| Plan Review Stops For Permit 01101097 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-12-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-12-04 |
Time |
17:39 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2001-12-04 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2001-12-04 00:00:00 | PROVISO: PLANS TO COUNTY FOR IMPACT FEES | | | 12/04/01 JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-30 |
Time |
18:33 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2001-10-30 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | PLAN REVIEW | | | PERMIT: 01091097 | | | 3420 CELEBRATION BLVD | | | CIMORELLI & ASSOCIATES | | | (561) 832-7535 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- SBC 1203.1.2. WHERE WINDOWS ARE RE- | | | QUIRED SUCH WINDOWS SHALL OPEN ON A | | | STREET, PUBLIC SPACE, YARD OR APPROVED | | | OPEN SPACE THAT WILL AFFORD ADEQUITE | | | AIR & LIGHT. REQUIRED WINDOWS SHALL BE | | | CONSTRUCTED THAT WHEN FULLY OPENED, THE | | | TOTAL OPEN SPACE SHALL BE NOT LESS THAN | | | ONE-HALF THE REQUIRED WINDOW AREA. | | | | | | 2)- 1203.4.2 EVERY TOILET ROOM SHALL | | | HAVE WINDOWS AS SPECIFIED FOR HABITABLE | | | ROOMS PROVIDING IN NO CASE LESS THAN 3 | | | SQ. FT. OPEN SPACE, OR SHALL HAVE | | | APPROVED EQUIVALENT MECHANICAL VENTILA- | | | TION. | | | | | | 3)- RESTROOM FLOOR FINISH, G-A1.0 | | | DETAIL 2 SEE FLOOR FINISH SSCHEDULE? | | | SBC 1204.2 THE WALLS & FLOORS OF ALL | | | PUBLIC RESTROOMS SHALL BE LINED WITH | | | NONABSORBANT MATERIAL TO A HEIGTH OF | | | 4 FT ABOVE THE FLOOR. | | | | | | 4)- CONTRACTOR TO TAKE THE PLANS TO THE | | | COUNTY BUILDING DEPARTMENT FOR COUNTY | | | IMPACT FEE ASSESMENT. | | | | | | 5)- RADON FEES PAID TO CITY, $1.94. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-11-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-26 |
Time |
21:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-26 |
Time |
21:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-30 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-30 |
Time |
16:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-11-27 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2001-11-27 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2001-11-27 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-20 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-20 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2001-12-20 00:00:00 | 1) FIRE RESCUE ACCESS TO BE AT LEAST | | | 20 FEET IN CLEAR WIDTH. PROVISIONS | | | ARE TO BE MADE FOR FIRE RESCUE ACCESS | | | IN THE EVENT OF LOSS OF POWER. | | | | | | APPROVED PROVISO: INSTALLATION SUBJECT | | | TO INSPECTION BY FIRE RESCUE OFFICIALS | | | AFTER THE JOB IS COMPLETETED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-24 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-24 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2001-10-24 00:00:00 | 1) WILL THE GUARD-HOUSE ALWAYS BE | | | STAFFED 24 HOURS A DAY, SEVEN DAYS | | | A WEEK, 365 DAYS A YEAR. | | | 2) WHAT PROVISIONS HAVE BEEN MADE FOR | | | FIRE RESCUE ACCESS. | | | 3) THERE ARE SEVERAL MEDIANS SHOWN. FIRE | | | CODES REQUIRES AT LEAST 20 FEET IN | | | CLEAR WIDTH. PLEASE DEMONSTRATE | | | COMPLIANCE. | | | 4) WHAT PROVISIONS HAVE BEEN MADE FOR | | | LOSS OF POWER. | | | 5) A MINIMUM OF 13'- 6" IS REQUIRED IF | | | FIRE APPARATUS ARE EXPECTED TO PASS | | | UNDER THE OVERHANGS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-04-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-04-23 |
Time |
13:36 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-04-23 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2002-04-23 00:00:00 | INSTALLATION OF EXHAUST FAN ONLY | | | MECHANICAL PERMIT 02041046 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-05 |
Time |
13:05 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2001-12-05 |
Time |
12:58 |
Sent To |
Z |
|
| Notes |
| 2001-12-05 00:00:00 | | | | ENGINEER RESPONSE FROM REVIEW DATED | | | 10-29-01,NO MECHANICAL SYSTEM FOR | | | GUARD HOUSE EXCEPT FOR EXHAUST FAN IN | | | TOILET ROOM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-29 |
Time |
12:47 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-29 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | | | | | | | NO MECHANICAL PLANS SUBMITTED WITH THIS | | | PERMIT APPLICATION. | | | | | | PLEASE PROVIDE PLANS WTIH MECHANICAL | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-12-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-21 |
Time |
09:38 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-12-21 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-29 |
Time |
09:35 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2001-11-29 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2001-11-29 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT G-A2.0 SANITARY ISOMETERIC DETAIL | | | TWO WAY C/O REQD NEAR JUNCTION OF BLDG | | | DRAIN AND BLDG SEWER. | | | 2) SHT G-A2.0 WATER ISOMETERIC AIR | | | CHAMBERS REQUIRE ACCESS AND MUST BE RE- | | | CHARGED. APPROVED WATER HAMMER ARRESTORS | | | DO NOT REQUIRE ACCESS PANELS. PLEASE | | | SHOW DETAILS. | | | 3) SHT G-A2.0 3" VTR REQUIRED CAN NOT | | | RUN THROUGH TIE BEAM PER SBC-97 SEC | | | 1907.3.5. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-05 |
Time |
13:53 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|