Plan Review Details - Permit 01101746
Plan Review Stops For Permit 01101746
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-06 Cont ID  
Sent By pkrauss Date 2001-11-06 Time 12:26 Rev Time 0.40
Received By pkrauss Date 2001-11-06 Time 12:26 Sent To  
Notes
2001-11-06 00:00:00*******************PROVISO**************
  
  
 CONDENSATE DRAIN SHALL GO TO STORM DRAIN
 OR AN APPROVED DRY WELL. (AMENDED 1994
 SPC 804.3 #2 OR 3)
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-02 Cont ID  
Sent By pkrauss Date 2001-11-02 Time 07:01 Rev Time 0.35
Received By pkrauss Date 2001-11-02 Time 07:01 Sent To  
Notes
2001-11-02 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.10 CFM PER PERSON
 DOES NOT COMPLY WITH TABLE 2 OF ASHRAE
 62-89 FOR THIS OCCUPANCY TYPE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.