| Plan Review Stops For Permit 01101224 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2003-11-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-11-18 |
Time |
10:31 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2003-11-18 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2003-11-18 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 01101224 | | | ADD: 421 31ST STREET | | | CONT: MARION | | | TEL: (561)###-#### | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | REVISION: 16"X16" COLUMNS | | | ACTION: DENIED | | | | | | 1) NOT COVERED UNDER BUILDING PERMIT, | | | IS COVERED UNDER FENCE PERMIT 03092009 | | | | | | 2) DENIED BY ZONING & HISTORICS, COLUMN | | | HEIGHT NOT MORE THAN 4'-0" TALL (OVER- | | | ALL HEIGHT) | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-05-29 |
Time |
16:49 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-29 00:00:00 | BUILDING PROVISO; | | | OK TO PROCEED WITH THE REPLACEMENT OF | | | FOOTERS. | | | | | | UTILITY ROOM SHALL REQUIRE HISTORICAL | | | BOARD APPROVAL | | | ANY QUESTIONS PLEASE CALL, | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 | | | JIM WITMER | | | BUILDING PLAN REVIEW | | | DEPARTMENT OF CONSTRUCTION SERVICES | | | CITY OF WEST PALM BEACH | | | (561) 659-8096 EXT. 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-01-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-11 |
Time |
08:13 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2002-01-11 |
Time |
08:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-31 |
Time |
12:08 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2001-12-31 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2001-12-31 00:00:00 | PLAN REVIEW | | | PERMIT # 01101224 | | | 421 31ST ST | | | CONT: MARION CONSTRUCTION | | | TEL: 659-5292 | | | | | | 1)- CONTRACTOR TO SUBMIT PLANS TO COUNTY | | | FOR IMPACT FEE ASSESSMENT. | | | | | | 2)- NEW PLANS ARE TO BE SUBMITTED TO | | | HISTORICAL DEPARTMENT FOR STAMPING | | | APPROVAL. | | | | | | 3)- STATE RADON & TRAINING CHARGE $11.98 | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-19 |
Time |
13:53 |
Rev Time |
4.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 01101224 | | | 421 31ST STREET | | | CONT: MARION CONST. | | | TEL: 659-5192 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- SHEET A100: EXTERIOR DOOR OPENINGS | | | VS. LANDINGS SEE SBC 1012.1.6. | | | B) FACTORY BAR-B-Q: SBC 2808 SHALL | | | REQUIRE THE MANUFACTURES SPEC.(2 COPIES) | | | C) EXTERIOR FIREPLACE, ADDITIONAL | | | INFORMATIOIN REQUIRED, FACTORY BUILT OR | | | MASONARY? | | | D) GREAT ROOM: 125 MB TUH, FIREPLACE, | | | ADDITIONAL INFORMATION REQUIRED, FACTORY | | | BUILT IF SO MUST COMPLY WITH UL 127 PRO- | | | VIDE MANUFACTURES SPEC. IF MASONARY PROV | | | IDE INFORMATION ON FIRE BOX SIZE & | | | CHIMNEY FLUE SIZE, MISSING CHIMNEY ON | | | ELEVATION, SHOW COMPLIANCE WITH SBC2804. | | | 2.4, SEE CHIMNEY HEIGTH REQUIREMENTS. | | | E) FIREPLACES FRESH AIR INTAKE REQUIREME | | | NTS, & FIREPLACE DOORS REQUIREMENTS SEE | | | ENERGY CODE. | | | | | | 2)- SHEET 301: | | | A) STEM WALL TO LOW SEE 2304.2.5* | | | STUCCO STOP REQUIREMENTS 6" CLEARENCE | | | BETWEEN STUCCO, SHEETHING AND GROUND. | | | B) DETAIL "C" PORTE COCHERE | | | 1) WALL SECTION VS (2X6 POST/ 4)? | | | SBC 2308.1.5 REQUIRES TOP/ BOTTOM | | | PLATES? | | | 2) WHAT TYPE OF ANCHOR IS TO BE USED | | | IN STEM WALL CONSTRUCTION? | | | 3) WHAT LENGTH OF MICROLAM IS TO BE | | | USED? HOW MANY SUPPORTS? | | | | | | 