST
 12' WIDE AND THE COMMON ACCESS AISLE AT
 LEAST 5' WIDE.WHILST SHEET A1.2 SHOWS
 ADEQUATE WIDTH, SHEET A1.1 SHOWS AN
 OVERALL WIDTH LESS THAN THE REQUIRED
 MINIMUM.
  
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-05-29 Cont ID  
Sent By dpalmer Date 2002-05-29 Time 18:45 Rev Time 0.00
Received By dpalmer Date 2002-05-29 Time 18:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-01-03 Cont ID  
Sent By dpalmer Date 2002-01-03 Time 09:28 Rev Time 0.00
Received By dpalmer Date 2002-01-03 Time 09:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By dpalmer Date 2001-11-26 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2001-11-26 Time 19:02 Sent To  
Notes
2001-11-26 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE SHOWN. PLANS HAVE BEEN DONE\\
 WITH CONNECTED LOADS SHOWN IN THE PAST,
 LOAD CALCS ARE REQ`D TO BE SHOWN.
 PER 215-5, 220-3,220-10,220-11,220-13
 PLEASE NOTE THAT ALL CONTINUOUS LOADS
 NEED TO BE SHOWN AT 125% PER 230-42,215-
 3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-01-24 Cont ID  
Sent By mamini Date 2002-01-24 Time 14:46 Rev Time 1.00
Received By mamini Date 2002-01-24 Time 14:45 Sent To  
Notes
2002-01-24 00:00:00PASSED WITH PROVISOS :
 1. A SEPARATE PERMIT APPLICATIONS AND
 FEES FOR SITE WORKS / UNDERGROUND
 UTILITIES AT THE TIME OF ACTUAL
 PERMITING WILL BE REQUIRED.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By mamini Date 2001-11-26 Time 09:21 Rev Time 3.00
Received By mamini Date 2001-11-26 Time 09:21 Sent To  
Notes
2001-11-26 00:00:00FAILED :
 1. PLEASE PROVIDE CALCULATIONS FOR STORM
 WATER AND FOR THE REQUIRED PIPE SIZES,
 FOR OUR REVIEW AND APPROVAL.
 2. A SEPARATE PERMIT APPLICATIONS AND
 FEES FOR SITE WORKS / UNDERGROUND
 UTILITIES AT THE TIME OF ACTUAL
 PERMITTING IS REQUIRED.
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-06-19 Cont ID  
Sent By mcarsill Date 2002-06-19 Time 09:39 Rev Time 0.00
Received By mcarsill Date 2002-06-19 Time 09:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-26 Cont ID  
Sent By mcarsill Date 2001-12-26 Time 09:06 Rev Time 0.00
Received By mcarsill Date 2001-12-26 Time 09:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-26 Cont ID  
Sent By mcarsill Date 2001-11-26 Time 12:45 Rev Time 0.00
Received By mcarsill Date 2001-11-26 Time 12:45 Sent To  
Notes
2001-11-26 00:00:001) IT DEPENDS WHEN THE BUILDING IS
 OFFICIALLY PERMITTED WHAT FIRE CODE
 WILL BE USED. ON JANUARY 1, 2002, THE
 FLORIDA FIRE PREVENTION CODE WILL BE
 USED WHICH INVOKES THE 2000 EDITION
 OF THE LIFE SAFETY CODE.
 2) SINCE NO FIRE SPRINKLER SYSTEM IS
 PLANNED, ALL STORAGE ROOMS, AND
 ELECTRICAL ROOM ARE TO BE FIRE RATED.
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
 4) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT,AND EXTINGUISHING SYSTEM
 PLANNED FOR KITCHEN.
 5) BOARDROOM DOORS MUST SWING IN THE
 DIRECTION OF EXIT TRAVEL. PRELIMINARY
 OCCUPANT LOAD CALCULATIONS INDICATE
 LOADS OF 50 OR MORE PERSONS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT. 8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-06-07 Cont ID  
Sent By pkrauss Date 2002-06-07 Time 10:25 Rev Time 0.25
Received By pkrauss Date 2002-06-07 Time 10:25 Sent To  
Notes
2002-06-07 00:00:00SUBMITTALS

