Plan Review Details - Permit 01101295
| Plan Review Stops For Permit 01101295 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-21 |
Time |
15:40 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-21 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK # 01101295 | | | 4017 PINEWOOD AV | | | CITY PROJECT "GYMNASIUM" | | | TEL: (561) 848-1988 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING | | | AMENDMENTS | | | | | | FLORIDA STATE STATUTE 553.80.2(B) | | | THE LOCAL GOVERNMENT SHALL IMPOSE, EACH | | | TIME AFTER THE THIRD SUCH REVIEW THE | | | PLANS ARE REJECTED FOR THE CODE VIOLA- | | | TION, A FEE OF FOUR TIMES THE AMOUNT OF | | | THE PROPORTION OF THE PERMIT FEE ATTRIB- | | | UTED TO PLAN REVIEW. | | | | | | THE CHECKLIST FROM 11/14/01 IS UNCHANGED | | | ALL COMMENTS (10) ARE TO BE ADDRESSED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-14 |
Time |
07:07 |
Rev Time |
7.00 |
| Received By |
jwitmer |
Date |
2001-11-14 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2001-11-14 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK# 01101295 | | | 4017 PINEWOOD AV | | | CITY PROJECT "GYMNASIUM" | | | TEL: (561) 848-1988 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | **** PLANS SUBMITTED AFTER JAN. 1,2002 | | | FOR PERMIT APPLICATION WILL BE REVIEWED | | | UNDER THE 2001 FLORIDA CODE.****** | | | | | | 1)- SBC 104.2.2 ADD INFORMATION REQUIRED | | | A CURRENT SURVEY INDICATE THE PROPOSED | | | LOCATION OF BUILDING ON SURVEY FOR TABLE | | | 600 ISSUES. | | | | | | 2)- SBC 1804.2.7.2(3) SOILS REPORT/ WITH | | | THE MINIMUM SOIL BEARING VALUE. | | | | | | 3)- ENERGY CALCULATIONS WITH MANUAL "J" | | | | | | 4)- A SITE PLAN WITH HANDICAPPED INDICA- | | | TING AN ACCESSIBLE ROUTE FROM CURB FOR | | | (PUBLIC TRANSPORTATION) AND FROM THE | | | HANDICAPPED PARKING SPACES. | | | INDICATE WHAT AREAS ARE TO BE ACCESS | | | IBLE, FOR AXAMPLE FROM THE EXTERIOR | | | HANDICAPPED RESTROOMS TO THE RECEPTION | | | AREA DO YOU GO BACK OUT TO THE CITY SIDE | | | WALKS OR ARE THERE OTHER EGRESS PATHS | | | NOT INDICATED? | | | | | | 5)- S.S.553.79.(5A) THIS BUILDING | | | QUALIFIES AS A THRESHOLD BUILDING. | | | THE OCCUPANT LOAD OF THE GYM, 704 PEOPLE | | | QUALIFIES THIS BUILDING AS A THRESHOLD | | | BUILDING. | | | A) A THRESHOLD INSPECTION PLAN WILL | | | BE REQUIRED TO BE FILED WITH THE | | | BUILDING DEPARTMENT. THE ENFORC- | | | ING AGENCY SHALL REQUIRE A SPEC- | | | IAL INSPECTOR TO PREFORM STRUCTUR | | | AL INSPECTIONS ON A THRESHOLD | | | BUILDING PURSUANT TO A STRUCTURAL | | | INSPECTION PLAN PREPARED BY THE | | | ENGINEER OR ARCHITECT OF RECORD. | | | THE STRUCTURAL INSPECTION PLAN | | | MUST BE SUBMITTED TO AND APPROVED | | | BY THE ENFORCING AGENCY PRIOR TO | | | THE ISSUANCE OF THE PERMIT FOR | | | THE CONSTRUCTION OF THE THRESHOLD | | | BUILDING. | | | B)- THE THRESHOLD INSPECTOR SHALL | | | MEET WITH ASSISTANT BUILDING