| Plan Review Stops For Permit 01101847 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-11-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-14 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-14 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-11-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-01 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-01 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2001-11-01 00:00:00 | 1) NO SMOKE DETECTOR LOCATED ABOVE FIRE | | | ALARM CONTROL PANEL. | | | 2) MANUAL PULL-STATIONS NOT PRESENT | | | AT ALL EXIT DOOR LOCATIONS. | | | 3) NO CUT-SHEETS PROVIDED FOR FIRE | | | ALARM EQUIPMENT PLANNED FOR USE. | | | 4) PLEASE INDICATE ON PLANS, MOUNTING | | | HEIGHTS FOR FIRE ALARM EQUIPMENT. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
|