Plan Review Details - Permit 01101634
| Plan Review Stops For Permit 01101634 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-04-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-23 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-23 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-02-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-07 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-07 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2002-02-07 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT EVEN RECESSED | | | FIXTURE IN CLOSET IS SHOWN TOO CLOSE. | | | PER 410-8 MAY BE FLOURESCENT ON WALL, | | | ABOVE DOOR. | | | | | | 2)NOTE: PLEASE NOTE THAT THE LOAD | | | CALCULATIONS SUBMITTED WERE ONLY FOR | | | DETACHED BLDG. PLEASE INLCUDE MAIN | | | HOUSE. | | | | | | 3)NOTE: PLEASE NOTE THAT A RISER | | | DIAGRAM WAS STILL NOT SUBMITTED FOR | | | REVIEW FOR FEED FROM EXSITING SERVICE. | | | | | | 4)NOTE: PLEASE NOTE GROUNDING DETAIL | | | FOR DETACHED BLDG NOT SHOWN PER 250-32 | | | | | | | | | PLEASE PICK UP PLANS AND RESUBMIT FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-29 |
Time |
20:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-29 |
Time |
20:43 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT OUTLETS SHOWN | | | FOR BATHS NEED TO BE SHOWN AS GFI/ | | | ALSO MUST BE 20A AND #12 210-8,210-11-C | | | -3. | | | | | | 2)NOTE: PLEASE NOTE THAT SD`S WILL BE | | | REQ`D INSIDE AND OUTSIDE BEDROOMS. | | | NFPA-72 2-2.1.1.1 | | | | | | 3)NOTE: PLEASE NOTE THAT LIGHT IN CLOSET | | | NEEDS TO MEET 410-8 FOR CLEARENCE AND | | | TYPE OF FIXTURE. | | | | | | 4)NOTE: PLEASE NOTE WATER HEATER IS | | | NOT PERMITTED IN CLOSET WITH IGNITABLE | | | MATERIALS. A SEPARATE WALL WOULD HAVE TO | | | BE BUILT FOR CLEARENCE/SEPARATION. | | | 422-17 | | | | | | 5)NOTE: PLEASE NOTE THAT PLANS DO NOT | | | SHOW ENOUGH INFORMATION FOR PANEL AND | | | HOW OR WHERE IT IS BEING FED?? WIRE/ | | | CONDUIT? GROUNDING? LOAD CALCULATIONS? | | | EXSITING ? NEW? 215-5 | | | | | | 6)NOTE: PLEASEOUTLET OUTSIDE NEEDS TO | | | BE SHOWN AS GFI 210-8 | | | | | | **PLEASE NOTE THAT PLAN WILL NEED TO | | | BE REVIEWED BY ZONING FOR ACCESSORY | | | SLEEPING UNIT.***** | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|
|
|