3)- MISSINGROOF FRAMING PLAN, A101 | | | HOLDOWN SCHEDULE DOESN'T INDICATETHE | | | LOCATIONS OF THESE ANCHORS OR THE MAGNIT | | | UDE OF FORCES TO BE RESISTED? | | | | | | 4)- A101 NEW BEDROOM # 3 WINDOWS DO NOT | | | MEET THE EGRESS REQUIREMENTS OF 5.7 SQ. | | | FT. OPEN AREA. SBC 1005.4.4. ARE THE | | | WINDOWS IN THE OTHER SLEEPING ROOMS | | | BEING REPLACED? IF SO THEY ALSO WILL | | | NEED TO COMPLY! | | | | | | 5)- BATH #2 WINDOW AND SHOWER DOOR, | | | HAZARDOUS LOCATION SBC 2405.2.1. | | | | | | 6)- MISSING PRODUCT APPROVAL REPORT FOR | | | ROOFING ASSEMBLIES, TESTED FOR 110 MPH. | | | PROVIDE 2 COPIES SBCCI OR DADE COUNTY | | | REPORTS ARE ACCEPTABLE. | | | | | | 7)- PLANS WILL BE REQUIRED TO HAVE | | | PALM BEACH COUNTY IMPACT FEES STAMP | | | BEFORE PERMIT ISSUANCE. | | | | | | 8)- SHOW COMPLIANCE WITH OPENING VENTI- | | | LATION AS IN 1804.6.2.1.(3) TAKE REDUCTI | | | ON FOR VAPOR BARRIER. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2004-03-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-03-22 |
Time |
07:52 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-03-22 |
Time |
07:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-04-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-16 |
Time |
15:20 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-04-08 |
Time |
06:35 |
Sent To |
P |
|
| Notes |
| 2003-04-08 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND MAKE NECESSARY CHANGES | | | ON PLANS AND RESUBMIT FOR REVIEW. | | | | | | 1} PANEL "A" MUST COMPLY WITH 230-70 WPB | | | AMMENDMENTS.LOCATION OF THE DISCONNECT | | | AT NEAREST POINT OF ENTRY,SEE NOTE #3 | | | LAST REVIEW.GROUND PER 250-32. | | | | | | 2} THE OVEN LISTED ON THE LOAD CALCS | | | MUST COMPLY WITH TABLE 220-19,OR | | | CORRESPONDING NOTES. PLEASE CLARIFY HOW | | | 5KW WAS DERIVED. | | | | | | 3} PANEL "B" IS REQUIRED TO HAVE A NAIN | | | MEANS OF DICONNECT PER 230-71. | | | | | | 4} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-08-14 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-25 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-08-14 |
Time |
08:42 |
Sent To |
P |
|
| Notes |
| 2002-08-14 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | ON THE PLANS AND RESUBMIT FOR REVIEW | | | | | | 1} THE REVISION SUBMITTED SHOWS THE | | | METER MOVED OFF THE HOUSE TO A REMOTE | | | LOCATION.PLEASE REDRAW THE RISER TO | | | INDICATE THE TYPE OF GROUNDING SYSTEM | | | AT THIS LOCATION,PLEASE NOTE THAT THE | | | GEC SYSTEM IN 250-50 ARE AVAILABLE AND | | | MUST BE USED AS INDICATED. | | | | | | 2} PLEASE CLARIFY THAT PANEL "B" IS | | | STILL AN MLO AND BEING FED BACK FROM | | | PANEL "A"? PLEASE NOTE BURIAL DEPTHS | | | REQUIRE INSPECTIONS. | | | | | | 3} PANEL "A" MUST COMPLY WITH 230-70(A) | | | NEC AND WEST PALM BEACH AMMENDMENTS, | | | LOCATION OF DISCONNECT AT NEAREST POINT | | | OF ENTRY,MAXIMUM OF 8' OF CONDUCTORS & | | | NOT IN BATHROOM AS IT APPEARS ON THE | | | DRAWING PLEASE CLARIFY. | | | | | | 4} INDICATE THE AIC RATING OF THE MAIN | | | DISCONNECT PER 110-9 & 110-10. | | | | | | 5} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.LIST SAME ON | | | PANEL SCHEDULE. | | | | | | 6} NOTE THAT THE WATER HEATER IS LISTED | | | @ 6000VA/240V ON THE CALC'S AND SHOWN | | | AS 4AMPS/120V ON THE SCHEDULE, PLEASE | | | CLARIFY. | | | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-20 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-20 |
Time |
