Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-30 Cont ID  
Sent By mcarsill Date 2001-10-30 Time 15:57 Rev Time 0.00
Received By mcarsill Date 2001-10-30 Time 15:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-09 Cont ID  
Sent By mcarsill Date 2001-10-09 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2001-10-09 Time 10:58 Sent To  
Notes
2001-10-09 00:00:001) WHY IS THERE NO MANUAL PULL STATION
 SHOWN NEAR THE STAIRWAY. IS THERE AN
 EXISTING ONE?
 2) NO HORN STROBES SHOWN IN THE AREA
 OF THE MEDITATION, SALON, WAITING, OR
 MEDITATION AREAS.
 3) A SMOKE DETECTOR IS SHOWN IN THE
 LAUNDRY ROOM. A HEAT DETECTOR WOULD
 BETTER SERVE THIS LOCATION.
 4) WHY IS THERE NO SMOKE DETECTOR
 SHOWN AT THE ELEVATOR AREA. IS THERE
 AN EXISTING ONE?
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910