Plan Review Details - Permit 01101097
Plan Review Stops For Permit 01101097
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-04 Cont ID  
Sent By jwitmer Date 2001-12-04 Time 17:39 Rev Time 0.50
Received By jwitmer Date 2001-12-04 Time 17:39 Sent To  
Notes
2001-12-04 00:00:00PROVISO: PLANS TO COUNTY FOR IMPACT FEES
 12/04/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-30 Cont ID  
Sent By jwitmer Date 2001-10-30 Time 18:33 Rev Time 1.50
Received By jwitmer Date 2001-10-30 Time 18:33 Sent To  
Notes
2001-10-30 00:00:00PLAN REVIEW
 PERMIT: 01091097
 3420 CELEBRATION BLVD
 CIMORELLI & ASSOCIATES
 (561) 832-7535
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SBC 1203.1.2. WHERE WINDOWS ARE RE-
 QUIRED SUCH WINDOWS SHALL OPEN ON A
 STREET, PUBLIC SPACE, YARD OR APPROVED
 OPEN SPACE THAT WILL AFFORD ADEQUITE
 AIR & LIGHT. REQUIRED WINDOWS SHALL BE
 CONSTRUCTED THAT WHEN FULLY OPENED, THE
 TOTAL OPEN SPACE SHALL BE NOT LESS THAN
 ONE-HALF THE REQUIRED WINDOW AREA.
  
 2)- 1203.4.2 EVERY TOILET ROOM SHALL
 HAVE WINDOWS AS SPECIFIED FOR HABITABLE
 ROOMS PROVIDING IN NO CASE LESS THAN 3
 SQ. FT. OPEN SPACE, OR SHALL HAVE
 APPROVED EQUIVALENT MECHANICAL VENTILA-
 TION.
  
 3)- RESTROOM FLOOR FINISH, G-A1.0
 DETAIL 2 SEE FLOOR FINISH SSCHEDULE?
 SBC 1204.2 THE WALLS & FLOORS OF ALL
 PUBLIC RESTROOMS SHALL BE LINED WITH
 NONABSORBANT MATERIAL TO A HEIGTH OF
 4 FT ABOVE THE FLOOR.
  
 4)- CONTRACTOR TO TAKE THE PLANS TO THE
 COUNTY BUILDING DEPARTMENT FOR COUNTY
 IMPACT FEE ASSESMENT.
  
 5)- RADON FEES PAID TO CITY, $1.94.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-26 Cont ID  
Sent By dpalmer Date 2001-11-26 Time 21:55 Rev Time 0.00
Received By dpalmer Date 2001-11-26 Time 21:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-30 Cont ID  
Sent By dpalmer Date 2001-10-30 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2001-10-30 Time 16:53 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-11-27 Cont ID  
Sent By mamini Date 2001-11-27 Time 11:43 Rev Time 0.00
Received By mamini Date 2001-11-27 Time 11:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-20 Cont ID  
Sent By mcarsill Date 2001-12-20 Time 14:40 Rev Time 0.00
Received By mcarsill Date 2001-12-20 Time 14:40 Sent To  
Notes
2001-12-20 00:00:001) FIRE RESCUE ACCESS TO BE AT LEAST
 20 FEET IN CLEAR WIDTH. PROVISIONS
 ARE TO BE MADE FOR FIRE RESCUE ACCESS
 IN THE EVENT OF LOSS OF POWER.
  
 APPROVED PROVISO: INSTALLATION SUBJECT
 TO INSPECTION BY FIRE RESCUE OFFICIALS
 AFTER THE JOB IS COMPLETETED.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By mcarsill Date 2001-10-24 Time 14:56 Rev Time 0.00
Received By mcarsill Date 2001-10-24 Time 14:56 Sent To  
Notes
2001-10-24 00:00:001) WILL THE GUARD-HOUSE ALWAYS BE
 STAFFED 24 HOURS A DAY, SEVEN DAYS
 A WEEK, 365 DAYS A YEAR.
 2) WHAT PROVISIONS HAVE BEEN MADE FOR
 FIRE RESCUE ACCESS.
 3) THERE ARE SEVERAL MEDIANS SHOWN. FIRE
 CODES REQUIRES AT LEAST 20 FEET IN
 CLEAR WIDTH. PLEASE DEMONSTRATE
 COMPLIANCE.
 4) WHAT PROVISIONS HAVE BEEN MADE FOR
 LOSS OF POWER.
 5) A MINIMUM OF 13'- 6" IS REQUIRED IF
 FIRE APPARATUS ARE EXPECTED TO PASS
 UNDER THE OVERHANGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-04-23 Cont ID  
Sent By pkrauss Date 2002-04-23 Time 13:36 Rev Time 0.30
Received By pkrauss Date 2002-04-23 Time 13:09 Sent To  
Notes
2002-04-23 00:00:00INSTALLATION OF EXHAUST FAN ONLY
 MECHANICAL PERMIT 02041046

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2001-12-05 Cont ID  
Sent By pkrauss Date 2001-12-05 Time 13:05 Rev Time 0.30
Received By pkrauss Date 2001-12-05 Time 12:58 Sent To Z
Notes
2001-12-05 00:00:00 
 ENGINEER RESPONSE FROM REVIEW DATED
 10-29-01,NO MECHANICAL SYSTEM FOR
 GUARD HOUSE EXCEPT FOR EXHAUST FAN IN
 TOILET ROOM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-10-29 Cont ID  
Sent By pkrauss Date 2001-10-29 Time 12:47 Rev Time 0.35
Received By pkrauss Date 2001-10-29 Time 12:31 Sent To  
Notes
2001-10-29 00:00:00 
  
 NO MECHANICAL PLANS SUBMITTED WITH THIS
 PERMIT APPLICATION.
  
 PLEASE PROVIDE PLANS WTIH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-12-21 Cont ID  
Sent By kstevens Date 2001-12-21 Time 09:38 Rev Time 0.50
Received By kstevens Date 2001-12-21 Time 09:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-29 Cont ID  
Sent By kstevens Date 2001-11-29 Time 09:35 Rev Time 0.75
Received By kstevens Date 2001-11-29 Time 09:35 Sent To  
Notes
2001-11-29 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT G-A2.0 SANITARY ISOMETERIC DETAIL
 TWO WAY C/O REQD NEAR JUNCTION OF BLDG
 DRAIN AND BLDG SEWER.
 2) SHT G-A2.0 WATER ISOMETERIC AIR
 CHAMBERS REQUIRE ACCESS AND MUST BE RE-
 CHARGED. APPROVED WATER HAMMER ARRESTORS
 DO NOT REQUIRE ACCESS PANELS. PLEASE
 SHOW DETAILS.
 3) SHT G-A2.0 3" VTR REQUIRED CAN NOT
 RUN THROUGH TIE BEAM PER SBC-97 SEC
 1907.3.5.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-22 Cont ID  
Sent By pkrauss Date 2001-12-05 Time 13:53 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***