| Plan Review Stops For Permit 01100677 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-03-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-01 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-03 |
Time |
11:16 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-01-03 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2002-01-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01100677 | | | 1041 45TH STREET | | | CONT: CATALFUMO | | | 624-9697 X 256 | | | | | | 1)- FROM PREVIOUS REVIEW, | | | SBC 1606.2.6.2 COMPONENTS & CLADDING | | | MISSING PRODUCT APPROVAL REPORTS (2 | | | COPIES) SBCCI OR DADE COUNTY REPORTS ARE | | | ACCEPTED: | | | WINDOWS | | | DOORS | | | DOORS/ SIDELITES/TRANSOM (TESTED AS AN | | | ASSEMBLY) | | | ROOFING | | | STORM SHUTTERS | | | | | | CONT TO SUBMIT PLANS TO COUNTY FOR | | | IMPACT FEE ASSESSMENT. | | | MISSING SOILS REPORT SBC*1804.2.7 | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-31 |
Time |
18:08 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2001-10-31 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2001-10-31 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01100677 | | | 1041 45TH ST | | | CONT: CATALFUMO | | | TEL: 624-9697X256 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS/ STANDARD BUILDING CODE | | | | | | 1)- SQ.FT. OF EXISTING BUILDING, SQ.FT | | | OF NEW ADDITION? IS THE ENTIRE BLDG | | | FIRE SPRIKLERED? | | | | | | 2)- MINIMUM BUILD. TYPE? | | | | | | 3) SBC TABLE 500, INSTITUTIONAL,OR | | | RESTRAIED OR UNRESTRAINED? | | | | | | 4)- SH-1 INDICATES SOILS REPORT TO | | | BE COMPLETED? | | | | | | 5)- PLANS ARE UNCLEAR AS TO AREAS OF | | | WORK OTHER THAN ADDITION? | | | | | | 6)- SHEET 34 DETAIL #1: | | | A) 12"X12" BLOCK COLUMN W/4 #5 REBAR, | | | ARE HOOPS REQUIRED? ACI 530-95 5.9 | | | B) 12"X12" BLOCK COLUMN, MISSING INFO | | | FOR THE EMBED PLATE TOP OF COLUMN? | | | THICKNESS,SIZE, EMBED STUD SIZE & | | | COUNTOR WELD SIZE, TYPE TO W8X14. | | | C) 12"-0" BEAM NO STIRRUPS OR HOOPS? | | | | | | 7)- SHEET 4 DETAILS 1,2&3 INDICATE A 8" | | | HIGH PARAPET AROUND THE ROOF DECK, ROOF | | | DRAINAGE? SCUPPERS & OVERFLOWS SEE | | | SBC 1517.6.4.3. | | | | | | 8)- ROOF DETAILS INDICATE A P.T. 2X_ | | | AROUND THE EDGE OF THE ROOF NO INFO FOR | | | ATTACHMENT TO CONCRETE BM OR METAL DECK. | | | | | | 9)- SBC 1606.2.6.2COMPONENTS & CLADDING | | | MISSING PRODUCT APPROVAL REPORTS (2COP- | | | IES) REQUIRED FOR: | | | WINDOWS | | | DOORS | | | DOORS/SIDELITES/TRANSOM (TEST ASSEMBLY) | | | ROOFING | | | STORM SHUTTERS,SEE ATTACHMENT SCHEDULE | | | | | | 10)- SBC TABLE 803.3 MIMIMUM INTERIOR | | | FINISH SCHEDULE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-10-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-24 |
Time |
23:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-24 |
Time |
23:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-01-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-02 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-02 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-17 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-17 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2001-10-17 00:00:00 | 1) NO INTERIOR FINISH INFORMATION | | | PROVIDED WITH PLANS. PLEASE PROVIDE | | | INTERIOR FINISH CLASSIFICATION | | | INFORMATION FOR WALLS AND CEILING. | | | 2) ON THE FLOOR PLAN IT APPEARS THAT | | | A WINDOW IS PRESENT ON THE EAST SIDE. | | | THE ELEVATION DRAWING FOR THE EAST | | | SIDE APPEARS TO INDICATE POSSIBLY | | | A DOOR. PLEASE CLARIFY. | | | 3) PLEASE CLEARLY IDENTIFY EXISTING | | | CONSTRUCTION FROM NEW CONSTRUCTION. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-31 |
