|
 |
 |
 |
 |
 |
Plan Review Details - Permit 01101601
| Plan Review Stops For Permit 01101601 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-02-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-07 |
Time |
16:16 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
2002-02-07 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2002-02-07 00:00:00 | APPROVED PER CAPT MIKE CARSILLO | | | 2-7-02. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-02-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-22 |
Time |
13:16 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-02-22 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2002-02-22 00:00:00 | AS BUILTS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-01-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-23 |
Time |
08:32 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-01-23 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2002-01-23 00:00:00 | | | | | | | PROVISO: | | | | | | SECTIONS TO "BLANKED" OFF SHALL BE | | | MARKED ACCORDINGLY AS TO NOT | | | INADVERTENTLY MISPLACE THESE SECTIONS | | | AFTER CLEANING/MAINTENANCE. | | | | | | PLEASE NOTE SECTIONS "BLANKED" OFF SHALL | | | NOT HAVE EQUIPMENT THAT PRODUCE GREASE | | | LADEN VAPORS INSTALLED BENEATH THESE | | | AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-16 |
Time |
07:30 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-11-16 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2001-11-16 00:00:00 | PROVISO ON PLAN- FAN SHUTDOWN BY DUCT | | | SMOKE DETECTOR WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS.1997 SMC 406.1 AND NFPA 90A | | | 4-4.4.3. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
|
Date |
2001-10-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-26 |
Time |
09:37 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-10-26 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2001-11-01 00:00:00 | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | NOTE:PRIOR TO CONNECTING TO EXISTING | | | AHU, AHU SHALL BE CLEANED AND | | | SANITIZED. | | | | | | PLEASE PROVIDE TWO SETS OF | | | PLANS WITH THE ABOVE INFORMATION. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT 8388. |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |