Plan Review Stops For Permit 01100606
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-11-27 Cont ID  
Sent By rbrown Date 2001-11-27 Time 15:06 Rev Time 0.00
Received By rbrown Date 2001-11-27 Time 15:00 Sent To  
Notes
2001-11-27 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN
 TEL: (561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE
 SBC* = STANDARD BUILDING CODE (AMENDMENT
 S)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
 FL ENERGY CODE = FLORIDA ENERGY EFFICIEN
 CY CODE FOR BUILDING CONSTRUCTION
  
  
 1) SBC* 104.2.3 DRAWING SHEETS S-1, S-2
 AND S-3 SHALL BE SIGNED AND SEALED.
  
 2) SBC* 104.2.5 SUBMIT A SURVEY DRAWING
 SIGNED AND SEALED BY A QUALIFIED
 SURVEYOR.
  
 3) AMEND ALL SECTION AND DETAIL MARKERS
 AND LABELS SO THAT THEY REFER TO THE
 CORRECT DRAWING SHEET NUMBER AS PER THE
 SYMBOL LEGEND ON SHEET SP-1.
  
 4) FL ENERGY CODE 103.0 SUBMIT THE
 APPROPRIATE ENERGY CONSERVATION CODE
 COMPLIANCE FORM.
  
 5) SBC 1006.2.2 EXTERIOR EXITWAY PORCHES
 AND STAIRS SHALL BE LOCATED AT LEAST 10
 FT FROM ADJACENT PROPERTY LINES.
  
 6) SBC 1006.2.4 OPENINGS IN WALLS WITHIN
 10 FT OF EXTERIOR EXITWAY STAIRS SHALL
 BE EQUIPPED WITH FIXED 3/4 HOUR
 ASSEMBLIES.
  
 7) SBC 1007.1.4 CLOSETS SHALL NOT BE
 LOCATED BENEATH STAIRS UNLESS SUCH
 STAIRS ARE PROTECTED AS REQUIRED BY
 1006.1.1.SUBMIT DETAILS STATING
 PROPOSED MEANS OF PROTECTION FOR THE
 STAIRCASE.
  
 8) SBC 1007.4.2 AND 1007.6.2 THE WIDTH
 OF LANDINGS SHALL NOT BE LESS THAN THE
 STAIRWAYS THE SERVE.INCREASE THE WIDTH
 OF THE HALF LANDING TO CONFORM.
  
 9) SBC 1012.1.5 WHEN FULLY OPEN, A DOOR
 SHALL NOT PROJECT MORE THAN 7 INCHES
 INTO THE REQUIRED WIDTH OF A LANDING.
 AMEND THE CONFIGURATION OF THE EXIT DOOR
 FROM FOYER 211 TO CONFORM.
  
 10) SBC 1007.5.1 AND 1015.2 THE HEIGHT
 OF HANDRAILS SHALL BE BETWEEN 34" AND
 38" ABOVE THE LEADING EDGE OF A TREAD.
 THE HEIGHT OF GUARDRAILS SHALL BE AT
 LEAST 42".HANDRAILS THAT FORM PART OF
 A GUARDRAIL MAY BE BETWEEN 38" AND 42"
 HIGH. ADD DIMENSIONS TO THE STAIR
 SECTION TO SHOW COMPLIANCE.
  
 11) SBC 1007.5.4 HANDRAIL GRIPPING
 SURFACES SHALL BE CONTINUOUS, WITHOUT
 INTERRUPTION BY NEWEL POSTS OR OTHER
 OBSTRUCTIONS.
  
 12) SBC 1007.5.5 HANDRAILS SHALL EXTEND
 AND CONTINUE TO SLOPE FOR A DISTANCE
 EQUAL TO ONE TREAD DEPTH BEYOND THE
 BOTTOM RISER.
  
 13) SBC* 1804.2.2 SOIL BEARING CAPACITY
 TEST REPORTS SHALL BE SUBMITTED.
  
 14) SBC 1804.4 FOOTING DESIGN.SUBMIT
 CALCULATIONS FOR THE EXISTING FOOTINGS
 WHICH ARE TO SUPPORT INCREASED LOADING
 AND FOR ALL NEW FOOTINGS.
  
