Plan Review Details - Permit 01101066
Plan Review Stops For Permit 01101066
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-02 Cont ID  
Sent By pkrauss Date 2001-11-02 Time 07:34 Rev Time 0.50
Received By pkrauss Date 2001-11-02 Time 07:34 Sent To  
Notes
2001-11-02 00:00:00*******************PROVISO**************
  
  
 PLAN INDICATES REMOVAL OF FIRE DAMPERS.
 SHOULD FIRE DAMPERS NOT BE INSTALLED A
 SUBMITTAL OF THE CEILING ASSEMBLY IS
 REQUIRED.
  
 SHOULD FIRE DAMPERS REMAIN PLEASE SUBMIT
 ACCESS DOORS BEING INSTALLED FOR FIRE
 DAMPERS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-16 Cont ID  
Sent By ndenmark Date 2001-10-16 Time 12:48 Rev Time 0.33
Received By ndenmark Date 2001-10-16 Time 12:48 Sent To  
Notes
2001-10-16 00:00:00DENIED
 1. DUCT SHALL NOT BE LOCATED IN
 STAIRWELL
 2. NO RETURN SHOWN FOR FIRST FLOOR FROM
 RTU 1
 3. FAN SHUT DOWN BY DUCT SMOKE
 DETECTORSREQUIRED.
 4. LOCATION AND INSTALLATION DETAILS FOR
 FIRE DAMPERS SHALL BE PROVIDED ON PLANS
 BY THE DESIGNER.
 5. PROVIDE CALCULATIONS SHOWING
 COMPLIANCE WITH ASHRAE 62-89 OUTSIDE
 AIR REQUIREMENTS.
 6. PROVIDE DETAILS FOR RTU'S ON ROOF
 SHOWING ATTACHMENT AND PENETRATION
 REQUIREMENTS.
 7. SPECIFY DUCT MATERIAL AND R-VALUE
 8. PROVIDE ENERGY EFFICIENCY VALUES FOR
 EQUIPMENT.