| 2001-11-26 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT# 01101812 |
| | 1925 S OLIVE AV |
| | CONT: IRONWOOD PROPERTIES |
| | TEL: (561) 279-8952 |
| | |
| | SBC=1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS STANDARD BUILDING CODE |
| | FL ACC CODE= FLORIDA ACCESSIBILITY CODE |
| | FL S. S.= FLORIDA STATE STATUTE |
| | |
| | 1)- FL S S 514.021 SHOW COMPLIANCE WITH |
| | FENCING & REQUIRED SECURE ENTRY AROUND |
| | THE POOL AREA. |
| | |
| | 2)- THE PERMIT APPLICATION STATES THIS |
| | APPLICATION WILL BE FOR CABANAS, TRELLIS |
| | AND WALL, IS THE POOL DECK TO BE CONSID- |
| | ERED UNDER THIS PERMIT? IF SO THE PLANS |
| | NEED TO SHOW THE SLOPE AWAY FROM THE |
| | POOL, NOTE THE WALL ON THE BACK SIDE OF |
| | THE TRELLIS WILL NOT ALLOW FOR DRAIAGE? |
| | |
| | 3)- SHEET A.63 DOESN'T HAVE ANY SECTIONS |
| | THROUGH THE CABANA SLABS, INDICATING THE |
| | FOUNDATION DESIGN, SOILS TERMITE TREAT- |
| | MENT OR VAPOR BARRIER. THERE IS NO INFOR |
| | MATION ON THE VERTICLAL NOR HORIZONTAL |
| | STEEL REINFORCING OR COLUMN BEAM DESIGN. |
| | |
| | 4)- SBC 104.2.2* DISCREPANCY BETWEEN |
| | SHEETS A.62 & E.8/P.1 SEE STORAGE LAYOUT |
| | |
| | 5)- PLUMBING DETAILS VENTING WILL RE- |
| | QUIRE 3" VENTS FOR EACH CABANA. THE DE- |
| | TAILS FOR THE BEAM ARE NOT INDICATED FOR |
| | THESE 2 BUILDINGS, IF CONCRETE BEAM SBC |
| | 1907.3.5(1) PIPES EMBEDDED IN BEAMS |
| | SHALL NOT BE LARGER IN OUTSIDE DIMENSION |
| | THAN 1/3 THE OVERALL THICKNESS OF THE |
| | BEAM. |
| | IF BLOCK, A MASONRY APPLICATION, |
| | ACI530.(4.1.1.1) DESIGN SHALL NOT CONSID |
| | ER CONDUITS,PIPES OR SLEEVES AS |
| | STRUCURALLYREPLACING THE DISPLACED |
| | MASONARY. |
| | |
| | 6)- SBC 1204.2 PUBLIC RESTROOMS, THE |
| | WALLS & FLOORS OF ALL PUBLIC RESTROOMS |
| | SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4 FT ABOVE THE |
| | FLOOR LINE. |
| | |
| | 7)- SBC 1606.2.6.2 COMPONENTS & CLADDING |
| | ALL GLAZED OPENINGS WILL REQUIRE PRODUCT |
| | TESTING, WINDOWS, DOORS & ROOFING ASSEM- |
| | BLIES. |
| | |
| | 8)- SHEET A.62 BAR-B-Q GRILL, THERE |
| | ISN'T ACCESS TO THE BAR-B-Q GRILL AS |
| | REQUIRED UNDER THE FAIR HOUSING ACT. |
| | SEE 4.3 ACCESSIBLE ROUTE, & 4.5 GROUND |
| | AND FLOOR SURFACES. |
| | |
| | 9)- SHEET A.64 DETAIL FOR HI RIB LATH, |
| | SBC2504.2.2 INSTALLATION OF EXTERIOR |
| | LATHING AND FRAMING SHALL COMPLY WITH |
| | ASTM 1063 C. ATTACHMENT OF HI-RIB METAL |
| | LATH TO HORIZONTAL FRAMING MEMBERS SHALL |
| | HAVE 1 3/4" PENETRATION INTO HORIZONTAL |
| | WOOD SUPPORTS.RIB LATH SHALL BE ATTACHED |
| | AT EACH RIB. |
| | |
| | PLANS SHALL BE TAKEN TO PALM BEACH |
| | COUNTY FOR IMPACT FEE ASSESSMENT. |
| | |
| | SBC 104.2.2 ADDITIONAL INFORMATION, |
| | THERE ARE STAIR DETAILS ON SHEET A.63 & |
| | S4.0 WHERE ARE THEY TO BE USED? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |