| Plan Review Stops For Permit 01101215 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-29 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-29 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | 1) NO PRODUCT APPROVALS FOR FIREWRAP | | | INFORMATION NOTED ON PLANS. | | | 2) PLEASE PROVIDE DETAILS FOR | | | SEPARATION OF DUCT TO COMBUSTIBLE | | | MATERIAL. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-26 |
Time |
08:36 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-10-26 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2001-10-26 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.MANUFACTURER SUBMITTAL DATA/PRODUCT | | | APPROVAL/INSTALLATION FOR THE 3M | | | FIREMASTER WRAP. | | | | | | 2.PLANS INDICATE EF-1 AGAINST EXTERIOR | | | WALL.SHOW COMPLIANCE WITH 1997 SMC | | | 506.1 AND NFPA 96 4-8.2.1.EXHAUST | | | TERMINATION SHALL BE A MINIMUM OF | | | 10' CLEARANCE FROM THE OUTLET TO | | | ADJACENT BUILDINGS, PROPERTY LINES, | | | AND AIR INTAKES. | | | | | | ADDITIONAL PERMIT REQUIRED FOR FIRE | | | SUPRESSION.PLEASE SUBMIT PLANS WITH | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|