OFF- | | | ICAL DON NEELY FOR APPROVAL. | | | C)- (3) SETS OF PLANS WILLBE REQUIRED | | | FOR THE PERMITED SET. | | | | | | 5)- MISSINGINFORMATION, THE MINIMUM | | | BUILDING TYPE FOR OCCUPANCY SMALL ASSEM- | | | BLY? SEE SBC TABLE 500, SPRINKLERED/ | | | PROTECTED?SQ. FT. UNDER ROOF NOT GIVEN | | | | | | 6)- SBC 104.2.2.ADDITIONAL INFORMATIOIN, | | | SBC TABLE 600 PROPERTY LINE CAN NOT BE | | | ESTABLISHED, NO SURVEY, TABLE 600 % OF | | | OPENINGS MAY BE AN ISSUE. | | | | | | 7)- FOOTING SCHEDULE- MISSING T.E.-1 | | | ON FOOTING SCHEDULE, THERE IS A THICKEN | | | EDGE SECTION ON S-4 WHICH IS TO BE USED? | | | ONE IS 12" THE THER 16" VERTICALLY? | | | | | | 8)- MISSING IS INFORMATIONM FOR MC1/MC2 | | | 2103.1 ENGINEERED MASONARY DESIGN SHALL | | | COMPLY WITH ASCE 530- COLUMNS 5.6.1.4 | | | VERTICAL COLUMNS MINIMUM NUMBER OF BARS | | | SHALL BE FOUR. | | | | | | 9)- SBC TABLE 1606. IMPORTANCE FACTOR OF | | | 1.15 TO BE A USE FACTOR, OCCUPANT LOAD | | | =>300. | | | | | | 10)-SBC 1606.2.6.2 COMPONENTS & CLADDING | | | (3) PRODUCT APPROVAL REPORTS WILL BE RE- | | | QUIRED FOR THE FOLLOWING ITEMS: | | | A) EXTERIOR WINDOWS | | | B) EXTERIOR DOORS | | | C) ROLL UP OR GARAGE OVERHEAD DOORS | | | D) SKYLIGHTS | | | E) ROFFING ASSEMBLIES | | | | | | THE PLANS ARE LACKING SUFFICIENT INFORMA | | | TION TO DO A THOROUGH PLAN REVIEW AT | | | THIS TIME. THE QUESTIONS RAISED UNDER | | | THIS REVIEW WILL RAISE ADDITIONAL | | | QUESTIONS NOT ABLE TO BE ANSWER PRESENT- | | | LY. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-30 |
Time |
23:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-30 |
Time |
23:01 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE | | | NOT COMPLETED FOR COMPLET PLAN REVIEW | | | PLEASE NOTE THAT NO LOAD CALCULATIONS | | | WERE SUBMITTED? PLEASE SHOW CALCS AND | | | ALL CONTINUOUS LOADS AT 125%.215-5 215-2 | | | 230-42, 220 ETC | | | | | | 2)NOTE: PLEASE NOTE WIRE SIZES , CONDUIT | | | S ETC. | | | | | | PLEASE COMPLETE AND SUBMIT FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-10-30 |
Time |
08:48 |
Rev Time |
3.00 |
| Received By |
mamini |
Date |
2001-10-30 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | FAILED: | | | 1. INSUFFICENT INFORMATIONS FOR CIVIL | | | ENGINEERING REVIEW, PLEASE SUBMIT CIVIL | | | PLANS FOR OUR REVIEW AND APPROVAL. | | | 2. CIVIL PLANS SHOULD INCLUDE STORM | | | WATER CALCULATIONS FOR ENTIRE SITE, | | | UNDERGROUND UTILITIES, PAVEMENTS AND | | | POLLUTION PREVENTION PLANS. | | | 3. PLEASE INCLUDE PERVIOUS & IMPERVIOUS | | | CALCULATIONS FOR THE PROPOSED SITE. | | | 4. WE RECOMMEND A SEPARATE PERMIT | | | APPLICATIONS FOR SITE WORKS. