Plan Review Details - Permit 01100405
Plan Review Stops For Permit 01100405
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-19 Cont ID  
Sent By jwitmer Date 2001-11-19 Time 17:35 Rev Time 1.00
Received By jwitmer Date 2001-11-19 Time 17:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By jwitmer Date 2001-10-29 Time 18:37 Rev Time 1.00
Received By jwitmer Date 2001-10-29 Time 18:37 Sent To  
Notes
2001-10-29 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01100405
 460 S ROSEMARY AV / 172
 PLAN REVIEW
 CITY PLACE RETAIL LLC
 833-6888
  
 1)- SHEET A-3 INDICATES THAT THERE IS TO
 BE IMPACT RESISTANT GLASS, MISSING
 PRODUCT APPROVAL,SBCCI OR DADE COUNTY
 REPORTS (2 COPIES).
  
 2)- PLANS DEPICT SOFFITS HUNG FROM THE
 CEILING, NO DETAILS NOR FRAMING INFORMA-
 TION.
  
 3)- SBC TABLE 803.3 MINIMUM INTERIOR
 FINISH CLASSIFICATION, IS THIS BUILDING
 SPRINKLERED?
  
 4)- STOREFRONT DETAIL#5 ALSO DOESN'T
 GIVE INFORMATION ON THE FRAMING REQUIRED
 FOR THE RECESSED STOREFRONT
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2001-10-24 Cont ID  
Sent By dpalmer Date 2001-10-24 Time 20:10 Rev Time 0.00
Received By dpalmer Date 2001-10-24 Time 20:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-14 Cont ID  
Sent By mcarsill Date 2001-11-14 Time 10:04 Rev Time 0.00
Received By mcarsill Date 2001-11-14 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-10 Cont ID  
Sent By mcarsill Date 2001-10-10 Time 09:12 Rev Time 0.00
Received By mcarsill Date 2001-10-10 Time 09:12 Sent To  
Notes
2001-10-10 00:00:001) A FIRE SPRINKLER HEAD WILL BE
 REQUIRED OUTSIDE OF FRONT DOOR IN
 RECESSED AREA.
 2) NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS FOR THE WALLS
 AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-11-21 Cont ID  
Sent By pkrauss Date 2001-11-21 Time 13:09 Rev Time 0.35
Received By pkrauss Date 2001-11-21 Time 13:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status C Date 2001-10-16 Cont ID  
Sent By ndenmark Date 2001-10-16 Time 10:02 Rev Time 0.33
Received By ndenmark Date 2001-10-16 Time 10:02 Sent To  
Notes
2001-10-16 00:00:00PROVISO:
 1. OUTSIDE AIR BALANCE CONFLICTS W/ THE
 ASHRAE CALCULATIONS. ASHRAE REQUIRED 210
 CFM OF OUTSIDE AIR IS REQUIRED.
 2. LOCATE AHU WITH RESPECT TO BUILDING C
 ONSTRUCTION TO ALLOW FOR SERVICE AND REP
 LACEMENT PER SMC 304.2

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-16 Cont ID  
Sent By kstevens Date 2001-11-16 Time 14:56 Rev Time 0.50
Received By kstevens Date 2001-11-16 Time 14:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By kstevens Date 2001-10-29 Time 15:26 Rev Time 0.50
Received By kstevens Date 2001-10-29 Time 15:26 Sent To  
Notes
2001-10-29 00:00:00DENIED
 REFERENCE SPC-94
  
 1) PAGE MP-1, WATER RISER DIAGRAM.
 AIR CHAMBERS ARE "QUICK FIX" AND NEED TO
 BE ACCESSIBLE AND RECHARGEABLE PER WH-
 PDI 201. WATER HAMMER ARRESTORS SHALL BE
 INSTALLED PER MANUFACTURES INSTALLATION
 INSTRUCTIONS AND WH-PDI 201, DOWN CLOSE
 TO FIXTURES NOT AT TOP OF DROP AS SHOWN.
 PLEASE SUBMIT RISER DIAGRAM SHOWING
 THIS FOR PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 569-8096 EXT 8377