Plan Review Details - Permit 01101896
| Plan Review Stops For Permit 01101896 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-21 |
Time |
06:40 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-11-21 |
Time |
06:40 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01101896 | | | 2121 N DIXIE HWY | | | CONT: DAVID BIAGETTI | | | TEL: 436-9700 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- PERMIT APPLICATION ON FIRST REVIEW | | | WAS FOR "REMOVAL OF DOORS AND WINDOWS | | | AND TO REPLACE WITH BLOCK", THE SECOND | | | TIME IN ADDED "PLUMBING, ELEC & HVAC". | | | THERE IS NOTHING SAID ABOUT A PERMIT FOR | | | THE RECONSTRUCTION, EXTERIOR DOOR, AND | | | TWO OTHER OPENING OPENINGS THAT ARE NOT | | | INDICATED ON THE PLANWINDOW OR DOOR? | | | NOR DOES THE PERMIT APPLICATION SAY THIS | | | IS A TENANT BUILD OUT THOUGH THE PLANS | | | HAVE INTERIOR WALLS BATH ROOMS ETC! | | | NO MINIMUM BUILDING TYPE! | | | NO USAGE, OCCUPANCY! | | | NO ENERGY CALS! | | | NO PRODUCT APPROVALS FOR: | | | WINDOWS | | | DOORS | | | NO INFORMATION FOR INTERIOR FINISH | | | SCHEDULE | | | NO MINIMUM INTERIOR FINISH CLASSIFICA- | | | TION T 803.3 | | | SBC 1204.2 MISSING PUBLIC REST ROOM | | | NONABSORBANT MATERIALS ON FLOOR AND ON | | | WALLS TO A HEIGTH OF 4'-0". | | | PERMIT VALUE TO LOW FOR TYPE V RETAIL | | | VALUE 50% $44,460.00. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-11-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-05 |
Time |
12:19 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2001-11-05 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2001-11-05 00:00:00 | BUILDING PROVISO: PERMIT FOR BLOCKING UP | | | OPENINGS WITH CMU ONLY! |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-19 |
Time |
19:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-19 |
Time |
19:38 |
Sent To |
|
|
| Notes |
| 2001-11-19 00:00:00 | ***************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS AND CORRELATE WITH THE | | | SUBMITTED PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT | | | PER 600-5. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER NEC. 220-3/220-13/220-11 | | | PLEASE NOTE ALL CONTINUOUS LOADS AT 125% | | | | | | | | | 4)NOTE: PLEASE NOTE THAT RISER SHOW AN | | | EQUIPMENT GROUNDING CONDUCTOR BEING | | | INSTALLED BETWEEN METERCAN AND PANEL.... | | | PLEASE NOTE THAT THIS IS ONLY INSTALLED | | | AFTER FIRST MEANS OF DISCONNECT. | | | | | | 5)NOTE: PLEASE INDICATE ON PLANS THE | | | PANEL AS HAVING A MCB. | | | | | | 6)NOTE: PLEASE CLARFIY 1 CIRCUIT FOR | | | LIGHTING AT 1-POLE 15A WITH 2124W`S? | | | SEEMS TO EXCEED OCP. | | | | | | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-16 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-16 |
Time |
11:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-31 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-31 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2001-10-31 00:00:00 | 1) PLEASE INDICATE OCCUPANCY | | | CLASSIFICATION FOR BUILDING. | | | 2) PLEASE INDICATE LOCATIONS OF | | | ILLUMINATED EXIT SIGNS AND EMERGENCY | | | LIGHT FITURES. | | | 3) ANY EXIT DOOR CANNOT EXCEED FOUR | | | FEET IN WIDTH. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT 8497 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-11-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-21 |
Time |
11:16 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-11-21 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2001-11-21 00:00:00 | | | | | | | INSUFFICIENT INFORMATION FOR MECHANICAL | | | REVIEW.PLEASE PROVIDE PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-20 |
Time |
15:54 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-11-20 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2001-11-20 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE 2 0F 2 SHOW 5' TURNING RADIUS IN | | | SHOWER BATH AS REQUIRED IN FACBC SEC | | | 4.2.3 | | | 2) PAGE 2 OF 2, SHOWER STALL. SHOW | | | COMPLIANCE WITH FACBC SEC 4.21. SHOW DE- | | | TAILS FOR SEC 4.21.1 THRU 4.21.8 | | | 3) PAGE 2 0F 2, SHOWER NOT SHOWN ON | | | SANITARY RISER DIAGRAM. | | | 4) PAGE 2 OF 2, PLUMBING NOTES #14. | | | AIR CHAMBERS ARE QUICK FIX AND REQUIRE | | | ACCESS PANEL AND VALVES TO RECHARGE PER | | | SPC 607.8.3 AND PDI-WH 201. APPROVED | | | WATER HAMMER ARRESTORS DO NOT REQUIRE | | | ACCESS AND SHALL BE SIZED AND LOCATED | | | PER MANUFACTURE INSTALLATION INSTRUCTION | | | AND PDI-WH 201. | | | 5) PAGE 2 0F 2, 2 COMPARTMENT STAINLESS | | | STEEL SINK. PLEASE INDICATE USAGE FOR | | | BLDG SO A DETERMINATION CAN BE MADE FOR | | | THE DRAINAGE SYSTEM FOR SINK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|