| Notes |
| 2001-10-29 00:00:00 | ****************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT TWO SETS OF | | | PLANS ARE REQ`D TO BE SUBMITTED. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 3)NOTE: PLEASE NOTE EQUIPMENT GROUNDING | | | CONDUCTOR MISSING FROM MAIN HOUSE TO | | | DETACHED BLDG.ALSO GROUNDING AT DETACHED | | | BLDG.250-32 | | | | | | 4)NOTE: PLEASE THAT ANY ROOMS IN DETACHE | | | D BLDG. CAN BE CONVERTED TO SLEEPING | | | ROOMS, SD`S WILL BE REQ`D. NFPA-72 | | | 2-2.1.1.1 | | | | | | 5) PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | | | | 6)NOTE: PLEASE NOTE THAT BATHS ARE TO | | | 20A #12. 210-11-C-3 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
|