Plan Review Details - Permit 01101346
Plan Review Stops For Permit 01101346
Review Stop P PLUMBING
Rev No 3 Status P Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 08:59 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 08:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-11-01 Cont ID  
Sent By kstevens Date 2001-11-01 Time 11:59 Rev Time 0.50
Received By kstevens Date 2001-11-01 Time 11:59 Sent To  
Notes
2001-11-01 00:00:00DENIED
 REFERENCE: SGC-97
  
 1) COMMENT #1 FROM PREVIOUS REVIEW NOT
 ADDRESSED. 2 COPIES OF SIGNED AND SEALED
 PLANS REQUIRED. PLANS NOT SEALED.
 2) CONFLICTING INFORMATION ON SHEETS.
 ONE SHEET SHOWS 54,000 BTUS (3 AT 18,000
 AND THE OTHER SHOWS 2 DRYERS AT 18,000
 AND THE 3RD AT 90,000. PLEASE CLARIFY.
 3) SEE GAS PERMIT APPLICATION REQUIRE-
 MENTS SHEET #'S 1- 5 & 9, INFORMATION
 STILL REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By pschmitz Date 2001-10-24 Time 15:06 Rev Time 1.00
Received By pschmitz Date   Time 15:06 Sent To  
Notes
2001-10-24 00:00:00PLUMBING PLAN REVIEW,DENIED
 GAS PERMIT APPLICATION REQUIRMENTS
 (1) 2 COPIES OF IOMETRIC SIGNED AND
 SEALED BY MR ROBERT BELL ARCHITECT.
 ISOMETRIC TO SHOW EACH GAS OUTLET AND
 CORRESPONDING LGTHS, PIPE SIZES.
 (2) CONFLICTING INFORMATION ON SHEETS
 SUBMITTED, BOILER 670K AND 300 BTU,S?
 (3)BOILER IN A CONFINED SPACE, PROVIDE
 CALCULATIONS FOR COMBUSTION AIR AND
 VENTILATION AIR SIZE
 REFERENCE 1997 STD GAS CODE SEC 104.2
 DRAWINGS AND SPECIFICATIONS.
 END OF COMENTSPAUL SCHMITZ
 QUESTIONS561 659 8096X8233