| 2001-12-03 00:00:00 | CHECKLIST: |
| | 1-NEED NOTICE OF COMMENCEMENT. |
| | 2-PROVIDE COMPLETE SECTION/DETAIL AT |
| | INTERIOR BEARING WALL BETWEEN GARAGE |
| | AND FOYER AREA SHOWING THE RECESS AT |
| | GARAGE SIDE. SEE SIZE OF FOOTING |
| | SPECIFIED. SPECIFY ALL FASTENERS. |
| | 3-REVISE ATTIC ACCESS SIZE AT MASTER BED |
| | RM. ALSO, REVISE DETAIL D/2. SEE PLANS |
| | AND SECTION 2309.6 SBC 1997. |
| | 4-PROVIDE STEEL COLUMN DETAIL SHOWING |
| | CONNECTORS AT BOTTOM OF COLUMN. SEC. |
| | 104.2.2 CITY AMENDMENTS TO SBC 1997. |
| | 5-PROVIDE PRODUCT APPROVAL FOR: |
| | A)FRENCH DOORS WITH SIDELITES SINGLE |
| | ASSEMBLY AS SHOWN ON PLANS. |
| | B)FIXED GLASS AT BREAKFAST AREA WITH |
| | SIZE SHOWN ON PLANS. |
| | C)ENTRY DOORS PRODUCT APPROVAL EXPIRED. |
| | 6-REVISE ENERGY CALCULATIONS: |
| | -UNDER ATTIC AREA IS INCORRECT. SEE SEC |
| | 604.1.A.1 FLORIDA ENERGY CODE, 1997 ED |
| | 7-CONNECTOR SPECIFIED FOR TRUSS H7B DOES |
| | NOT RESIST THE UPLIFT LOADS CALCULATED |
| | 8-ROOF TRUSSES: |
| | -UPDATE ALL GENERAL TRUSS DETAILS. USE |
| | ASCE 7-95 140MPH, NOT ASCE 7-93. SEE |
| | COMMENTS ON REVIEWED SET. |
| | 9-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE TO ORIGINAL DWGS |
| | IN ORDER TO EXPEDITE THE REVIEW. |