Plan Review Details - Permit 01101352
| Plan Review Stops For Permit 01101352 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-29 |
Time |
19:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-29 |
Time |
19:24 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE AIC RATINGS FROM | | | FIRST REVIEW, HAS NOT BEEN SUBMITTED. | | | 110-9/215-5 | | | PLEASE SUBMIT THE RATING. | | | | | | 2) NOTE: PLEASE SHOW ALL OUTLETS | | | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECT--ED PER 210-8-A-6. | | | | | | 3)NOTE: PLEASE NOTE THAT PER | | | CONVERSATION WITH THE ELECTRICAL | | | INSPECTOR THERE | | | IS ALSO OTHER WORK ON SITE AND NEEDS TO | | | BE SHOWN. | | | | | | 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | | SHOWS OVERHEAD SERVICE AND APPL SAYS | | | UNDERGROUND.?? PLEASE CALRIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-25 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-25 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2001-10-25 00:00:00 | ************* UNSAT ************ | | | | | | 1)NOTE: PLEASE NOTE THAT THERE IS NO | | | LAYOUT FOR KITCHEN? | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REIVEW | | | 561-659-8096 EXT 8372 |
|
|
|