| Plan Review Stops For Permit 01100853 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-10-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-16 |
Time |
13:26 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2001-10-16 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2001-10-16 00:00:00 | SUBMITTED ENERGY CALCS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-15 |
Time |
08:48 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-15 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2001-10-15 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | | | | 1.PROVIDE ENGERGY CALCULATIONS AS | | | PER 1997 FLORIDA ENERGY CODE SECTION | | | 101.4.1.1, SHOW COMPLIANCE WITH | | | CHAPTER 6 METHOD C. | | | | | | 2.COOLING AND HEATING DESIGN LOADS, | | | FOR THE PURPOSE OF SIZING HVAC | | | SYSTEMS, SHALL BE DETERMINED FOR | | | EACH ZONE WITHIN A DWELLING IN | | | ACCORDANCE WITH ACCA MANUAL J, ACCA | | | MANUAL N OR THE ASHRAE COOLING AND | | | HEATING LOAD CALCULATION MANUAL | | | SECOND EDITION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
|