 15) SBC* 1503.3.2 ROOF COVERINGS AND
 SYSTEMS SHALL BE DESIGNED TO WITHSTAND
 THE APPROPRIATE WIND LOADS PRESCRIBED IN
 1606.
  
 16) SBC 1606.2 WIND LOADS.THE DESIGN
 OF ALL ROOFS AND FASTENERS, INCLUDING
 THE OPEN WALKWAY AND STAIRCASE ROOFS,
 SHALL BE BASED UPON THE APPROPRIATE WIND
 VELOCITY PRESSURE AND PRESSURE
 COEFFIENTS.SUBMIT CALCULATIONS TO SHOW
 CONFORMITY.
  
 17) SBC 1507 SUBMIT DETAILS TO SHOW
 CONFORMITY WITH THE REQUIREMENTS FOR
 ROOF TILES AND FASTENING.
  
 18) SBC* 1606.4 EXTERIOR GLAZED OPENINGS
 SHALL BE DESIGNED FOR IMPACTS, FROM WIND
 BORNE DEBRIS, IN ACCORDANCE WITH 1606.4
 AS AMENDED
  
 19) SBC* 1707.4 EXTERIOR WINDOW AND DOOR
 ASSEMBLIES. SUBMIT PRODUCT APPROVALS,
 WHICH SHALL INCLUDE MULLIONS WERE
 APPROPRIATE.
  
 20) SBC* 104.2.2ADDITIONAL DATA.
 CALCULATIONS AND DETAILS SHALL BE
 SUBMITTED TO SHOW THE MEANS OF SUPPORT
 FOR THE SECOND FLOOR WEST ELEVATION WALL
 ABOVE THE THE PROPOSED FIRST FLOOR
 OPENING AND THE MEANS OF SUPPORT FOR THE
 NEW SECOND FLOOR 8" CMU WALL
 CONSTRUCTION BETWEEN THE STAIRCASE AND
 THE ADJACENT FOYER.
  
 21) FL ACC CODE 4.13.5 ADD DIMENSIONS OR
 DOOR SCHEDULE REFERENCES TO DEMONSTRATE
 A MINIMUM CLEAR OPENING WIDTH OF 32" FOR
 THE DOORS LEADING FROM WORK AREA
 (ROOM 108).
  
 22) FL ACC CODE 4.15AN ACCESSIBLE
 DRINKING FOUNTAIN SHALL BE PROVIDED.
  
 23) FL ACC CODE 4.16 AND 4.19 SUBMIT
 DETAILS TO DEMONSTRATE CONFORMITY WITH
 THE DIMENSIONAL AND EQUIPMENT
 REQUIREMENTS FOR ACCESSIBLE WATER
 CLOSETS AND LAVATORIES.
  
 24) FL ACC CODE 4.26 GRAB RAILS SHALL
 COMPLY WITH THE REQUIREMENTS FOR SIZE,
 STRENGTH AND TYPE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-11-05 Cont ID  
Sent By dpalmer Date 2001-11-05 Time 20:48 Rev Time 0.00
Received By dpalmer Date 2001-11-05 Time 20:48 Sent To  
Notes
2001-11-05 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT THE SEOCND
 SERVICE (METER BANK #2 ) NEEDS TO HAVE
 MAINS LABELED AS MAINS 1-5. PLEASE NOTE
 THAT THIS IS A SEPARATE SERVICE FROM
 THE OTHER BLDG (METER 1).
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 WITH CIRCUIT #`S ON PLANS.
 PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE BATH GFI FOR PANEL
 "F" APT SHOW BATH GFI ON CIRCUIT #13
 W/ OTHER OUTLETS? PLEASE CORRECT.
 210-11-C-3.
  
 4)NOTE: PLEASE NOTE EGRESS LIGHTING FOR
 BEDROOMS, SHOWN AS FANS?? CLARIFY IF
 THEY ARE FAN/LT KITS? PLEASE SHOW.
  
 5)NOTE: PLEASE NOTE LOCATION OF WATER
 HEATER UNDER CABINET IN KITCHEN DOES NOT
 SEEM TO MEET ACCESS OR CLEARENCE CODES
 FOR HEATING APPLIANCES OR DISCONNECTING
 MEANS. 110-26 PLEASE CLARIFY WATER
 HEATER SHOWN IN CORNER? DOORS CABINET
 WALLS?
  