06:48 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-11-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-05 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-05 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2001-11-05 00:00:00 | ******************* UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PANELS ARE SHOWN AT 22,000, WHAT ABOUT | | | MAIN? IS THE 22,000 FOR BREAKERS IN | | | PANELS ALSO? | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 4) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | NOTE; MISSING IN BEDROOM #3 ALSO, SD | | | SHOWN NEAR KITCHEN DOOR NEEDS TO BE A | | | MIN OF 3` NFPA-72 2-5.2.1.6 | | | | | | 5)NOTE: PLEASE NOTE THE MISSING SMALL | | | APPLIANCE CIRCUITS ON PANEL SCHEDULES. | | | 210-11-C-1 | | | | | | 6)NOTE: PLEASE NOTE THAT ONLY ONE PANEL | | | IS SHOWN ON PLANS? RISER SHOWS TWO? | | | | | | 7)PLEASE NOTE THAT THE ELECTRICAL PANEL | | | IS SHOWN IN BATHROOM. THIS IS NOT | | | PERMITTED PER 240-24E. PLEASE NOTE THAT | | | PANEL CLEARENCE PER 110-26 | | | | | | 8)NOTE:PLEASE NOTE THAT PANEL SCHEDULES | | | DO NOT CORRELATE>>> "A" SHOWS 3-AHU`S | | | AND "B" SHOWS CU`S 1,2A,2B AND 3??? | | | PLEASE CLARIFY. | | | | | | 9)NOTE: PLEASE SHOW ALL AHU`S AND CU`S | | | ON PLANS AND DISCONNECTS PER 440-11 AND | | | RECEPTS FOR SERVICE. | | | | | | 10)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS BETWEEN MAIN AND | | | PANEL "A". 250-122 | | | | | | 11)NOTE: PLEASE CLARIFY WHERE PANEL "B" | | | IS BEING FED FROM? PANEL SCHEDULE "A" | | | DOES NOT HAVE PANEL "B" ON SCHED. | | | | | | 12)NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | GREAT ROOM. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-03-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-16 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-03-16 |
Time |
15:20 |
Sent To |
E |
|
| Notes |
| 2004-03-16 00:00:00 | TO BT DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-11-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-17 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-17 |
Time |
09:04 |
Sent To |
P |
|
| Notes |
| 2003-11-17 00:00:00 | TO KS BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-11-03 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-03 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-03 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2003-11-03 00:00:00 | TO JW DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-06-12 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-12 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-12 |
Time |
11:25 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-25 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-25 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-25 |
Time |
09:57 |
Sent To |
E |
|
| Notes |
| 2003-03-25 00:00:00 | TO BT DESK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-04-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-09 |
Time |
13:09 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-04-09 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2003-04-09 00:00:00 | REFERENCE NOTE ON PLANS SHEET M100, | | | "4 INCH FLUE PIPING FOR GAS WATER | | | HEATER.MOUNT 7" (MIN) ABOVE EXTERIOR | | | GRADE.ORIGINAL SUBMITTAL INDICATES 7 | | | FT.PLEASE VERIFY. | | | | | | ADDITIONAL PERMIT REQUIRED FOR GAS, | | | PLEASE PROVIDE PLANS WITH PERMIT | | | APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-08 |
Time |
09:51 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-08-20 |
Time |
14:36 |
Sent To |
P |
|
| Notes |
