| Plan Review Stops For Permit 01101303 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-21 |
Time |
16:44 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-21 00:00:00 | SAME COMMENTS AS FIRST REVIEW ON | | | 11/02/01 SEE COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-02 |
Time |
13:20 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-02 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01101303 | | | 720 39TH ST | | | CITY PROJECT | | | DAY CARE FACILITY | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS STANDARD BUILDING CODE | | | | | | 1)- DROP OFF SITE: FL ACC CODE 4.3.2 | | | ACCESSIBLE ROUTE, CURB CUTS. THE SITE | | | DOESN'T INDICATE PARKING? | | | | | | 2)- FL ACC CODE : PLANS DO NOT DESIGNATE | | | WHICH RESROOMS ARE TO BE HANDICAPPED | | | ACCESIBLE? | | | | | | 3)- PORCH 123 SHEET S-1 INDICATES MW-1 | | | A 8" CMU, VERSES A-2 1'-0" THICK. | | | | | | 4)- S-1 THE COMMON WALL BETWEEN ROOM 117 | | | & HALLWAY 107 INDICATES THIS TO BE | | | A BEARING MASONARY WALL, MISSING | | | VERTICAL SUPPORT? | | | | | | 5)- S-1, S-2 LINTAL INFORMATIOIN MISSING | | | S-3 CONCRETE LINTALS NOTE "A" INDICATES | | | THERE MAY BE DROP BEAM OR LINTALS? | | | | | | 6)- MISSING MINIMUM BEARING, SOILS | | | REPORT. | | | | | | 7)- SBC 1606.6.2.6COMPONENTS& CLADDING | | | THE CITY REQUIRES PRODUCT TESTING | | | REPORTS FOR ALL GLAZED OPENINGS: | | | WINDOWS | | | FRENCH DOORS( IF DOOR ARE CONNENCTED | | | WITH SIDE LITES TESTING | | | IS TO INDICATE THIS, | | | ALSO IF TRANSOMS ARE | | | TO BE USED. | | | WINDOW MULLIONS | | | ROOFING ASSEMBLIES | | | STORM SHUTTERS | | | GLAZED OPENINGS REQUIRE PRODUCT TESTING | | | FOR LARGE MISSLE IMPACT RESISTANCE | | | TESTING. IF WINDOWS HAVEN'T RECEIVED | | | THIS CERTIFICATION STORM SHUTTERS PASS- | | | ING THIS TEST MAY BE SUBMITTED. | | | | | | 8)- COUNTY IMPACT FEES TO BE PAID TO THE | | | COUNTY BEFOR ISSUANCE. | | | | | | PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-30 |
Time |
19:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-30 |
Time |
19:09 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT | | | COMPLETE FOR COMPLETE PLAN REVIEW. | | | | | | 2)NOTE: PLEASE NOTE E-2 GYMNASIUM PLAN?? | | | AND YET NO GYM IS SHOWN?? | | | | | | 3)NOTE: PLEASE NOTE THAT WIRE SIZES, | | | CONDUITS? GROUNDING??? LOAD CALCAS?? | | | ETC ETC. | | | | | | 4)NOTE: PLEASE NOTE THAT PLANS MUST BE | | | SIGNED, DATED AND SEALED BY THE ENGINEER | | | OF RECORD. 471.025 | | | | | | PLEASE SUBMIT COMPLETE PLANS FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-10-30 |
Time |
15:11 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2001-10-30 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | FAILED : | | | 1. INSUFFICENT INFORMATIONS FOR CIVIL | | | ENGINEERING REVIEW, PLEASE SUBMIT CIVIL | | | PLANS FOR OUR REVIEW AND APPROVAL. | | | 2. CIVIL PLANS SHOULD INCLUDE STORM | | | WATER CACULATIONS FOR ENTIRE SITE , | | | UNDERGROUND UTILITIES, PAVEMENT AND | | | POLLUTIONS PREVENTION PLANS. | | | 3. PLEASE INCLUDE PERVIOUS & IMPERVIOUS | | | CALCULATIONS FOR THE PROPOSED SITE. | | | 4. WE RECOMMEND A SEPARATE PERMIT | | | APPLICATION FOR SITE WORK. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-25 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-25 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2001-10-25 00:00:00 | 1) PLEASE INDICATE THE HOURS OF | | | OPERATION, AGES OF CHILDREN, AND | | | NUMBER OF STAFF. | | | 2) ANY CLOSET DOORS ARE REQUIRED TO BE | | | UNLOCKED FROM THE INSIDE. | | | 3) BATHROOM DOORS ARE TO BE UNLOCKED | | | BY STAFF. | | | 4) NO SMOKE DETECTION SYSTEM SHOWN | | | ON THE DRAWINGS. | | | 5) BUILDING ADDRESS REQUIRED PER CITY | | | CODE. | | | 6) PLEASE INDICATE LOCATIONS OF ALL | | | EMERGENCY LIGHT FIXTURES. | | | 7) GENERAL NOTES INDICATES A FIRE | | | SPRINKLER SYSTEM. NO DRAWINGS HAVE | | | BEEN PROVIDED. | | | 8) PAGE E-2 IS LABELED GYMNASIUM BUT | | | THE PLANS INDICATE THAT IT IS A | | | DAY CARE. | | | 9) ANY COOKING THAT PRODUCES SMOKE OR | | | GREASE LADEN VAPORS MUST BE PROTECTED | | | BY A HOOD,DUCT AND EXTINGUISHING SYSTEM. | | | SEPARATE PLANS AND PERMITS REQUIRED. | | | 10) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-03-25 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-03-25 |
Time |
14:10 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2002-03-25 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2002-03-25 00:00:00 | ***************DENIED******************* | | | 1. LIFE SAFETY PLAN SHOWS RATED WALL AT | | | MECH RM, PROVIDE FIRE DAMPER LOCATION | | | IN DUCTS PER 1997 SMC 610.6 | | | 2. CLARIFY RATING AT DIFFUSERS RG-2 AND | | | CD-3 IN LOBBY. IS THIS A REQUIRED RATED | | | CEILING? IF SO SHOW WALL RATINGS FOR | | | DETERMINATION OF OPENING PROTECTION | | | REQUIRED AT OTHER DUCT LOCATIONS. NO | | | RATINGS ARE INDICATED ON LIFE SAFETY | | | DRAWING IN THIS AREA. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-05 |
Time |
12:51 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-11-05 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2001-11-05 00:00:00 | ********************DENIED************** | | | | | | | | | MECHANICAL PLANS NOT SUBMITTED FOR | | | REVIEW. | | | | | | PLEASE PROVIDE PLANS WITH MECHANICAL | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-26 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-03-26 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2002-03-26 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) OTHER THAN A SANITARY RISER DIAGRAM | | | ADDED, AND PLANS BEING SIGNED AND SEALED | | | ALL COMMENTS FROM PREVIOUS REVIEW HAVE | | | NOT BEEN ADDRESSED. SEE PREVIOUS COMM- | | | ENTS DATED 10-19-01 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-30 |
Time |
16:12 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2001-10-30 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | DENIED | | | REFERENCES: SPC-94 - FACBC-97 | | | | | | 1) PLEASE SUPPLY CALCULATIONS FOR MINI- | | | MUM FACILITIES. REQUEST INFORMATION ON | | | AGE OF CHILDREN, HOURS OF OPERATION AND | | | AVERAGE ATTENDENCE FIGURES. SPC TAB 407 | | | 2) PAGE A2. FLOOR PLAN PLEASE SHOW DE- | | | TAIL FOR TYPICAL DRINKING FOUNTAIN IN | | | CLASS ROOM. SHOW DETAIL OF HIGH/LOW | | | DRINKING FOUNTAIN. SHOW COMPLIANCE WITH | | | FACBC-97 SEC 4.15 | | | 3) PAGE A2. PLEASE SHOW CLEAR FLOOR | | | SPACE FOR ALL HDCP PLUMBING FIXTURES | | | PER FACBC-97 | | | 4) SUBMIT SANITARY AND WATER RISER DIA- | | | GRAMS FOR REVIEW. PLEASE SHOW WATER HAM- | | | MER ARRESTORS PLACED NEAR FIXTURES PER | | | MANUFACTURES INSTALLATION INSTRUCTION & | | | WH-PDI 201 NOT ON TOP OP DROP. | | | 5) PLEASE PROVIDE SIGNED AND SEALED SETS | | | OF PLANS FOR REVIEW FOR PERMIT. | | | 6) PLANS TO BE ROUTED TO THE PALM BEACH | | | COUNTY HEALTH UNIT, DIVISION OF ENVIRON- | | | MENTAL HEALTH 901 EVERNIT STREET WPB FL | | | 33041 | | | 7) MINIMUM GREASE TRAP 750 GALS. PLEASE | | | CONTACT UTILITY DEPT FOR SIZE AND LOCAT- | | | ION OF GREASE TRAP. CALL RODNEY COMPO | | | (561) 837-4074. | | | 8) PLEASE SUBMIT A GREASE LINE RISER | | | DIAGRAM FOR REVIEW FOR FOOD PREP AREA. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-22 |
Time |
11:50 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|