Plan Review Details - Permit 01100677
Plan Review Stops For Permit 01100677
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-03-01 Cont ID  
Sent By hpiskura Date 2002-03-01 Time 10:12 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-01-03 Cont ID  
Sent By jwitmer Date 2002-01-03 Time 11:16 Rev Time 1.50
Received By jwitmer Date 2002-01-03 Time 11:16 Sent To  
Notes
2002-01-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01100677
 1041 45TH STREET
 CONT: CATALFUMO
 624-9697 X 256
  
 1)- FROM PREVIOUS REVIEW,
 SBC 1606.2.6.2 COMPONENTS & CLADDING
 MISSING PRODUCT APPROVAL REPORTS (2
 COPIES) SBCCI OR DADE COUNTY REPORTS ARE
 ACCEPTED:
 WINDOWS
 DOORS
 DOORS/ SIDELITES/TRANSOM (TESTED AS AN
 ASSEMBLY)
 ROOFING
 STORM SHUTTERS
  
 CONT TO SUBMIT PLANS TO COUNTY FOR
 IMPACT FEE ASSESSMENT.
 MISSING SOILS REPORT SBC*1804.2.7
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-31 Cont ID  
Sent By jwitmer Date 2001-10-31 Time 18:08 Rev Time 4.00
Received By jwitmer Date 2001-10-31 Time 18:08 Sent To  
Notes
2001-10-31 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01100677
 1041 45TH ST
 CONT: CATALFUMO
 TEL: 624-9697X256
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SQ.FT. OF EXISTING BUILDING, SQ.FT
 OF NEW ADDITION? IS THE ENTIRE BLDG
 FIRE SPRIKLERED?
  
 2)- MINIMUM BUILD. TYPE?
  
 3) SBC TABLE 500, INSTITUTIONAL,OR
 RESTRAIED OR UNRESTRAINED?
  
 4)- SH-1 INDICATES SOILS REPORT TO
 BE COMPLETED?
  
 5)- PLANS ARE UNCLEAR AS TO AREAS OF
 WORK OTHER THAN ADDITION?
  
 6)- SHEET 34 DETAIL #1:
 A) 12"X12" BLOCK COLUMN W/4 #5 REBAR,
 ARE HOOPS REQUIRED? ACI 530-95 5.9
 B) 12"X12" BLOCK COLUMN, MISSING INFO
 FOR THE EMBED PLATE TOP OF COLUMN?
 THICKNESS,SIZE, EMBED STUD SIZE &
 COUNTOR WELD SIZE, TYPE TO W8X14.
 C) 12"-0" BEAM NO STIRRUPS OR HOOPS?
  
 7)- SHEET 4 DETAILS 1,2&3 INDICATE A 8"
 HIGH PARAPET AROUND THE ROOF DECK, ROOF
 DRAINAGE? SCUPPERS & OVERFLOWS SEE
 SBC 1517.6.4.3.
  
 8)- ROOF DETAILS INDICATE A P.T. 2X_
 AROUND THE EDGE OF THE ROOF NO INFO FOR
 ATTACHMENT TO CONCRETE BM OR METAL DECK.
  
 9)- SBC 1606.2.6.2COMPONENTS & CLADDING
 MISSING PRODUCT APPROVAL REPORTS (2COP-
 IES) REQUIRED FOR:
 WINDOWS
 DOORS
 DOORS/SIDELITES/TRANSOM (TEST ASSEMBLY)
 ROOFING
 STORM SHUTTERS,SEE ATTACHMENT SCHEDULE
  
 10)- SBC TABLE 803.3 MIMIMUM INTERIOR
 FINISH SCHEDULE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-24 Cont ID  
Sent By dpalmer Date 2001-10-24 Time 23:12 Rev Time 0.00
Received By dpalmer Date 2001-10-24 Time 23:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-01-02 Cont ID  
Sent By mcarsill Date 2002-01-02 Time 16:37 Rev Time 0.00
Received By mcarsill Date 2002-01-02 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-17 Cont ID  
Sent By mcarsill Date 2001-10-17 Time 10:31 Rev Time 0.00
Received By mcarsill Date 2001-10-17 Time 10:31 Sent To  
Notes
2001-10-17 00:00:001) NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS. PLEASE PROVIDE
 INTERIOR FINISH CLASSIFICATION
 INFORMATION FOR WALLS AND CEILING.
 2) ON THE FLOOR PLAN IT APPEARS THAT
 A WINDOW IS PRESENT ON THE EAST SIDE.
 THE ELEVATION DRAWING FOR THE EAST
 SIDE APPEARS TO INDICATE POSSIBLY
 A DOOR. PLEASE CLARIFY.
 3) PLEASE CLEARLY IDENTIFY EXISTING
 CONSTRUCTION FROM NEW CONSTRUCTION.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-31 Cont ID  
Sent By pkrauss Date 2001-12-31 Time 15:07 Rev Time 0.35
Received By pkrauss Date 2001-12-31 Time 15:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-12-20 Cont ID  
Sent By pkrauss Date 2001-12-20 Time 11:27 Rev Time 0.45
Received By pkrauss Date 2001-12-20 Time 11:27 Sent To  
Notes
2001-12-20 00:00:00********************DENIED**************
  
