Plan Review Details - Permit 01101224
Plan Review Stops For Permit 01101224
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-11-18 Cont ID  
Sent By jwitmer Date 2003-11-18 Time 10:31 Rev Time 2.00
Received By jwitmer Date 2003-11-18 Time 10:31 Sent To  
Notes
2003-11-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 01101224
 ADD: 421 31ST STREET
 CONT: MARION
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 REVISION: 16"X16" COLUMNS
 ACTION: DENIED
  
 1) NOT COVERED UNDER BUILDING PERMIT,
 IS COVERED UNDER FENCE PERMIT 03092009
  
 2) DENIED BY ZONING & HISTORICS, COLUMN
 HEIGHT NOT MORE THAN 4'-0" TALL (OVER-
 ALL HEIGHT)
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-05-29 Cont ID  
Sent By jwitmer Date 2002-05-29 Time 16:49 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-29 00:00:00BUILDING PROVISO;
 OK TO PROCEED WITH THE REPLACEMENT OF
 FOOTERS.
  
 UTILITY ROOM SHALL REQUIRE HISTORICAL
 BOARD APPROVAL
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-11 Cont ID  
Sent By jwitmer Date 2002-01-11 Time 08:13 Rev Time 1.00
Received By jwitmer Date 2002-01-11 Time 08:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-12-31 Cont ID  
Sent By jwitmer Date 2001-12-31 Time 12:08 Rev Time 2.00
Received By jwitmer Date 2001-12-31 Time 10:38 Sent To  
Notes
2001-12-31 00:00:00PLAN REVIEW
 PERMIT # 01101224
 421 31ST ST
 CONT: MARION CONSTRUCTION
 TEL: 659-5292
  
 1)- CONTRACTOR TO SUBMIT PLANS TO COUNTY
 FOR IMPACT FEE ASSESSMENT.
  
 2)- NEW PLANS ARE TO BE SUBMITTED TO
 HISTORICAL DEPARTMENT FOR STAMPING
 APPROVAL.
  
 3)- STATE RADON & TRAINING CHARGE $11.98
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-19 Cont ID  
Sent By jwitmer Date 2001-11-19 Time 13:53 Rev Time 4.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-11-19 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01101224
 421 31ST STREET
 CONT: MARION CONST.
 TEL: 659-5192
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SHEET A100: EXTERIOR DOOR OPENINGS
 VS. LANDINGS SEE SBC 1012.1.6.
 B) FACTORY BAR-B-Q: SBC 2808 SHALL
 REQUIRE THE MANUFACTURES SPEC.(2 COPIES)
 C) EXTERIOR FIREPLACE, ADDITIONAL
 INFORMATIOIN REQUIRED, FACTORY BUILT OR
 MASONARY?
 D) GREAT ROOM: 125 MB TUH, FIREPLACE,
 ADDITIONAL INFORMATION REQUIRED, FACTORY
 BUILT IF SO MUST COMPLY WITH UL 127 PRO-
 VIDE MANUFACTURES SPEC. IF MASONARY PROV
 IDE INFORMATION ON FIRE BOX SIZE &
 CHIMNEY FLUE SIZE, MISSING CHIMNEY ON
 ELEVATION, SHOW COMPLIANCE WITH SBC2804.
 2.4, SEE CHIMNEY HEIGTH REQUIREMENTS.
 E) FIREPLACES FRESH AIR INTAKE REQUIREME
 NTS, & FIREPLACE DOORS REQUIREMENTS SEE
 ENERGY CODE.
  
 2)- SHEET 301:
 A) STEM WALL TO LOW SEE 2304.2.5*
 STUCCO STOP REQUIREMENTS 6" CLEARENCE
 BETWEEN STUCCO, SHEETHING AND GROUND.
 B) DETAIL "C" PORTE COCHERE
 1) WALL SECTION VS (2X6 POST/ 4)?
 SBC 2308.1.5 REQUIRES TOP/ BOTTOM
 PLATES?
 2) WHAT TYPE OF ANCHOR IS TO BE USED
 IN STEM WALL CONSTRUCTION?
 3) WHAT LENGTH OF MICROLAM IS TO BE
 USED? HOW MANY SUPPORTS?
  
 3)- MISSINGROOF FRAMING PLAN, A101
 HOLDOWN SCHEDULE DOESN'T INDICATETHE
 LOCATIONS OF THESE ANCHORS OR THE MAGNIT
 UDE OF FORCES TO BE RESISTED?
  
 4)- A101 NEW BEDROOM # 3 WINDOWS DO NOT
 MEET THE EGRESS REQUIREMENTS OF 5.7 SQ.
 FT. OPEN AREA. SBC 1005.4.4. ARE THE
 WINDOWS IN THE OTHER SLEEPING ROOMS
 BEING REPLACED? IF SO THEY ALSO WILL
 NEED TO COMPLY!
  
 5)- BATH #2 WINDOW AND SHOWER DOOR,
 HAZARDOUS LOCATION SBC 2405.2.1.
  
 6)- MISSING PRODUCT APPROVAL REPORT FOR
 ROOFING ASSEMBLIES, TESTED FOR 110 MPH.
 PROVIDE 2 COPIES SBCCI OR DADE COUNTY
 REPORTS ARE ACCEPTABLE.
  
 7)- PLANS WILL BE REQUIRED TO HAVE
 PALM BEACH COUNTY IMPACT FEES STAMP
 BEFORE PERMIT ISSUANCE.
  
 8)- SHOW COMPLIANCE WITH OPENING VENTI-
 LATION AS IN 1804.6.2.1.(3) TAKE REDUCTI
 ON FOR VAPOR BARRIER.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-03-22 Cont ID  
Sent By btrobaug Date 2004-03-22 Time 07:52 Rev Time 0.50
Received By btrobaug Date 2004-03-22 Time 07:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-04-08 Cont ID  
Sent By csiegber Date 2004-03-16 Time 15:20 Rev Time 1.00
Received By btrobaug Date 2003-04-08 Time 06:35 Sent To P
Notes
2003-04-08 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND MAKE NECESSARY CHANGES
 ON PLANS AND RESUBMIT FOR REVIEW.
  
 1} PANEL "A" MUST COMPLY WITH 230-70 WPB
 AMMENDMENTS.LOCATION OF THE DISCONNECT
 AT NEAREST POINT OF ENTRY,SEE NOTE #3
 LAST REVIEW.GROUND PER 250-32.
  
 2} THE OVEN LISTED ON THE LOAD CALCS
 MUST COMPLY WITH TABLE 220-19,OR
 CORRESPONDING NOTES. PLEASE CLARIFY HOW
 5KW WAS DERIVED.
  
 3} PANEL "B" IS REQUIRED TO HAVE A NAIN
 MEANS OF DICONNECT PER 230-71.
  
 4} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-08-14 Cont ID  
Sent By sthyng Date 2003-03-25 Time 09:58 Rev Time 0.00
Received By btrobaug Date 2002-08-14 Time 08:42 Sent To P
Notes
2002-08-14 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW
  
 1} THE REVISION SUBMITTED SHOWS THE
 METER MOVED OFF THE HOUSE TO A REMOTE
 LOCATION.PLEASE REDRAW THE RISER TO
 INDICATE THE TYPE OF GROUNDING SYSTEM
 AT THIS LOCATION,PLEASE NOTE THAT THE
 GEC SYSTEM IN 250-50 ARE AVAILABLE AND
 MUST BE USED AS INDICATED.
  
 2} PLEASE CLARIFY THAT PANEL "B" IS
 STILL AN MLO AND BEING FED BACK FROM
 PANEL "A"? PLEASE NOTE BURIAL DEPTHS
 REQUIRE INSPECTIONS.
  
 3} PANEL "A" MUST COMPLY WITH 230-70(A)
 NEC AND WEST PALM BEACH AMMENDMENTS,
 LOCATION OF DISCONNECT AT NEAREST POINT
 OF ENTRY,MAXIMUM OF 8' OF CONDUCTORS &
 NOT IN BATHROOM AS IT APPEARS ON THE
 DRAWING PLEASE CLARIFY.
  
 4} INDICATE THE AIC RATING OF THE MAIN
 DISCONNECT PER 110-9 & 110-10.
  
 5} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.LIST SAME ON
 PANEL SCHEDULE.
  