Time |
15:07 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-12-31 |
Time |
15:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-20 |
Time |
11:27 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-12-20 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2001-12-20 00:00:00 | ********************DENIED************** | | | | | | | | | COMMENTS FROM FIRST REVIEW NOT | | | ADDRESSED. | | | | | | PLEASE NOTE, ONE SET OF PLANS IS | | | MISSING SHEET 5 OF 7.PLEASE SUBMIT | | | THE AFOREMENTIONED SHEET TO HAVE 2 | | | COMPLETE SETS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-29 |
Time |
16:04 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-10-29 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | *******************PROVISO************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.PLEASE NOTE DRYER EXHAUST BEING | | | EXTENDED TO NEW EXTERIOR WALL SHALL | | | COMPLY WITH 1997 SMC 509.3.THE | | | MAXIMUM LENGTH SHALL NOT EXCEED 25'. | | | THERE SHALL BE A DEDUCTION OF 2 1/2' | | | FOR EACH 45 DEGREE BEND AND 5' FOR | | | EACH 90 DEGREE BEND.TERMINATION | | | SHALL BE LOCATED 10' FROM ANY | | | ADJACENT BUILDING, PARKING AREA, | | | ADJACENT PROPERTY LINE, WINDOW, | | | DOOR OR AIR INTAKE.OPENING SHALL | | | BE LOCATED AT LEAST 10' ABOVE THE | | | ADJOINING GRADE LEVEL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-22 |
Time |
13:31 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-01-22 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2002-01-22 00:00:00 | PASSED/PROVISO | | | | | | SCUPPER DRAINS LOCATED AT EACH WINDOW | | | OVERHANG PER ARCHITECT COMMENTS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-01-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-08 |
Time |
17:52 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2002-01-08 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2002-01-08 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT 1 0F 7 PLEASE SHOW DETAILS FOR | | | SCUPPERS. SHOW SIZE AND LOCATION. | | | PLEASE SUBMIT DETAILS FOR NEW AND EXIST- | | | ING ROOFS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-30 |
Time |
08:43 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2001-10-30 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE 1 OF 7 NEW ROOF PLAN. SUBMIT | | | ROOF DRAINAGE CALCULATIONS FOR PRIMARY | | | & SECONDARY ROOF DRAINS. INCLUDE 1/2 OF | | | AREA OF PARAPET WALLS AND AREA OF UPPER | | | ROOF DRAINING ON NEW ROOF. PLEASE SUBMIT | | | DETAILS FOR PRIMARY AND SECONDARY DRAINS | | | USE SPC SEC 1108 AND 1109 FOR CALCULAT- | | | IONS. | | | 2) PAGE 1 0F 7 EXISTING ROOF PLAN. SUB- | | | MIT CALCULATIONS FOR PRIMARY AND SECOND- | | | ARY ROOF DRAINS FOR EXISTING ROOF TO SEE | | | IF THEY COMPLY WITH PRESENT CODE. USE | | | SEC 1108 & 1109 ADDING 1/2 PARAPET WALLS | | | AND AREA OF ROOF THAT DRAINS FROM ABOVE. | | | 3) PAGE 2 0F 7 FLOOR PLAN NOTES #29. | | | PLEASE SHOW DETAILS FOR SHOWER ALTERAT- | | | ION. SHOW HOW SHOWERS COMPLY WITH FACBC- | | | 97 SEC 4.21. | | | 4) PLEASE INDICATE HOW 20 PERCENT OVER | | | CONTRACT PRICE IS SPENT ON ADA. (36,000) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|