Plan Review Details - Permit 01101215
Plan Review Stops For Permit 01101215
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By mcarsill Date 2001-10-29 Time 12:22 Rev Time 0.00
Received By mcarsill Date 2001-10-29 Time 12:21 Sent To  
Notes
2001-10-29 00:00:001) NO PRODUCT APPROVALS FOR FIREWRAP
 INFORMATION NOTED ON PLANS.
 2) PLEASE PROVIDE DETAILS FOR
 SEPARATION OF DUCT TO COMBUSTIBLE
 MATERIAL.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-26 Cont ID  
Sent By pkrauss Date 2001-10-26 Time 08:36 Rev Time 0.50
Received By pkrauss Date 2001-10-26 Time 08:36 Sent To  
Notes
2001-10-26 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.MANUFACTURER SUBMITTAL DATA/PRODUCT
 APPROVAL/INSTALLATION FOR THE 3M
 FIREMASTER WRAP.
  
 2.PLANS INDICATE EF-1 AGAINST EXTERIOR
 WALL.SHOW COMPLIANCE WITH 1997 SMC
 506.1 AND NFPA 96 4-8.2.1.EXHAUST
 TERMINATION SHALL BE A MINIMUM OF
 10' CLEARANCE FROM THE OUTLET TO
 ADJACENT BUILDINGS, PROPERTY LINES,
 AND AIR INTAKES.
  
 ADDITIONAL PERMIT REQUIRED FOR FIRE
 SUPRESSION.PLEASE SUBMIT PLANS WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.