Plan Review Details - Permit 01101258
| Plan Review Stops For Permit 01101258 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-16 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-16 |
Time |
09:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-29 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-29 |
Time |
12:36 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | PLANS THAT WERE SUBMITTED ARE DIFFICULT | | | TO UNDERSTAND. PROVIDE APPROPRIATE | | | PLANS FOR REVIEW FOR THE ITEMS THAT | | | WANT TO BE PERMITTED. THE DRAWINGS | | | SUBMITTED APPEAR TO BE VERY OLD | | | AND HAVE AS-BUILTS STAMPED ON THEM. | | | PLANS ALSO HAVE TITLE BLOCKS AND | | | THE DRAWINGS ARE NOT SIGNED AND | | | SEALED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-13 |
Time |
12:32 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-11-13 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2001-11-13 00:00:00 | *******************PROVISO************** | | | | | | | | | 1.EQUIPMENT RACK ON ROOF SHALL BE A | | | MINIMUM OF 18"FOR ROOF SURFACE TO | | | BOTTOM OF SUPPORT RAIL.PLEASE | | | SUBMIT MANUFACTURER SUBMITTAL DATA | | | FOR REVIEW. | | | | | | 2.FIRE DAMPERS SHALL COMPLY WITH UL | | | 555 AND SHALL BEAR THE LABLE OF AN | | | APPROVED TESTING AGENCY. | | | | | | FIRE DAMPERS SHALL HAVE AN ACCESS | | | DOOR FOR PROPER MAINTENANCE AND | | | RESETTING (1997 SMC 610.5) | | | | | | 2 INSPECTIONS REQUIRED - | | | | | | FIRST WHEN DRYWALL AND FRAME | | | WORK IS INSTALLED. | | | SECOND WHEN ANGLE IS ATTACHED | | | TO DUCTWORK. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-25 |
Time |
12:07 |
Rev Time |
1.15 |
| Received By |
pkrauss |
Date |
2001-10-25 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2001-10-25 00:00:00 | ******************DENIED**************** | | | | | | | | | PLANS HAVE ENGINEER AND ARCHITECT TITLE | | | BLOCKS WITH NO SEAL, SIGNATURE OR DATES | | | AS REQUIRED BY FLORIDA STATUE (CHAPTER | | | 471). | | | | | | REVIEW NOTES FROM SUBMITTAL OF MASTER | | | PERMIT 01060851 | | | | | | 1.PROVIDE LOCATION OF EXHAUST | | | TERMINATION FOR THE FUME HOOD. | | | TERMINATION SHALL COMPLY WITH 1997 | | | SMC 506.1, A MINIMUM OF 10' FROM | | | ANY ADJACENT BUILDING, PARKING AREA, | | | ADJACENT PROPERTY LINE, WINDOW, DOOR | | | OR AIR INTAKE OPENING AND SHALL BE | | | LOCATED AT LEAST 10' FROM ADJOINING | | | GRADE LEVEL. | | | | | | 2.PROVIDE INFORMATION ON EXHUAST FAN | | | TO FUME HOOD. | | | | | | 3.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 501.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|