| Plan Review Stops For Permit 01101066 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-02 |
Time |
07:34 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-11-02 |
Time |
07:34 |
Sent To |
|
|
| Notes |
| 2001-11-02 00:00:00 | *******************PROVISO************** | | | | | | | | | PLAN INDICATES REMOVAL OF FIRE DAMPERS. | | | SHOULD FIRE DAMPERS NOT BE INSTALLED A | | | SUBMITTAL OF THE CEILING ASSEMBLY IS | | | REQUIRED. | | | | | | SHOULD FIRE DAMPERS REMAIN PLEASE SUBMIT | | | ACCESS DOORS BEING INSTALLED FOR FIRE | | | DAMPERS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-16 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-10-16 |
Time |
12:48 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2001-10-16 |
Time |
12:48 |
Sent To |
|
|
| Notes |
| 2001-10-16 00:00:00 | DENIED | | | 1. DUCT SHALL NOT BE LOCATED IN | | | STAIRWELL | | | 2. NO RETURN SHOWN FOR FIRST FLOOR FROM | | | RTU 1 | | | 3. FAN SHUT DOWN BY DUCT SMOKE | | | DETECTORSREQUIRED. | | | 4. LOCATION AND INSTALLATION DETAILS FOR | | | FIRE DAMPERS SHALL BE PROVIDED ON PLANS | | | BY THE DESIGNER. | | | 5. PROVIDE CALCULATIONS SHOWING | | | COMPLIANCE WITH ASHRAE 62-89 OUTSIDE | | | AIR REQUIREMENTS. | | | 6. PROVIDE DETAILS FOR RTU'S ON ROOF | | | SHOWING ATTACHMENT AND PENETRATION | | | REQUIREMENTS. | | | 7. SPECIFY DUCT MATERIAL AND R-VALUE | | | 8. PROVIDE ENERGY EFFICIENCY VALUES FOR | | | EQUIPMENT. |
|
|
|