| Plan Review Stops For Permit 01101754 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-27 |
Time |
11:50 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-03-27 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | | | | DUCT SIZES ARE MISSING FROM ONE BRANCH | | | LINE ON THE 1ST FL AND THREE BRANCH | | | LINES ON THE 2ND FL. | | | | | | CFM DISTRIBUTION NOT INDICATED ON PLAN. | | | | | | EQUIPMENT NOT LISTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS T 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-01-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-28 |
Time |
13:54 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-01-28 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2002-01-28 00:00:00 | | | | | | | ORIGINAL PLANS THAT ARE APPROVED FOR | | | PERMIT ARE DONE BY AN ARCHITECT.ALL | | | REVISIONS SHALL BE SIGNED, SEALED AND | | | DATED BY THE ARCHITECT OF RECORD. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
ydavis |
Date |
2001-10-29 |
Time |
09:51 |
Rev Time |
0.25 |
| Received By |
ydavis |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | OKAY TO PRINT PASSED ON MAIN PERMIT YD |
|
|
|