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-04 Cont ID  
Sent By ndenmark Date 2002-06-04 Time 06:36 Rev Time 0.33
Received By ndenmark Date 2002-06-04 Time 06:36 Sent To  
Notes
2002-06-04 00:00:00REVISION FOR CONFERENCE ROOM DUCT
 LOCATION AND OUTSIDE AIR CHANGES DATED
 6/4/02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-01-05 Cont ID  
Sent By pkrauss Date 2002-01-05 Time 07:32 Rev Time 0.40
Received By pkrauss Date 2002-01-05 Time 07:21 Sent To  
Notes
2002-01-05 00:00:00 
 ADDITIONAL PERMITS REQUIRED FOR HOOD AND
 FIRE SUPRESSION.PLEASE PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 NOTE:GREASE DUCT EXHAUST SHALL BE A
 MINIMUM OF 10' FROM ANY ADJACENT
 BUILDING, PARKING AREA, ADJACENT
 PROPERTY LINE, WINDOW, DOOR, OR
 AIR INTAKE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-12-08 Cont ID  
Sent By pkrauss Date 2001-12-08 Time 08:09 Rev Time 0.45
Received By pkrauss Date 2001-12-08 Time 07:54 Sent To  
Notes
2001-12-08 00:00:00******************DENIED****************
  
  
 AS PER FIRE DEPT COMMENTS ALL STORAGE &
 ELECTICAL ROOMS ARE TO BE FIRE RATED.
 PLEASE IDENTIFY FIRE DAMPERS ON PLAN.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. (NFPA 90A
 4-4.4.3)
  
 ADDITIONAL PERMIT REQUIRED FOR HOOD AND
 FIRE SUPRESSION.PLEASE PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA/PRODUCT
 APPROVALS WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-01-12 Cont ID  
Sent By kstevens Date 2002-01-12 Time 18:51 Rev Time 1.50
Received By kstevens Date 2002-01-12 Time 18:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-28 Cont ID  
Sent By kstevens Date 2001-11-28 Time 19:39 Rev Time 1.50
Received By kstevens Date 2001-11-28 Time 19:38 Sent To  
Notes
2001-11-28 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT A2.1 PLEASE SUBMIT CALCULATIONS
 FOR MINIMUM FIXTURES PER SPC TABLE 407.
 2) SHT A2.3 PLEASE SUBMIT CALCULATIONS
 FOR ROOF DRAINAGE, PRIMARY AND SECONDARY
 DRAINS USING SPC SEC 1108 & 1109. ADD
 1/2 THE AREA OF ALL VERTICAL WALLS AND
 INCLUDE AREA OF UPPER ROOFS DRAINING ON
 TO ROOF. SHOW LOCATION OF SCUPPERS THAT
 DRAIN TYPICAL ROOFS AT CORNERS.
 3) PLEASE PROVIDE A STORM RISER DIAGRAM
 WITH ALL SQ FOOTAGE SHOWN AT EACH SECT-
 ION.
 4) SHT A7.1 DETAIL #4 PLEASE SHOW DETAIL
 OF FACBC SEC 4.18.2 & 4.18.3 FOR URNAL.
 5) SHT A7.1 DETAIL #11 PLEASE SHOW DE-
 TAIL FOR KITCHEN SINK SEC 4.24.2, 4.24.3
 AND 4.24.4 FACBC.
 5) SHT P0.1 PLUMBING NOTES #13, AIR
 CHAMBERS TO BE ACCESSIBLE AND RECHARGE-
 ABLE IF USED. WATER HAMMER ARRESTORS DO
 NOT NEED ACCESS IF APPROVED TYPE.
 6) SHT PO.2 PLEASE PROVIDE A WATER RISER
 DIAGRAM WITH PIPE SIZES AND SHOW WATER
 HAMMER ARRESTORS LOCATED CLOSE TO FIX-
 TURES IN AN "EFFECTIVE RANGE" NOT AT TOP
 OF DROP.
 7) IRRIGATION, LICENSED PLUMBING CONTRAC
 TOR TO SUPPLY A VALVE, WATTS-N36 VACUUMN
 BREAKER ABOVE GROUND FOR IRRIGATION FROM
 POTABLE WATER.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-11-19 Cont ID  
Sent By sgraham Date 2001-11-19 Time 09:13 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***