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-23 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-23 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-23 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2001-10-23 00:00:00 | 1) BUILDING ADDRESS REQUIRED PER CITY | | | CODE 3343-00. | | | 2) PLEASE INDICATE FIRE HYDRANT | | | LOCATIONS ON SITE PLAN. | | | 3) NO FIRE SPRINKLER PLANS OR | | | HYDRAULIC CALCULATIONS PROVIDED WITH | | | PLANS. | | | 4) PLEASE PROVIDE MORE DETAILS ON | | | BLEACHERS PLANNED FOR USE. | | | 5) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | 6) A SMOKE DETECTOR IS REQUIRED ABOVE | | | FIRE ALARM CONTROL PANEL, HALL 105. | | | ALSO A REMOTE ANNUNCIATOR WILL | | | BE REQUIRED BECAUSE THE EAST ENTRY | | | PORCH MAY NOT BE FIRE RESCUE POINT | | | OF ENTRY. | | | 7) COULD NOT LOCATE KNOX-BOX. | | | 8) PROVISIONS ARE TO BE MADE FOR AT | | | LEAST TWO HANDICAPPED PERSONS. | | | 9) ANY COOKING THAT PRODUCES SMOKE OR | | | GREASE LADEN VAPORS IN CONCESSION AREA | | | TO HAVE AN APPROVED HOOD,DUCT,AND | | | EXTINGUISHING SYSTEM. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-03-25 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-03-25 |
Time |
13:35 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2002-03-25 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2002-03-25 00:00:00 | ***************DENIED******************* | | | | | | 1. OUTSIDE AIR CALCULATIONS FOR | | | GYMNASIUM AREA NEEDS TO BE 20 CFM PER | | | PER PER ASHRAE 62-89 TABLE 2 | | | 2. FIRE DAMPER LOCATIONS SHALL BE | | | INDICATED ON PLANS BY THE DESIGN | | | PROFESSIONAL PER 1997 SMC 610.6 | | | 3. PROVIDE TWO SETS OF RAISED SEAL, | | | SIGNED DRAWINGS FOR REVIEW | | | 4. CONDENSING UNITS ON ROOF SHALL BE ON | | | APPROVED STANDS MINIMUM 18" CLEARANCE | | | BETWEEN ROOF STRUCTURE AND BOTTOM OF | | | STAND SUPPORT. SUBMIT STAND DETAIL | | | INCLUDING ROOF ATTACHMENT AND ANCHOR | | | METHOD FOR UNITS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-21 |
Time |
15:58 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-03-21 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2002-03-21 00:00:00 | | | | PLEASE SEE COMMENTS DATED 11/05/01 | | | | | | TO HELP EXPEDITE PLAN REVIEW PROCESS | | | PLEASE PROVIDE WRITTEN RESPONSES TO | | | COMMENTS. | | | | | | PLANS ARE NOT SIGNED, SEALED & DATED BY | | | THE ENGINEER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-05 |
Time |
13:35 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-11-05 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2001-11-05 00:00:00 | ********************DENIED************** | | | | | | | | | PLAN SHEET LS1 NOTE #2, INDICATES 1 HR | | | FIRE RATED PARTITION AT MECH ROOMS 111, | | | 113, & 119.PLANS REFLECT MECH ROOMS | | | AS 111 AND 127.PLEASE CORRALATE PLANS | | | WITH PLAN NOTES. | | | | | | FIRE DAMPERS ARE NOT INDICATED ON PLANS. | | | PLEASE IDENTIFY ALL FIRE DAMPERS AND | | | ACCESS DOORS TO FIRE DAMPERS ON THE | | | PLAN SHEET. | | | | | | IF YOU HAVE ANY QUESTIONS. PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-25 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-03-25 