| 2002-08-20 00:00:00 | PROVISO: | | | | | | CALL FOR INSPECTION PRIOR TO COVERING | | | THE "SPUNSTRAND" DUCTWORK (UNDERGROUND). | | | | | | PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS ON THE JOBSITE FOR | | | INSPECTION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-12-27 |
Time |
11:23 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-12-27 |
Time |
11:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-08 |
Time |
09:28 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2001-11-08 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2001-11-08 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.LOCATION OF TOILET EXHAUST ON THE | | | FIRST FLOOR.PLAN INDICATES EXHAUST | | | DUCT IS RUNNING IN CRAWL SPACE TO | | | WALL CAP.PLEASE SPECIFY MATERIAL | | | USED FOR EXHAUST DUCT.EXHAUST | | | TERMINATION SHALL BE 10' FROM ANY | | | WINDOW, DOOR OR FRESH AIR INTAKE AS | | | PER 1997 SMC 506.1 OR 2' ABOVE FRESH | | | AIR INTAKE. | | | | | | 2.DUCT IN CRAWL SPACE UNDER FIRST | | | FLOOR SHALL NOT BE INSTALLED IN OR | | | WITHIN 4 INCHES OF THE GROUND AS PER | | | 1997 SMC 605.4. | | | | | | 3.PLEASE SPECIFY MATERIAL AND R-VALUE | | | OF ALL DUCTWORK BEING INSTALLED. | | | | | | 4.INDICATE SIZE LOCATION OF LIQUID AND | | | SUCTION REFRIGERANT LINES. | | | | | | 5.INDICATE LOCATION OF CONDENSER | | | UNITS.PLAN SHEET A000 SHOWS COND. | | | UNITS IN EXCESS OF 30' FROM THE | | | HOUSE.PLEASE REFER TO MANUFACTURER | | | INSTALLATION INSTRUCTIONS FOR LINE | | | SIZE FOR THIS DISTANCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2003-12-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-01 |
Time |
13:21 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2003-12-01 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2003-12-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) SHT P400, PIPE SIZES FOR GAS LINES | | | ARE INCORRECT. PLEASE CHANGES PIPES | | | SIZES TO CORRECT PIPE SIZES SHOWN IN RED | | | ON REVISION. ALSO SHOW ALL VALVES AT THE | | | APPLIANCES. | | | 2) PER RULING BY THE FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS, A SIGNATURE IS | | | REQUIRED ON SIGNED AND SEALED PLANS. IN- | | | ITIALS ARE NOT ACCEPTED. 61G15-23.002(1) | | | 3) ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS, AND LICENSE NUMBER | | | ON EACH SHEET. IF PRACTICING THORUGH A | | | DULY AUTHORIZED ENGINEERING BUSINESS, | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME AND LICENSE NUMBER, AS WELL AS, THE | | | NAME, ADDRESS, AND CERTIFICATE OF AUTH- | | | ORIZATION NUMBER OF THE ENGINEERING BUS- | | | INESS ON EACH SHEET. 61G15-23.002(2) | | | SEE ATTACHED SHEET... FS 471.025 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2003-06-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-17 |
Time |
09:04 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-06-18 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2003-06-18 00:00:00 | REVISION OK - GAS PIPING CHANGED | | | BTU'S / DISTANCE CHANGED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2003-06-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-06-17 |
Time |
