Plan Review Details - Permit 01101258
Plan Review Stops For Permit 01101258
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-16 Cont ID  
Sent By mcarsill Date 2001-11-16 Time 09:13 Rev Time 0.00
Received By mcarsill Date 2001-11-16 Time 09:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By mcarsill Date 2001-10-29 Time 12:36 Rev Time 0.00
Received By mcarsill Date 2001-10-29 Time 12:36 Sent To  
Notes
2001-10-29 00:00:00PLANS THAT WERE SUBMITTED ARE DIFFICULT
 TO UNDERSTAND. PROVIDE APPROPRIATE
 PLANS FOR REVIEW FOR THE ITEMS THAT
 WANT TO BE PERMITTED. THE DRAWINGS
 SUBMITTED APPEAR TO BE VERY OLD
 AND HAVE AS-BUILTS STAMPED ON THEM.
 PLANS ALSO HAVE TITLE BLOCKS AND
 THE DRAWINGS ARE NOT SIGNED AND
 SEALED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-13 Cont ID  
Sent By pkrauss Date 2001-11-13 Time 12:32 Rev Time 0.50
Received By pkrauss Date 2001-11-13 Time 12:32 Sent To  
Notes
2001-11-13 00:00:00*******************PROVISO**************
  
  
 1.EQUIPMENT RACK ON ROOF SHALL BE A
 MINIMUM OF 18"FOR ROOF SURFACE TO
 BOTTOM OF SUPPORT RAIL.PLEASE
 SUBMIT MANUFACTURER SUBMITTAL DATA
 FOR REVIEW.
  
 2.FIRE DAMPERS SHALL COMPLY WITH UL
 555 AND SHALL BEAR THE LABLE OF AN
 APPROVED TESTING AGENCY.
  
 FIRE DAMPERS SHALL HAVE AN ACCESS
 DOOR FOR PROPER MAINTENANCE AND
 RESETTING (1997 SMC 610.5)
  
 2 INSPECTIONS REQUIRED -
  
 FIRST WHEN DRYWALL AND FRAME
 WORK IS INSTALLED.
 SECOND WHEN ANGLE IS ATTACHED
 TO DUCTWORK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-25 Cont ID  
Sent By pkrauss Date 2001-10-25 Time 12:07 Rev Time 1.15
Received By pkrauss Date 2001-10-25 Time 11:33 Sent To  
Notes
2001-10-25 00:00:00******************DENIED****************
  
  
 PLANS HAVE ENGINEER AND ARCHITECT TITLE
 BLOCKS WITH NO SEAL, SIGNATURE OR DATES
 AS REQUIRED BY FLORIDA STATUE (CHAPTER
 471).
  
 REVIEW NOTES FROM SUBMITTAL OF MASTER
 PERMIT 01060851
  
 1.PROVIDE LOCATION OF EXHAUST
 TERMINATION FOR THE FUME HOOD.
 TERMINATION SHALL COMPLY WITH 1997
 SMC 506.1, A MINIMUM OF 10' FROM
 ANY ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, WINDOW, DOOR
 OR AIR INTAKE OPENING AND SHALL BE
 LOCATED AT LEAST 10' FROM ADJOINING
 GRADE LEVEL.
  
 2.PROVIDE INFORMATION ON EXHUAST FAN
 TO FUME HOOD.
  
 3.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 501.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.