Plan Review Details - Permit 01101896
Plan Review Stops For Permit 01101896
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-11-21 Cont ID  
Sent By jwitmer Date 2001-11-21 Time 06:40 Rev Time 1.00
Received By jwitmer Date 2001-11-21 Time 06:40 Sent To  
Notes
2001-11-21 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01101896
 2121 N DIXIE HWY
 CONT: DAVID BIAGETTI
 TEL: 436-9700
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- PERMIT APPLICATION ON FIRST REVIEW
 WAS FOR "REMOVAL OF DOORS AND WINDOWS
 AND TO REPLACE WITH BLOCK", THE SECOND
 TIME IN ADDED "PLUMBING, ELEC & HVAC".
 THERE IS NOTHING SAID ABOUT A PERMIT FOR
 THE RECONSTRUCTION, EXTERIOR DOOR, AND
 TWO OTHER OPENING OPENINGS THAT ARE NOT
 INDICATED ON THE PLANWINDOW OR DOOR?
 NOR DOES THE PERMIT APPLICATION SAY THIS
 IS A TENANT BUILD OUT THOUGH THE PLANS
 HAVE INTERIOR WALLS BATH ROOMS ETC!
 NO MINIMUM BUILDING TYPE!
 NO USAGE, OCCUPANCY!
 NO ENERGY CALS!
 NO PRODUCT APPROVALS FOR:
 WINDOWS
 DOORS
 NO INFORMATION FOR INTERIOR FINISH
 SCHEDULE
 NO MINIMUM INTERIOR FINISH CLASSIFICA-
 TION T 803.3
 SBC 1204.2 MISSING PUBLIC REST ROOM
 NONABSORBANT MATERIALS ON FLOOR AND ON
 WALLS TO A HEIGTH OF 4'-0".
 PERMIT VALUE TO LOW FOR TYPE V RETAIL
 VALUE 50% $44,460.00.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-11-05 Cont ID  
Sent By jwitmer Date 2001-11-05 Time 12:19 Rev Time 1.25
Received By jwitmer Date 2001-11-05 Time 12:19 Sent To  
Notes
2001-11-05 00:00:00BUILDING PROVISO: PERMIT FOR BLOCKING UP
 OPENINGS WITH CMU ONLY!

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By dpalmer Date 2001-11-19 Time 19:40 Rev Time 0.00
Received By dpalmer Date 2001-11-19 Time 19:38 Sent To  
Notes
2001-11-19 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
  
 2)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT
 PER 600-5.
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER NEC. 220-3/220-13/220-11
 PLEASE NOTE ALL CONTINUOUS LOADS AT 125%
  
  
 4)NOTE: PLEASE NOTE THAT RISER SHOW AN
 EQUIPMENT GROUNDING CONDUCTOR BEING
 INSTALLED BETWEEN METERCAN AND PANEL....
 PLEASE NOTE THAT THIS IS ONLY INSTALLED
 AFTER FIRST MEANS OF DISCONNECT.
  
 5)NOTE: PLEASE INDICATE ON PLANS THE
 PANEL AS HAVING A MCB.
  
 6)NOTE: PLEASE CLARFIY 1 CIRCUIT FOR
 LIGHTING AT 1-POLE 15A WITH 2124W`S?
 SEEMS TO EXCEED OCP.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-16 Cont ID  
Sent By mcarsill Date 2001-11-16 Time 11:51 Rev Time 0.00
Received By mcarsill Date 2001-11-16 Time 11:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-31 Cont ID  
Sent By mcarsill Date 2001-10-31 Time 14:59 Rev Time 0.00
Received By mcarsill Date 2001-10-31 Time 14:59 Sent To  
Notes
2001-10-31 00:00:001) PLEASE INDICATE OCCUPANCY
 CLASSIFICATION FOR BUILDING.
 2) PLEASE INDICATE LOCATIONS OF
 ILLUMINATED EXIT SIGNS AND EMERGENCY
 LIGHT FITURES.
 3) ANY EXIT DOOR CANNOT EXCEED FOUR
 FEET IN WIDTH.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT 8497

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-11-21 Cont ID  
Sent By pkrauss Date 2001-11-21 Time 11:16 Rev Time 0.40
Received By pkrauss Date 2001-11-21 Time 11:16 Sent To  
Notes
2001-11-21 00:00:00 
  
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-20 Cont ID  
Sent By kstevens Date 2001-11-20 Time 15:54 Rev Time 1.00
Received By kstevens Date 2001-11-20 Time 15:53 Sent To  
Notes
2001-11-20 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE 2 0F 2 SHOW 5' TURNING RADIUS IN
 SHOWER BATH AS REQUIRED IN FACBC SEC
 4.2.3
 2) PAGE 2 OF 2, SHOWER STALL. SHOW
 COMPLIANCE WITH FACBC SEC 4.21. SHOW DE-
 TAILS FOR SEC 4.21.1 THRU 4.21.8
 3) PAGE 2 0F 2, SHOWER NOT SHOWN ON
 SANITARY RISER DIAGRAM.
 4) PAGE 2 OF 2, PLUMBING NOTES #14.
 AIR CHAMBERS ARE QUICK FIX AND REQUIRE
 ACCESS PANEL AND VALVES TO RECHARGE PER
 SPC 607.8.3 AND PDI-WH 201. APPROVED
 WATER HAMMER ARRESTORS DO NOT REQUIRE
 ACCESS AND SHALL BE SIZED AND LOCATED
 PER MANUFACTURE INSTALLATION INSTRUCTION
 AND PDI-WH 201.
 5) PAGE 2 0F 2, 2 COMPARTMENT STAINLESS
 STEEL SINK. PLEASE INDICATE USAGE FOR
 BLDG SO A DETERMINATION CAN BE MADE FOR
 THE DRAINAGE SYSTEM FOR SINK.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***