Plan Review Details - Permit 01101603
Plan Review Stops For Permit 01101603
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-04 Cont ID  
Sent By jwitmer Date 2001-12-04 Time 17:18 Rev Time 1.33
Received By jwitmer Date 2001-12-04 Time 17:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-22 Cont ID  
Sent By jwitmer Date 2001-11-22 Time 12:20 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-22 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01101603
 222 LAKEVIEW SUITE 164/166/168
 CONT KOLTER SIGNATURE HOMES, INC
 TEL: (561) 468-4703
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- CITY CODE 7.2 ALLOWS FOR THE BUILD-
 ING DEPARTMENT TO CALCULATE THE PERMIT
 FEES USING THE FEE TABLE SET UP THROUGH
 SBCCI WITH A FLORIDA MULTIPLIER. YOUR
 PERMIT VALUE IS NOT REALISTIC, TOO LOW,
 EITHER PRODUCE A SIGNED CONTRACT OR THE
 VALUES WILL BE TAKEN FOR TYPE II CON-
 STRUCTION, FLORIDA MULTIPLIER AND
 REDUCED 50% SINCE THE STRUCTURE IS NOT
 TO BE CONSIDERED.CALCULATED FIGURE WITH
 50% REDUCTION IS:
 (1814SQ FT X $106.08) X 50%=$96,214.56.
  
 2)- SBC 1001.1.3 ALLOWS FOR THE USE OF
 OFFICE TO BE USED AS A SECOND MEANS OF
 EGRESS, SEC 1020 ALLOWS FOR SINGLE MEANS
 OF EGRESS IF:
 A) A MAXIMUM OF 2 STORIES IN HEIGTH
 B) EACH FLOOR AREA SERVED DOESN'T
 EXCEED 3,500 SQ FT
 C) NO MORE THAN 40 PEOPLE ABOVE THE
 STREET FLOOR
 D) THE MAXIMUM TRAVEL DISTANCE TO A
 SINGLE EXIT DOES NOT EXCEED 75'.
 THIS OFFICE MEETS REQUIREMENTS FOR
 SINGLE MEANS OF EGRESS THROUGH THE
 BUILDING CODE.
  
 3) THIS IS A TYPE II BUILDING,
 SBC 609.2.1 NO COMBUSTIBLE MATERIALS IN
 WALLS. FIRE RESISTANT TREATED WOOD MAY
 BE USED AS SILL, OR BACKING MATERIAL.
  
 4) MISSING THE MINIMUM INTERIOR FINISH
 CLASSIFICATION SBC TABLE 803.3.
  
 5) TYPE 1 & II BUILDINGS REQUIRE FIRE
 SPRINKLER PLANS AS PART OF THE BUILDING
 PERMIT PACKAGE. SEPERATE PLANS, FEES &
 PERMIT REQUIRED FOR FIRE SPRINKLERS.
  
 6)- FLOOR FINISHES NOT INDICATED:
 FL ACCESS CODE 4.5 FLOOR SURFACES ALONG
 ACCESIBLE ROUTES AND IN ACCESSIBLE ROOMS
 SPACES INCLUDING FLOORS ,RAMPS AND
 STAIRS SHALL BE STABLE, FIRM, AND
 SLIP RESISTANT. ADDAAG A-5 A STATIC
 COEFFICIENT OF FRICTION OF 0.6 FOR ALL
 ACCESSIBLE ROUTES & 0.8 FOR RAMPS.
  
 7)SEE KITHEN & RESTROOM NOTES:
 WATER CLOSET: FL ACCESS CODE 4.16.3
 THE HEIGTH OF THE WATER CLOSET SHALL BE
 17" TO 19" MEASURED TO THE TOP OF THE
 TOLIET SEAT.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-12-31 Cont ID  
Sent By dpalmer Date 2001-12-31 Time 09:20 Rev Time 0.00
Received By dpalmer Date 2001-12-31 Time 09:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-24 Cont ID  
Sent By dpalmer Date 2001-12-24 Time 13:15 Rev Time 0.00
Received By dpalmer Date 2001-12-24 Time 13:15 Sent To  
Notes
2001-12-24 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT UNDER FS/FAC
 HANDWRITTEN CHANGES TO SIGNED AND
 SEALED PLANS MUST BE DONE BY THE
 ENGINEER OF RECORD PER 471.025.
  
 2)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE CLOUDED/TRIANGLES SHHOWING LOCATIONS
 OF REVISIONS.
  
 PLEASE MAKE THE ABOVE CHANGES/CORRECTION
 -S AND SUBMIT FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.,
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 3)NOTE: PLEASE ALSO NOTE THAT SIGNED
 AND SEALED PLANS MAY NOT BE COPIED W/OUT
 BEING RE-SIGNED DATED AND SEALED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-11-16 Cont ID  
Sent By dpalmer Date 2001-11-16 Time 12:40 Rev Time 0.00
Received By dpalmer Date 2001-11-16 Time 12:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-05 Cont ID  
Sent By mcarsill Date 2001-12-05 Time 15:53 Rev Time 0.00
Received By mcarsill Date 2001-12-05 Time 15:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-11-21 Cont ID  
Sent By mcarsill Date 2001-11-21 Time 12:06 Rev Time 0.00
Received By mcarsill Date 2001-11-21 Time 12:06 Sent To  
Notes
2001-11-21 00:00:001) THE OFFICE DOOR LEADING TO THE
 FIRE EXIT CANNOT BE LOCKED TO PREVENT
 EGRESS. ALSO A MINIMUM AISLE IS TO
 BE MAINTAINED WITHIN THE OFFICE TO
 ENSURE PROPER EXITING.
 2) ALSO AN ADDITIONAL EXIT SIGN WILL
 BE REQUIRED TO DIRECT PERSONS TO THE
 OFFICE AREA.
 3) NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS. PLEASE INDICATE
 INTERIOR FINISH CALSSIFICATION FOR
 WALLS AND CEILINGS (A,B,OR C).
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT. 8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-11-21 Cont ID  
Sent By pkrauss Date 2001-11-21 Time 15:40 Rev Time 0.30
Received By pkrauss Date 2001-11-21 Time 15:40 Sent To  
Notes
2001-11-21 00:00:00 
  
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 12:05 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 12:05 Sent To  
Notes
***NONE***