 6} NOTE THAT THE WATER HEATER IS LISTED
 @ 6000VA/240V ON THE CALC'S AND SHOWN
 AS 4AMPS/120V ON THE SCHEDULE, PLEASE
 CLARIFY.
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8392

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-12-20 Cont ID  
Sent By dpalmer Date 2001-12-20 Time 07:00 Rev Time 0.00
Received By dpalmer Date 2001-12-20 Time 06:48 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 14:12 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 14:12 Sent To  
Notes
2001-11-05 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PANELS ARE SHOWN AT 22,000, WHAT ABOUT
 MAIN? IS THE 22,000 FOR BREAKERS IN
 PANELS ALSO?
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 4) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 NOTE; MISSING IN BEDROOM #3 ALSO, SD
 SHOWN NEAR KITCHEN DOOR NEEDS TO BE A
 MIN OF 3` NFPA-72 2-5.2.1.6
  
 5)NOTE: PLEASE NOTE THE MISSING SMALL
 APPLIANCE CIRCUITS ON PANEL SCHEDULES.
 210-11-C-1
  
 6)NOTE: PLEASE NOTE THAT ONLY ONE PANEL
 IS SHOWN ON PLANS? RISER SHOWS TWO?
  
 7)PLEASE NOTE THAT THE ELECTRICAL PANEL
 IS SHOWN IN BATHROOM. THIS IS NOT
 PERMITTED PER 240-24E. PLEASE NOTE THAT
 PANEL CLEARENCE PER 110-26
  
 8)NOTE:PLEASE NOTE THAT PANEL SCHEDULES
 DO NOT CORRELATE>>> "A" SHOWS 3-AHU`S
 AND "B" SHOWS CU`S 1,2A,2B AND 3???
 PLEASE CLARIFY.
  
 9)NOTE: PLEASE SHOW ALL AHU`S AND CU`S
 ON PLANS AND DISCONNECTS PER 440-11 AND
 RECEPTS FOR SERVICE.
  
 10)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS BETWEEN MAIN AND
 PANEL "A". 250-122
  
 11)NOTE: PLEASE CLARIFY WHERE PANEL "B"
 IS BEING FED FROM? PANEL SCHEDULE "A"
 DOES NOT HAVE PANEL "B" ON SCHED.
  
 12)NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 GREAT ROOM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 15:20 Sent To E
Notes
2004-03-16 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-17 Time 09:04 Rev Time 0.00
Received By csiegber Date 2003-11-17 Time 09:04 Sent To P
Notes
2003-11-17 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-03 Time 10:43 Rev Time 0.00
Received By csiegber Date 2003-11-03 Time 10:43 Sent To  
Notes
2003-11-03 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-12 Cont ID  
Sent By shernand Date 2003-06-12 Time 11:25 Rev Time 0.00
Received By shernand Date 2003-06-12 Time 11:25 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-25 Cont ID  
Sent By sthyng Date 2003-03-25 Time 09:58 Rev Time 0.00
Received By sthyng Date 2003-03-25 Time 09:57 Sent To E
Notes
2003-03-25 00:00:00TO BT DESK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-04-09 Cont ID  
Sent By pkrauss Date 2003-04-09 Time 13:09 Rev Time 0.40
Received By pkrauss Date 2003-04-09 Time 11:45 Sent To  
Notes
2003-04-09 00:00:00REFERENCE NOTE ON PLANS SHEET M100,
 "4 INCH FLUE PIPING FOR GAS WATER
 HEATER.MOUNT 7" (MIN) ABOVE EXTERIOR
 GRADE.ORIGINAL SUBMITTAL INDICATES 7
 FT.PLEASE VERIFY.
  
 ADDITIONAL PERMIT REQUIRED FOR GAS,
 PLEASE PROVIDE PLANS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-20 Cont ID  
Sent By kstevens Date 2003-04-08 Time 09:51 Rev Time 0.40
Received By pkrauss Date 2002-08-20 Time 14:36 Sent To P
Notes
2002-08-20 00:00:00PROVISO:
  
 CALL FOR INSPECTION PRIOR TO COVERING
 THE "SPUNSTRAND" DUCTWORK (UNDERGROUND).
  
 PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS ON THE JOBSITE FOR
 INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-12-27 Cont ID  
Sent By ndenmark Date 2001-12-27 Time 11:23 Rev Time 0.33
Received By ndenmark Date 2001-12-27 Time 11:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-08 Cont ID  
Sent By pkrauss Date 2001-11-08 Time 09:28 Rev Time 1.00
Received By pkrauss Date 2001-11-08 Time 08:02 Sent To  
Notes
2001-11-08 00:00:00*******************DENIED***************
  
  
 1.LOCATION OF TOILET EXHAUST ON THE
 FIRST FLOOR.PLAN INDICATES EXHAUST
 DUCT IS RUNNING IN CRAWL SPACE TO
 WALL CAP.PLEASE SPECIFY MATERIAL
 USED FOR EXHAUST DUCT.EXHAUST
 TERMINATION SHALL BE 10' FROM ANY
 WINDOW, DOOR OR FRESH AIR INTAKE AS
 PER 1997 SMC 506.1 OR 2' ABOVE FRESH
 AIR INTAKE.
  
 2.DUCT IN CRAWL SPACE UNDER FIRST
 FLOOR SHALL NOT BE INSTALLED IN OR
 WITHIN 4 INCHES OF THE GROUND AS PER
 1997 SMC 605.4.
  
 3.PLEASE SPECIFY MATERIAL AND R-VALUE
 OF ALL DUCTWORK BEING INSTALLED.
  
 4.INDICATE SIZE LOCATION OF LIQUID AND
 SUCTION REFRIGERANT LINES.
  
 5.INDICATE LOCATION OF CONDENSER
 UNITS.PLAN SHEET A000 SHOWS COND.
 UNITS IN EXCESS OF 30' FROM THE
 HOUSE.PLEASE REFER TO MANUFACTURER
 INSTALLATION INSTRUCTIONS FOR LINE
 SIZE FOR THIS DISTANCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 8 Status F Date 2003-12-01 Cont ID  
Sent By kstevens Date 2003-12-01 Time 13:21 Rev Time 1.25
Received By kstevens Date 2003-12-01 Time 13:21 Sent To  
Notes
2003-12-01 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P400, PIPE SIZES FOR GAS LINES
 ARE INCORRECT. PLEASE CHANGES PIPES
 SIZES TO CORRECT PIPE SIZES SHOWN IN RED
 ON REVISION. ALSO SHOW ALL VALVES AT THE
 APPLIANCES.
 2) PER RULING BY THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS, A SIGNATURE IS
 REQUIRED ON SIGNED AND SEALED PLANS. IN-
 ITIALS ARE NOT ACCEPTED. 61G15-23.002(1)
 3) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THORUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS, AND CERTIFICATE OF AUTH-
 ORIZATION NUMBER OF THE ENGINEERING BUS-
 INESS ON EACH SHEET. 61G15-23.002(2)
 SEE ATTACHED SHEET... FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2003-06-18 Cont ID  
Sent By csiegber Date 2003-11-17 Time 09:04 Rev Time 1.00
Received By kstevens Date 2003-06-18 Time 17:28 Sent To  
Notes
2003-06-18 00:00:00REVISION OK - GAS PIPING CHANGED
 BTU'S / DISTANCE CHANGED

Review Stop P PLUMBING
Rev No 6 Status F Date 2003-06-17 Cont ID  
Sent By kstevens Date 2003-06-17 Time 09:56 Rev Time 1.50
Received By kstevens Date 2003-06-17 Time 09:55 Sent To  
Notes
2003-06-17 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) SHT P400 NATURAL GAS RISER DOES NOT
 REFLECT THE GAS APPLIANCE SCHEDULE.
 RISER SHOWS 200MBTUH FOR BBQ AND SCHED.
 SHOWS 69MBTUH. RISER SHOWS 200MBTUH FOR
 THE RANGE AND SCHED. SHOWS 144MBTUH.
 PLEASE CLAIRFY.
 2) PLEASE INDICATE TYPE OF PIPE FOR EACH
 SECTION OF THE RISER. ALSO SHOW ALL PIPE
 SIZES FOR THE RISER SECTIONS AND DROPS.
 3) SHT P100 INDICATES REVISIONS #4 & #5.
 PREVIOUS REVISION SHOWS #3 TO BE THE
 LAST REVISION. #4 NOT FOUND ON LATEST
 REVISION. PLEASE CLAIRFY.
 4) SHT P400 INDICATES REVISIONS #2 & #3.
 PREVIOUS REVISION SHOWS #1 TO BE THE
 LAST REVISION. #2 NOT FOUND ON LATEST
 REVISION. PLEASE CLAIRFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-06-12 Time 11:25 Rev Time 0.50
Received By kstevens Date 2003-04-08 Time 09:50 Sent To M
Notes
2003-04-08 00:00:00REVISION OK - CHANGED TUB TO SHR. SHR.
 TO TUB - CHANGED F.D. TO FLOOR SINK -
 REROUTE CONDENSATE LINE 2ND FLOOR.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-08-22 Cont ID  
Sent By btrobaug Date 2003-04-08 Time 08:02 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-08-22 00:00:00REVISION, PROVISO PER DARCY(DAM), PES

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-06 Cont ID  
Sent By pkrauss Date 2002-08-20 Time 16:01 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-06 00:00:00PROVISO: SEPERATE PLANS, PERMIT FOR GAS.
 ADDRESS ALL ITEMS ON GAS APPLICATION
 PERMIT REQUIRMENTS.PES

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-26 Cont ID  
Sent By jleech Date 2001-12-26 Time 13:40 Rev Time 2.00
Received By jleech Date 2001-12-26 Time 13:39 Sent To  
Notes
2001-12-26 00:00:00DENIED;
  
 PAGE P301 GAS RISER;
 1.LONGEST RUN IS 85',G-6,3,2. USING
 TABLE 305.4A IN THE 97 SMC.
 2.PLEASE DELETE GAS RISER DIAGRAM OR
 MAKE REQUIRED CHANGES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-06 Cont ID  
Sent By dpalmer Date 2001-12-20 Time 07:00 Rev Time 1.50
Received By kstevens Date 2001-11-06 Time 10:35 Sent To  
Notes
2001-11-06 00:00:00DENIED
 REFERENCE: SPC-94 - SGC-97
  
 1) PAGES A100 & P100 & P301. OUTSIDE
 SHOWER SHALL NOT HAVE A DRAIN. PLEASE
 REMOVE, NOT APPROVED PER UTILITY ORD.
 2) PAGE A101 PLEASE PROVIDE ROOF DRAIN-
 AGE CALCULATIONS FOR PRIMARY AND SECOND-
 ARY DRAINS USING SPC SEC 1108 AND 1109.
 ADD 1/2 AREA OF VERTICAL WALLS/PARAPET
 WALLS PER 1108.3. ALSO ADD ANY AREA OF
 ROOFS THAT DRAIN ONTO NEW ROOFS.
 PLEASE SHOW DETAILS OF PRIMARY AND SEC-
 ONDARY DRAINS. - ALSO PLEASE SUPPLY
 CALCULATIONS FOR EXISTING ROOF - SHOW
 PRIMARY AND SECONDARY DRAINS WITH SIZES.
 3) PAGE P300 DRYWELL DETAIL, OVERFLOW
 SHALL BE TIED INTO DRAIN LINE NOT DRY-
 WELL.
 4) PAGE P300 WATER HEATER DETAIL, BOTTOM
 FED WATER HEATER SHALL HAVE A N36 VAC-
 BREAKER INSTALLED ON SUPPLY SIDE OF W/
 HEATER. - EMERGENCY PAN DRAIN TO BE 1"
 5) PAGE P300 INDIRECT WASTE FROM ICE
 MACHINE SHALL DRAIN INTO A FLOOR SINK
 NOT FLOOR DRAIN AS SHOWN. SPC SEC 804.5
 6) PAGE P300 WASHER DETAIL CLEAN OUT RE-
 QUIRED AT 4' AFF ON VENT STACK
 7) PAGE P300 SEPARATE GAS PERMIT REQUIR-
 ED. SEE ATTACHED GAS PERMIT APPLICATION
 REQUIREMENT SHEET FOR FURTHER INFORMAT-
 ION REQUIRED. SUPPLY INFO FOR NUMBERS
 THAT ARE CIRCLED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-29 Cont ID  
Sent By sgraham Date 2001-10-29 Time 11:51 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***