| Plan Review Stops For Permit 01101061 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-01-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-18 |
Time |
16:25 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-18 00:00:00 | APPROVED BY L. MARTINEZ |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-03 |
Time |
10:55 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
2002-01-03 |
Time |
10:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2001-11-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-02 |
Time |
08:53 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-11-02 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-22 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-22 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-12-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-26 |
Time |
20:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-12-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-26 |
Time |
20:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-26 |
Time |
20:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-30 |
Time |
21:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-30 |
Time |
21:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-22 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-22 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-12-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-17 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-17 |
Time |
08:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-16 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-16 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2001-10-16 00:00:00 | 1) PLEASE PROVIDE DETAILS ON EXISTING | | | DOOR E NOTED ON THE PLANS. | | | 2) THE PLANS SEEM TO INDICATE THAT | | | CLASS C INTERIOR FINISH WILL BE | | | PROVIDED. PLEASE BE ADVISED THAT THE | | | PLANS INDICATES THAT NO FIRE SPRINKLERS | | | WILL BE PRESENT AND IF THAT IS THE CASE | | | THE INTERIOR FINISH MUST BE AT LEAST | | | CLASS A OR B IN THE EXITS. | | | 3) PLEASE INDICATE ON THE PLANS THE | | | NUMBER OF STORIES THE EXISTING | | | BUILDING IS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-01-25 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-25 |
Time |
15:04 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-01-25 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2002-01-25 00:00:00 | | | | MECHANICAL PERMIT REQUIRED. | | | | | | NOTE:2000 FLORIDA BUILDING CODE, | | | (MECHANICAL) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-12-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-19 |
Time |
15:10 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-12-19 |
Time |
15:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-29 |
Time |
14:32 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-10-29 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | ******************DENIED**************** | | | | | | | | | PLEASE PROVIDE DETAIL SHOWING HOW | | | CONDENSER UNIT STAND WILL BE ATTACHED | | | TO THE ROOF.PLEASE NOTE 18" MINIMUM | | | BETWEEN THE ROOF SURFACE TO THE BOTTOM | | | OF THE SUPPORT RAIL. | | | | | | PLEASE INDICATE TERMINATION OF EMERGENCY | | | DRAIN FROM THE AUXILIARY DRAIN PAN. | | | TERMINATION SHALL BE AT A CONSPICUOUS | | | POINT TO SERVE AS AN ALARM THAT THE | | | REGULAR DRAIN IS RESTRICTED. 1997 SMC | | | 304.8.6.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-25 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-03-25 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2002-03-25 00:00:00 | REVISION OK - SANT RISER DIAGRAM - ADD | | | SERVICE SINK REQUIRED PER FBC-2001 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-01-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-30 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-01-30 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-01-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-09 |
Time |
15:50 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2002-01-09 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2002-01-09 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT 1.1 SQ FOOTAGE IS 3033, MINUS | | | SQ FOOTAGE FOR RESTROOMS IS APPROX | | | 2900 SQ FT. @ 100 PERSONS PER SQ FT = 29 | | | 2 WC'S AND 2 LAV'S ARE REQUIRED FOR | | | WOMENS RESTROOM. PLEASE RESUBMIT PLANS | | | WITH PROPER MINIMUM FACILITIES SHOWN | | | SPC TABLE 407 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-30 |
Time |
13:15 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2001-10-30 |
Time |
13:15 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | DENIED | | | REFERENCES: SPC-94 - FACBC-97 | | | | | | 1) SUBMIT CALCULATIONS FOR MINIMUM FAC- | | | ILITIES PER SPC TABLE 407. PAGE 3.1 | | | 2) PAGE MP-1 DRINKING FOUNTAIN. PLEASE | | | SHOW DRINKING FOUNTAIN DETAIL TO SHOW | | | COMPLIANCE WITH FACBC-97 SEC 4.15. IF A | | | SINGLE DRINKING FOUNTAIN SPOUT TO BE 36" | | | OFF FLOOR AND PROVISIONS SHALL BE MADE | | | FOR THOSE THAT HAVE DIFFICULTY BENDING | | | OR STOOPING. | | | 3) PAGE MP-1 WATER RISER. WATER HAMMER | | | ARRESTORS SHALL BE INSTALLED PER MANU- | | | FACTURE INSTALLATION INSTRUCTIONS AND | | | WH-PDI 201. ARRESTORS SHALL BE LOCATED | | | NEAR FIXTURES NOT AT TOP OF DROP AS IN- | | | DICATED ON RISER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|