| Plan Review Stops For Permit 01100392 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-12-03 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-12-03 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-30 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | PROVIDE THE MIXED OCCUPANCY SEPARATION | | | REQUIREMENTS OF SBC 704.1.1 (2HR) | | | BETWEEN THE OFFICE B, AND WAREHOUSE, S, | | | USES. | | | | | | WHEN PRODUCT TEST REPORTS OR NOTICE OF | | | ACCEPTANCES ARE NOT INCLUDED AT TIME OF | | | PERMIT APPLICATION, A SEPARATE PERMIT | | | AND FEES WILL BE REQUIRED. | | | | | | PLEASE DECLARE THE NATURE OF BUSINESS | | | USE AND THE TYPE OF WARES THAT WILL BE | | | STORED.SEE SBC 104.2. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-02-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-21 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-21 |
Time |
06:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
22:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-10 |
Time |
22:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-02-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-22 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-22 |
Time |
10:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-11-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-11-14 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-11-14 |
Time |
10:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-10 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-10 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2001-10-10 00:00:00 | 1) NO FIRE SPRINKLER PLANS PROVIDED | | | WITH PLANS. NOTES ON COVER PAGE | | | INDICATES THAT TENANT SPACES WILL | | | BE FIRE SPRINKLER PROTECTED. | | | 2) PLEASE INDICATE LOCATIONS OF | | | PORTABLE FIRE EXTINGUISHERS IN BOTH | | | TENANT SPACES. | | | 3) EMERGENCY LIGHTING EQUIPMENT SHOWN | | | IN WAREHOUSE MAY NOT BE ADEQUATE TO | | | ILLUMINATE THE MEANS OF EGRESS DUE TO | | | THE DISTANCE FROM THE REAR DOOR. | | | 4) ARE ANY RACK STORAGE UNITS | | | ANTICIPATED FOR THE WAREHOUSE AREA. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-02-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-21 |
Time |
10:49 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-02-21 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2002-02-21 00:00:00 | | | | PROVISO: | | | | | | RTU-3 & RTU-1, DUCTS APPEAR TO BE | | | PENETRATING NEW 2 HR RATED WALL.FIRE | | | DAMPERS ARE REQUIRED IN WALLS HAVING A | | | FIRE RESISTANCE RATING OF 1 OR MORE | | | HOURS. | | | | | | FIRE DAMPERS SHALL COMPLY WITH UL 555 & | | | SHALL BEAR THE LABLE OF AN APPROVED | | | TESTING AGENCY. | | | | | | PROVIDE LOCATION AND INSTALLATION | | | DETAILS OF THE DAMPERS PRIOR TO | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-11-19 |
Time |
16:43 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-11-19 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-10-15 |
Time |
13:33 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2001-10-15 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-19 |
Time |
11:34 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-02-19 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2002-02-19 00:00:00 | REVISION - AAV'S - KITCHEN LAYOUT CHANGE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2001-10-21 |
Time |
07:53 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-21 00:00:00 | PLUMBING PROVISO,SEE SHTS A2,A7 FACBC. |
|
|