| 2002-02-12 00:00:00 | CHECKLIST: |
| | 1-REVISED ENERGY CALCULATIONS ARE WRONG |
| | AGAIN. SEE SQUARE FOOTAGES ENTERED FOR |
| | A/C AREA AND UNDER ATTIC AREA. |
| | -PROVIDE CORRECT UNDER ATTIC AREA AS |
| | REQUIRED BY SEC. 604.1.A.1 OF FLORIDA |
| | ENERGY EFFICIENCY CODE. 1997 ED. |
| | -NOTE: THIS IS A MODEL HOUSE. PREVIOUS |
| | ENERGY CALCULATIONS WERE DONE TO WORST |
| | CASE SCENARIO. NOW, THIS ONE IS NOT. |
| | CLARIFY IF USING WORST CASE SCENARIO |
| | OR IF ENERGY CALCULATIONS WILL BE |
| | CALCULATED FOR EACH HOUSE. |
| | 2-PLANS SUBMITTED AT TIME OF APPLICATION |
| | SHOW GARAGE AT RIGHT HAND SIDE. NOW, |
| | PLANS RESUBMITTED SHOW GARAGE AT LEFT |
| | HAND SIDE. PROVIDE REVISED SURVEY FOR |
| | ZONING AND BUILDING RE-REVIEW. |
| | 3-SPECIFY ON FLOOR PLAN 1 HR FIRE RATED |
| | GLASS BLOCK ASSEMBLY AT ZERO LOT LINE |
| | WALL AND REVISE GLASS BLOCK DETAILS ON |
| | SHEET 5 TO MATCH 1 HR ASSEMBLY AS PER |
| | UL LISTING. SEE ATTACHED COPY THAT WAS |
| | SUBMITTED BY CONTRACTOR. |
| | 4-TRUSS DRAWINGS: |
| | A)TRUSS ENGINEER TO SIGN, SEAL AND DATE |
| | TRUSS LAYOUT. |
| | B)UPDATE GENERAL DETAILS AS REQUIRED. |
| | USE CURRENT CODES AND CORRECT MPH |
| | WIND LOAD. |
| | C)THERE ARE 2 ENGINEER'S SEALS ON |
| | GENERAL DETAILS. REVISE AS REQUIRED. |
| | D)GENERAL DETAILS ARE NOT LEGIBLE. |
| | E)SPECIFY ON ENGINEERED TRUSSES WHAT |
| | EDITION OF SBC WAS USED FOR DESIGN. |
| | IT SHALL BE SBC 1997. |
| | F)MIXING AND MATCHING ASCE 7-98 AND SBC |
| | 1997 IS NOT ALLOWED. REVISE AS REQ'D. |
| | G)RIGHT WIND ZONE USING ASCE 7-98 IS |
| | 140 MPH. REVISE AS REQUIRED. |
| | 5-SPECIFY CEILING INSTALLATION AT FRONT |
| | AND BACK PORCH. SEE ASTM C-926 AND |
| | ASTM C-1063 AND PROVIDE SPECS AS REQ'D |
| | (SEC. 2504.2 SBC 1997). |
| | 6-SEE COMMENTS ON PLANS. |
| | 7-CLEARLY SPECIFY SIZE OF ANCHOR ON DWG |
| | 3B. EG: HETA 16, 20 OR 24 ETC. |