  
 COMMENTS FROM FIRST REVIEW NOT
 ADDRESSED.
  
 PLEASE NOTE, ONE SET OF PLANS IS
 MISSING SHEET 5 OF 7.PLEASE SUBMIT
 THE AFOREMENTIONED SHEET TO HAVE 2
 COMPLETE SETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By pkrauss Date 2001-10-29 Time 16:04 Rev Time 0.50
Received By pkrauss Date 2001-10-29 Time 16:04 Sent To  
Notes
2001-10-29 00:00:00*******************PROVISO**************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.PLEASE NOTE DRYER EXHAUST BEING
 EXTENDED TO NEW EXTERIOR WALL SHALL
 COMPLY WITH 1997 SMC 509.3.THE
 MAXIMUM LENGTH SHALL NOT EXCEED 25'.
 THERE SHALL BE A DEDUCTION OF 2 1/2'
 FOR EACH 45 DEGREE BEND AND 5' FOR
 EACH 90 DEGREE BEND.TERMINATION
 SHALL BE LOCATED 10' FROM ANY
 ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, WINDOW,
 DOOR OR AIR INTAKE.OPENING SHALL
 BE LOCATED AT LEAST 10' ABOVE THE
 ADJOINING GRADE LEVEL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-01-22 Cont ID  
Sent By kstevens Date 2002-01-22 Time 13:31 Rev Time 0.50
Received By kstevens Date 2002-01-22 Time 13:31 Sent To  
Notes
2002-01-22 00:00:00PASSED/PROVISO
  
 SCUPPER DRAINS LOCATED AT EACH WINDOW
 OVERHANG PER ARCHITECT COMMENTS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-01-08 Cont ID  
Sent By kstevens Date 2002-01-08 Time 17:52 Rev Time 0.75
Received By kstevens Date 2002-01-08 Time 17:52 Sent To  
Notes
2002-01-08 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT 1 0F 7 PLEASE SHOW DETAILS FOR
 SCUPPERS. SHOW SIZE AND LOCATION.
 PLEASE SUBMIT DETAILS FOR NEW AND EXIST-
 ING ROOFS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-30 Cont ID  
Sent By kstevens Date 2001-10-30 Time 08:43 Rev Time 1.25
Received By kstevens Date 2001-10-30 Time 08:43 Sent To  
Notes
2001-10-30 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PAGE 1 OF 7 NEW ROOF PLAN. SUBMIT
 ROOF DRAINAGE CALCULATIONS FOR PRIMARY
 & SECONDARY ROOF DRAINS. INCLUDE 1/2 OF
 AREA OF PARAPET WALLS AND AREA OF UPPER
 ROOF DRAINING ON NEW ROOF. PLEASE SUBMIT
 DETAILS FOR PRIMARY AND SECONDARY DRAINS
 USE SPC SEC 1108 AND 1109 FOR CALCULAT-
 IONS.
 2) PAGE 1 0F 7 EXISTING ROOF PLAN. SUB-
 MIT CALCULATIONS FOR PRIMARY AND SECOND-
 ARY ROOF DRAINS FOR EXISTING ROOF TO SEE
 IF THEY COMPLY WITH PRESENT CODE. USE
 SEC 1108 & 1109 ADDING 1/2 PARAPET WALLS
 AND AREA OF ROOF THAT DRAINS FROM ABOVE.
 3) PAGE 2 0F 7 FLOOR PLAN NOTES #29.
 PLEASE SHOW DETAILS FOR SHOWER ALTERAT-
 ION. SHOW HOW SHOWERS COMPLY WITH FACBC-
 97 SEC 4.21.
 4) PLEASE INDICATE HOW 20 PERCENT OVER
 CONTRACT PRICE IS SPENT ON ADA. (36,000)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377