09:56 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2003-06-17 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2003-06-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) SHT P400 NATURAL GAS RISER DOES NOT | | | REFLECT THE GAS APPLIANCE SCHEDULE. | | | RISER SHOWS 200MBTUH FOR BBQ AND SCHED. | | | SHOWS 69MBTUH. RISER SHOWS 200MBTUH FOR | | | THE RANGE AND SCHED. SHOWS 144MBTUH. | | | PLEASE CLAIRFY. | | | 2) PLEASE INDICATE TYPE OF PIPE FOR EACH | | | SECTION OF THE RISER. ALSO SHOW ALL PIPE | | | SIZES FOR THE RISER SECTIONS AND DROPS. | | | 3) SHT P100 INDICATES REVISIONS #4 & #5. | | | PREVIOUS REVISION SHOWS #3 TO BE THE | | | LAST REVISION. #4 NOT FOUND ON LATEST | | | REVISION. PLEASE CLAIRFY. | | | 4) SHT P400 INDICATES REVISIONS #2 & #3. | | | PREVIOUS REVISION SHOWS #1 TO BE THE | | | LAST REVISION. #2 NOT FOUND ON LATEST | | | REVISION. PLEASE CLAIRFY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2003-04-08 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-12 |
Time |
11:25 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-04-08 |
Time |
09:50 |
Sent To |
M |
|
| Notes |
| 2003-04-08 00:00:00 | REVISION OK - CHANGED TUB TO SHR. SHR. | | | TO TUB - CHANGED F.D. TO FLOOR SINK - | | | REROUTE CONDENSATE LINE 2ND FLOOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-04-08 |
Time |
08:02 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | REVISION, PROVISO PER DARCY(DAM), PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-01-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-20 |
Time |
16:01 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-06 00:00:00 | PROVISO: SEPERATE PLANS, PERMIT FOR GAS. | | | ADDRESS ALL ITEMS ON GAS APPLICATION | | | PERMIT REQUIRMENTS.PES |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-12-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-12-26 |
Time |
13:40 |
Rev Time |
2.00 |
| Received By |
jleech |
Date |
2001-12-26 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2001-12-26 00:00:00 | DENIED; | | | | | | PAGE P301 GAS RISER; | | | 1.LONGEST RUN IS 85',G-6,3,2. USING | | | TABLE 305.4A IN THE 97 SMC. | | | 2.PLEASE DELETE GAS RISER DIAGRAM OR | | | MAKE REQUIRED CHANGES. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-20 |
Time |
07:00 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2001-11-06 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2001-11-06 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 | | | | | | 1) PAGES A100 & P100 & P301. OUTSIDE | | | SHOWER SHALL NOT HAVE A DRAIN. PLEASE | | | REMOVE, NOT APPROVED PER UTILITY ORD. | | | 2) PAGE A101 PLEASE PROVIDE ROOF DRAIN- | | | AGE CALCULATIONS FOR PRIMARY AND SECOND- | | | ARY DRAINS USING SPC SEC 1108 AND 1109. | | | ADD 1/2 AREA OF VERTICAL WALLS/PARAPET | | | WALLS PER 1108.3. ALSO ADD ANY AREA OF | | | ROOFS THAT DRAIN ONTO NEW ROOFS. | | | PLEASE SHOW DETAILS OF PRIMARY AND SEC- | | | ONDARY DRAINS. - ALSO PLEASE SUPPLY | | | CALCULATIONS FOR EXISTING ROOF - SHOW | | | PRIMARY AND SECONDARY DRAINS WITH SIZES. | | | 3) PAGE P300 DRYWELL DETAIL, OVERFLOW | | | SHALL BE TIED INTO DRAIN LINE NOT DRY- | | | WELL. | | | 4) PAGE P300 WATER HEATER DETAIL, BOTTOM | | | FED WATER HEATER SHALL HAVE A N36 VAC- | | | BREAKER INSTALLED ON SUPPLY SIDE OF W/ | | | HEATER. - EMERGENCY PAN DRAIN TO BE 1" | | | 5) PAGE P300 INDIRECT WASTE FROM ICE | | | MACHINE SHALL DRAIN INTO A FLOOR SINK | | | NOT FLOOR DRAIN AS SHOWN. SPC SEC 804.5 | | | 6) PAGE P300 WASHER DETAIL CLEAN OUT RE- | | | QUIRED AT 4' AFF ON VENT STACK | | | 7) PAGE P300 SEPARATE GAS PERMIT REQUIR- | | | ED. SEE ATTACHED GAS PERMIT APPLICATION | | | REQUIREMENT SHEET FOR FURTHER INFORMAT- | | | ION REQUIRED. SUPPLY INFO FOR NUMBERS | | | THAT ARE CIRCLED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-29 |
Time |
11:51 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|