| 2001-11-20 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE IMPORTANCE FACTOR LISTED ON C-1 |
| | IS INCORRECT, IT SHOULD BE 1.0 FOR 97 |
| | SBC 1606. |
| | |
| | 3) THE FOOTING DIMENSIONS FOR SECTIONS A |
| | & B ON A-5 ARE INCORRECT. THE F-1 FOOT- |
| | INGS ARE INDICATED AS 16" DEEP ON S-1. |
| | |
| | 4) THE PLANS INDICATE R-30 CEILING |
| | INSULATION AND THE ENERGY CALCULATIONS |
| | LIST R- 19. PLEASE CLARIFY. |
| | |
| | 5) SEMCO AND HUGHES HAVE BEEN PURCHASED |
| | BY USP. SOME OF THEIR CONNECTORS HAVE |
| | VALUES THAT ARE CHANGED AND SOME ARE NO |
| | LONGER AVAILABLE. PLEASE PROVIDE A |
| | REVISED TRUSS ANCHOR SCHEDULE. CONSULT |
| | USP TECHNICAL ASSISTANCE FOR REDUCED |
| | LOAD VALUES FOR INSTALLATIONS OF EMBEDD- |
| | ED TRUSS ANCHORS SPACED CLOSER THAN 8" |
| | AND WHEN USING LESS THAN THE SPECIFIED |
| | NUMBER OF FASTENERS. |
| | |
| | 6) THERE IS NO TRUSS ANCHOR SPECIFIED |
| | FOR ONE END OF THE GIRDER AT THE GARAGE. |
| | |
| | 7) NOTE THREE ON S-3 INCORRECTLY |
| | REFERENCES ASCE 7-93. THE DESIGN MUST BE |
| | BASED ON 97 SBC SECTION 1606 FOR 110 MPH |
| | OR ASCE 7-95 FOR 140 MPH. PLEASE CORRECT |
| | |
| | 8) THE ROOF PLYWOOD SHEATHING NAILING |
| | SCHEDULE ON THE TOP OF S-2 LISTS ZONES |
| | RI AND SI. THE SPECIAL NAILING ZONES IN |
| | THE CITY OF WPB AMENDMENTS TO THE 97 SBC |
| | ARE DESIGNATED AS ZONES 1,2 AND 3. |
| | PLEASE CORRECT. |
| | |
| | 9) THE PRODUCT APPROVAL FOR THE GLASS |
| | BLOCK EXPIRED PRIOR TO APPLICATION FOR |
| | PERMIT. |
| | |
| | 10) PROVIDE INFORMATION ON GLASS BLOCK |
| | THAT INDICATES THAT THE BLOCK USED AT |
| | THE SHOWER HAS A MINIMUM UNIFORM FACE |
| | THICKNESS OF 0.25 INCH, TO COMPLY WITH |
| | 97 SBC 2405.2 GLASS IN HAZARDOUS |
| | LOCATIONS. |
| | |
| | 11) PROVIDE PRODUCT APPROVALS FOR |
| | STRUCTURAL MULLIONS USED TO CONNECT |
| | THE SLIDING GLASS DOOR AND THE FIXED |
| | GLASS WINDOWS ABOVE. |
| | |
| | 12) PROVIDE KEY PLAN, INSTALLATION |
| | SCHEDULE, METHOD OF INSTALLATION AND |
| | TYPE OF ANCHORS TO BE USED TO INSTALL |
| | STORM PANELS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |