| Plan Review Stops For Permit 01101538 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-01 |
Time |
11:19 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-11-01 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-25 |
Time |
13:45 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-25 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2001-10-25 00:00:00 | ******************DENIED**************** | | | | | | | | | PLEASE PROVIDE PLANS THAT A LEGIBLE. | | | CANNOT READ THE INFORMATION ON | | | EQUIPMENT. | | | | | | 1 1/2 TON IS INDICATED WHICH IS EQUAL TO | | | APPROXIMATELY 600 CFM.PLANS INDICATE | | | 770 CFM.PLEASE LIST TOTAL BTU'S FOR | | | THE EQUIPMENT. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|