| Plan Review Stops For Permit 01101599 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-11-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-05 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-05 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-29 |
Time |
21:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-29 |
Time |
21:19 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: PLEASE SHOW GROUNDING AT DETACH- | | | ED BLDG.250-32 | | | PLEASE NOTE MISSING EQUIPMENT GROUNDING | | | CONDUCTOR FROM MAIN HOUSE TO COTTAGE. | | | 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
|