 6) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 7)NOTE: PLEASE NOTE MISSING OUTLET FOR
 APT "C" BEDROOM WALL. 210-52 2' OF
 WALL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2001-10-30 Cont ID  
Sent By mamini Date 2001-10-30 Time 14:12 Rev Time 1.00
Received By mamini Date 2001-10-30 Time 14:12 Sent To  
Notes
2001-10-30 00:00:00FAILLED:
 1. PLEASE PROVIDE PERVIOUS & IMPERVIOUS
 CALCULATIONS FOR THE SITE DUE TO THE
 PROPOSED CHANGES.
 2. PLEASE PROVIDE PLAN IF THERE IS GOING
 TO BE NEW CONNECTIONS OR CAHNGES IN SIZE
 TO UTILITIES SERVICES.
 3. PLEASE PROVIDE POLLUTION PREVENTION
 PLAN. PLAN SHOULD BE INSTALLED IN FIELD
 PRIOR TO ANY SITE WORK.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-25 Cont ID  
Sent By mcarsill Date 2001-10-25 Time 15:12 Rev Time 0.00
Received By mcarsill Date 2001-10-25 Time 15:12 Sent To  
Notes
2001-10-25 00:00:001) NO SMOKE DETECTORS OBSERVED IN
 RESIDENTIAL UNITS. ELECTRIC POWERED
 SMOKE DETECTORS ARE REQUIRED.
 2) RESIDENTIAL UNIT DOORS TO BE AT
 LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES.
 3) RESIDENTIAL UNITS ARE TO BE SEPARATED
 FROM ONE ANOTHER BY AT LEAST ONE HOUR.
 4) PLEASE INDICATE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILINGS.
 5) EXIT DISCHARGE LOCATIONS NEAR AIR
 HANDLING UNITS DOES NOT MEET
 MINIMUM CODE REQUIREMENTS.
 6) BOTH EXITS FROM WORK AREA 108 ARE
 NOT PROPERLY SEPARATED FROM ONE ANOTHER
 BY AT LEAST 1/2 THE DIAGONAL DISTANCE.
 7) FABRIC AWNINGS TO BE FIRE RETARDANT
 MATERIAL.
 8) WINDOWS NOTED WITHIN 10 FEET OF
 STAIRS, PLEASE EXPLAIN PROTECTION.
 9) ARE THE CLOSETS SHOWN ON THE
 STAIRS FLOOR PLAN LOCATED UNDERNEATH
 THE STAIRS. IF SO WHAT IS THE
 FIRE RATING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-11-07 Cont ID  
Sent By ndenmark Date 2001-11-07 Time 12:05 Rev Time 0.33
Received By ndenmark Date 2001-11-07 Time 12:05 Sent To  
Notes
2001-11-07 00:00:00NO MECHANICAL INFORMATION INCLUDED FOR
 REVIEW.
 PROVIDE INFORMATION ON DUCT, EQUIPMENT,
 FIRE DAMPERS, BATHROOM EXHAUST, OUTSIDE
 AIR CACULATIONS FOR REVIEW

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-11-03 Cont ID  
Sent By kstevens Date 2001-11-03 Time 14:56 Rev Time 0.50
Received By kstevens Date 2001-11-03 Time 14:56 Sent To  
Notes
2001-11-03 00:00:00DENIED
  
 PLEASE SUBMIT 2 FULL SETS OF PLANS.
 M1, M2, P1, & P2 INDICATED ON FRONT PAGE
 (1) WERE NOT SUBMITTED WITH THESE SETS
 OF PLANS. PLEASE RESUBMIT FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status F Date 2001-10-25 Cont ID  
Sent By sgraham Date 2001-10-25 Time 09:32 Rev Time 1.00
Received By sgraham Date   Time   Sent To  
Notes
2001-10-25 00:00:001.NEED LANDSCAPE PLAN WITH LIGHTING.
 2.19.01 OF GLAZING REQUIRED(4 MORE
 FEET REQUIRED )
 3.EAST ELEVATION VERTICAL PROPORTION
 IS REQUIRED
 4.EAST ELEVATION-OPENING IN UPPER
 STORIES SHALL CENTERED OVER OPENING ON
 LOWER STORY