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2002-03-25 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEW. - SHT A2-1 REST | | | ROOMS #118, #126 H/C STALL TO COMPLY FIG | | | 30(E) SIZE, LAYOUT, CLEAR FLOOR SPACE, | | | DOOR SWING SEC 4.22.2(1). | | | 2) FROM PREVIOUS REVIEW. - SHT P1,2,3 | | | SEC 303 MATERIALS FOR DRAIN, WASTE, & | | | VENT. WATER PIPE AND RAIN WATER LEADERS. | | | 3) FROM PREVIOUS REVIEW. - SHT P1,3 PLBG | | | NOTE (5) WHA, LOCATION, PLACEMENT AS PER | | | MFG INSTRUCTIONS, NOT AT THE HIGH POINT | | | OF SYSTEM. 607.8.2 | | | 4) FROM PREVIOUS REVIEW. - SHT P1 PLBG | | | NOTE (9) AND DETAIL FOR THE WATER HEATER | | | CONFLICT? SEC 104.3 | | | 5) FROM PREVIOUS REVIEW. - SHT P2 PUBLIC | | | REST RM'S #119, #121 FLOOR DRAINS REQUIR | | | ED, SEC 409.4 | | | 6) FROM PREVIOUS REVIEW. - SHT A3, P2 | | | PROVIDE CALCULATIONS FOR ROOF DRAINS, | | | OVERFLOW DRAINS. 1/2 VERTICAL WALLS, | | | DRAIN TERMINATION, PIPE SIZE. SEC 1108, | | | 1108.3, 1109 | | | 7) SHT M4 HUB DRAIN FOR CONDENSATE NOT | | | APPROVED. ALL INDIRECT WASTE SHALL DRAIN | | | TO AN APPROVED RECEPTOR, FLOOR SINK. | | | SEC 804.5 | | | 8) SHT P2 CONDENSATE LINE SHALL HAVE A | | | RELIEF VENT INSTALLED AS CONDENSATE LINE | | | EXITS BLDG AND TERMINATE 6" ABOVE GRADE | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-11 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-11-11 |
Time |
12:14 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-11 00:00:00 | PLUMBING PLAN REVIEW, DENIED | | | CODE REFERENCE STD PLBG CODE-94 | | | STANDARD MECHANICAL CODE-97 | | | FLORIDA ACCESSIBILITY CODE-97 | | | (1A) SHT A2-1 REST RM'S #118,#126 H/C | | | STALL TO COMPLY FIG 30(E) SIZE, LAYOUT. | | | DOOR SWING SEC 4.22.2(1). | | | (1B) ENTRY TO MEN & WOMENS REST RM'S TO | | | COMPLY W/SEC 4.13.6 & FIG. 25 DOOR SWING | | | (2) SHT P1,2,3 SEC 303 MATERIALS, LIST | | | TYPES OF MATERIALS FOR DRAIN WASTE,VENT. | | | WATER PIPE AND RAIN WATER LEADERS. | | | (3)SHT P1,3 PLBG NOTE (5) WHA, LOCATION, | | | PLACEMENT AS PER MFG INSTRUCTIONS, NOT | | | AT THE HIGH POINT OF SYSTEM.607.8.2 | | | (4) SHT P1,PLBG NOTE (9) AND DETAIL FOR | | | THE WATER HEATER, CONFLICT? SEC 104.3 | | | (5) SHT P1 PLBG NOTE (10) TYPE OF BACK | | | FLOW PREVENTER SHALL BE A RPZV SEC 606. | | | (6) SHT P2 PUBLIC REST RM'S #119.#121 | | | FLR DRAINS REQUIRED, SEC 409.4 | | | (7) SHT A3,P2PROVIDE CALCULATIONS FOR | | | ROOF DRAINS,OVERFLO DRAINS, 1/2 VERTICAL | | | WALLS, DRAIN TERMINATION, PIPE SIZES. | | | SEC 1108,1108.3, 1109 | | | (8) SHT A3,RTU UNITS,SHOW TERMINATION OF | | | A/C CONDENSATE.SMC-97,SEC 304.8.3 | | | (9) SHT M3, MECHANICAL RM #111,#117, | | | REFERENCE TO LARGE SCALE MECHANICAL PLAN | | | SHT M-4,NOT INCLUDED, SHOW THE TERMIN- | | | ATION OF AHU A/C CONDENSATE SEC 304.8.3 | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-22 |
Time |
14:45 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|