Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By dpalmer Date 2001-10-29 Time 19:07 Rev Time 0.00
Received By dpalmer Date 2001-10-29 Time 19:07 Sent To  
Notes
2001-10-29 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT TWO SETS OF
 PLANS ARE REQ`D TO BE SUBMITTED.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3)NOTE: PLEASE NOTE EQUIPMENT GROUNDING
 CONDUCTOR MISSING FROM MAIN HOUSE TO
 DETACHED BLDG.ALSO GROUNDING AT DETACHED
 BLDG.250-32
  
 4)NOTE: PLEASE THAT ANY ROOMS IN DETACHE
 D BLDG. CAN BE CONVERTED TO SLEEPING
 ROOMS, SD`S WILL BE REQ`D. NFPA-72
 2-2.1.1.1
  
 5) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 6)NOTE: PLEASE NOTE THAT BATHS ARE TO
 20A #12. 210-11-C-3
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372