Plan Review Details - Permit 01100399
Plan Review Stops For Permit 01100399
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-10-09 Cont ID  
Sent By mcarsill Date 2001-10-09 Time 08:58 Rev Time 0.00
Received By mcarsill Date 2001-10-09 Time 08:58 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2001-10-16 Cont ID  
Sent By mcarsill Date 2001-10-16 Time 09:41 Rev Time 0.00
Received By mcarsill Date 2001-10-16 Time 09:41 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 1 Status F Date 2001-10-09 Cont ID  
Sent By mcarsill Date 2001-10-09 Time 08:58 Rev Time 0.00
Received By mcarsill Date 2001-10-09 Time 08:58 Sent To  
Notes
2001-10-09 00:00:001) PLEASE INDICATE ON PLANS WHERE THE
 NEAREST FIRE HYDRANT IS LOCATED TO
 THE DOCKS.
 2) PLEASE INDICATE HOW THE STANDPIPE
 WILL BE SUPPORTED TO THE DOCKS.
 3) ARE ANY CONNECTIONS PRESENT TO SUPPLY
 THE STANDPIPE SYSTEM.
 4) THE STANDPIPE SYSTEM WET OR DRY.
 5) PLEASE PROVIDE DETAIL ON STANDPIPE
 HOSE VALVES.
 6) PLANS DO NOT INDICATE PRESSURE
 TESTING OF PIPING.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-10-16 Cont ID  
Sent By mcarsill Date 2001-10-16 Time 09:41 Rev Time 0.00
Received By mcarsill Date 2001-10-16 Time 09:41 Sent To  
Notes
***NONE***