Plan Review Details - Permit 01100098
Plan Review Stops For Permit 01100098
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-10-03 Cont ID  
Sent By mcarsill Date 2001-10-03 Time 08:24 Rev Time 0.00
Received By mcarsill Date 2001-10-03 Time 08:24 Sent To  
Notes
2001-10-03 00:00:00TWO AIR PACKS WILL BE REQUIRED SINCE
 THE ROOM IS CONSIDERED HAZARDOUS. SINGLE
 WORK GROUPS NOT PERMITTED, TWO PERSONS
 MUST WORK IN HAZARDOUS AREAS NOT ONE.
 AIR PACKS PROVIDED MUST MEET ALL
 REQUIRED STANDARDS FOR HAZARDOUS AREAS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-10-03 Cont ID  
Sent By pkrauss Date 2001-10-03 Time 07:41 Rev Time 0.40
Received By pkrauss Date 2001-10-03 Time 07:35 Sent To  
Notes
2001-10-03 00:00:00******************PROVISO***************
  
  
 PRIOR TO FINAL INSPECTION BUILDING
 DEPARTMENT REQUIRES A SIGNED, SEALED
 AND DATED LETTER FROM STRUCTURAL
 ENGINEER CERTIFYING STABLITY OF
 STRUCTURAL SUPPORT FOR COOLING TOWER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By pkrauss Date 2001-10-01 Time 16:12 Rev Time 1.00
Received By pkrauss Date 2001-10-01 Time 15:32 Sent To  
Notes
2001-10-01 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE A PLAN OF MECHANICAL
 ROOM.SHOW COMPLIANCE WITH 1997 SMC
 CHAPTER 11.PLAN SHALL INDICATE THE
 FOLLOWING.PLANS SHALL BE SIGNED, DATED
 AND SEALED BY ENGINEER.
  
 1.LOCATION OF MECHINERY ROOM IN
 RELATION TO THE BUILDING.
  
 2.VENTILATION REQUIREMENTS FOR NORMAL
 AS WELL AS AN EMERGENCY CONDITIONS.
 SHOW CALCULATIONS FOR BOTH
 SITUATIONS. (1997 SMC 1105.7.4 &
 1105.7.5)
  
 3.INDICATE MAKE-UP AIR.
  
 4.INDICATE LOCATION OF LEAK DETECTOR.
  
 5.SHOW TERMINATION OF RELIEF DEVICES.
 (NOTE, NOT LESS THAN 15' ABOVE THE
 ADJOINING GROUND LEVEL AND NOT LESS
 THAN 20' FROM ANY WINDOW, EXIT TO
 ANY BUILDING, VENTILATION OPENING)
  
 6.INDICATE LOCATION OF BREATHING
 APPARATUS.
  
 7.SUBMIT ENGINEERED PLANS FOR
 STRUCTURAL STEEL REPLACEMENT FOR
 COOLING TOWER.LOAD CALCULATIONS.
  
 8.INDICATE HOW SENSORS AND VENTILATION
 WILL BE TIED INTO EMERGENCY POWER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.