| Plan Review Stops For Permit 01091712 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-04-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-04-19 |
Time |
09:09 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-03-11 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-03-11 |
Time |
15:46 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-11 00:00:00 | TRUSS ENGINEERING | | | ----------------- | | | | | | TRUSS DESIGN SHALL COMPLY WITH | | | BUIDING DESIGN. | | | | | | TRUSSES ASCE-93 | | | BUILDINGASCE-98 | | | | | | L.MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-12-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-12-21 |
Time |
14:39 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-21 00:00:00 | BUILDING COMMENTS | | | | | | | | | PROVISO | | | ------- | | | | | | COUNTY IMPACT FEES SHALL BE PAID. | | | | | | A SEPERATE PERMIT WILL BE REQUIRED FOR | | | THE WINDOWS, DOORS AND ROOF. | | | | | | | | | | | | LUIS MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-16 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-11-16 |
Time |
09:27 |
Rev Time |
10.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-11-16 00:00:00 | | | | BUILDING COMMENTS | | | ----------------- | | | | | | 1] | | | SUBMIT A CURRENT SIGNED AND SEALED | | | PROPERTY SURVEY. VERIFY FLOOD ZONE. | | | 2] | | | SHEET A2.0, WEST ELEVATION SHOWS GLASS | | | BLOCK WITHIN THE BOND BEAM. | | | 3] | | | SECTION 4.13.6, FL. ACC. CODE REQUIRES | | | MINIMUM 18" CLEAR ON PULL SIDE OF DOORS | | | E01, AND 03. | | | 4] | | | SUBMIT PRODUCT TEST REPORTS FOR ROOF | | | COVER, WINDOWS, DOORS, AND SIDING. | | | 5] | | | A RECORDED NOTICE OF COMMENCEMENT IS | | | REQUIRED. | | | 6] | | | COUNTY IMPACT FEES AND CITY TRAINING | | | FEES ARE DUE. | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-05 |
Time |
20:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-05 |
Time |
20:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-30 |
Time |
20:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-30 |
Time |
20:29 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | ******************* UNSAT ************ | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | SUBMITTED FOR PANELS BUT NOT FOR MAIN. | | | | | | 2)NOTE: PLEASE NOTE THAT THE PLANS DO | | | NOT SHOW ANY LOAD CALCULATIONS? ALSO | | | ALL CONTINOUS LOADS ARE TO BE SHOWN AT | | | 125% . 215-5/215-2-3/ 230-42 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-11-13 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-11-13 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2001-12-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-26 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-26 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2001-12-26 00:00:00 | ON 12.24.01 RECEIVED A LETTER FROM | | | TIMOTHY F. HULLIHAN INDICATING THAT | | | THE SINGLE EXIT WILL BE ONE HOUR FIRE | | | PROTECTED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-10 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-10 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2001-12-10 00:00:00 | 1) PLEASE INDICATE ON THE PLANS THAT | | | THE STAIR WILL BE ENCLOSED BY A ONE | | | HOUR FIRE RATING. SINGLE EXIT RATIONALE | | | IF BEING USED MUST COMPLY WITH | | | SECTION 5-1.3 WHICH REQUIRES THAT | | | EXIT STAIRS MUST BE RATED BY AT LEAST | | | ONE HOUR WHEN IT CONNECTS THREE STORIES | | | OR LESS. THIS WOULD INCLUDE DOORS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-31 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-31 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2001-10-31 00:00:00 | 1) A SINGLE MEANS OF EGRESS IS SHOWN | | | FROM THE SECOND WHICH IS NOT | | | PROTECTED. THE FIRE CODE REQUIRES | | | AT LEAST TWO MEANS OF EGRESS SHALL BE | | | PROVIDED AT EVERY LEVEL. THE TWO | | | EXCEPTIONS ARE AS FOLLOWS: | | | | | | # 1, OCCUPANT LOAD OF LESS THAN 100 | | | PERSONS, DIRECT ACCESS TO THE OUTSIDE, | | | TOTAL TRAVEL DISTANCE LESS THAN 100 | | | FEET, AND COMPLETELY SEPARATED FROM | | | OTHER PARTS OF THE BUILDING. | | | | | | # 2, BUILDING LESS THAN THREE STORIES, | | | OCCUPANT LOAD LESS THAN 30 PERSONS, | | | TRAVEL DISTANCE LESS THAN 100 FEET, AND | | | EXIT IS ENCLOSED. | | | | | | UNPROTECTED VERTICAL OPENINGS ARE | | | PERMITTED WITH THE FOLLOWING CONDITIONS: | | | THE AREA IS LOW HAZARD OR ORDINARY | | | HAZARD, THE LOWEST OR NEXT LEVEL IS | | | THE STREET FLOOR, AREA IS OPEN AND | | | UNOBSTRUCTED, AND EXIT CAPACITY CAN | | | PROVIDE FOR ALL OCCUPANTS. THE OTHER | | | EXCEPTION INDICATES CONNECTION WITH | | | TWO FLOORS, THE OPENING IS NOT A | | | REQUIRED MEANS OF EGRESS, OPENING IS | | | NOT CONNECTED WITH STAIRWAYS OR | | | CORRIDORS, AND A FIRE SPRINKLER SYSTEM | | | IS PROVIDED. | | | | | | BUISNESS OCCUPANCIES ACCORDING TO THE | | | FIRE CODE IS CONSIDERED AN ORDINARY | | | HAZARD. (CONTENTS) | | | | | | THE CODE ALSO INDICATES THAT WHERE | | | CHAPTERS 1-7 ARE DIFFERENT FROM 8-30, | | | THE INFORMATION IN CHAPTERS 8-30 | | | SHALL APPLY. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-27 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2001-12-27 |
Time |
14:22 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2001-12-27 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2001-12-27 00:00:00 | PROVISO: | | | DUCT PENETRATING RATED STAIR CEILING | | | SHALL BE PROTECTED PER 1997 SMC 610.2 | | | PROVIDE DETAIL PRIOR TO INSPECTION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-14 |
Time |
12:35 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-12-14 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2001-12-14 00:00:00 | *******************PROVISO************** | | | | | | PLEASE NOTE, AS PER 1997 SBC 1006.1.3.1, | | | PENETRATIONS INTO AND OPENINGS THROUGH | | | A STAIRWAY ENCLOSURE ASSEMBLY ASRE | | | PROHIBITED EXCEPT FOR REQUIRED EXIT | | | DOORS, DUCTWORK & EQUIPMENT NECESSARU | | | FOR INDEPENDENT STAIR PRESSURIZATION, | | | SPRINKLER PIPING, STANDPIPES, AND | | | ELECTRICAL CONDUIT SERVING THE STAIRWAY | | | AND TERMINATING AT A STEEL BOX NOTY | | | EXCEEDING 16 SQ INCHES. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-30 |
Time |
13:20 |
Rev Time |
1.20 |
| Received By |
pkrauss |
Date |
2001-10-30 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2001-10-30 00:00:00 | ********************DENIED************** | | | | | | PLANS DO NOT SPECIFY THAT DUCTWORK IS | | | IN A FIRE RATED ENCLOSURE. | | | | | | AS PER 1997 SMC 610.4, DUCTS PENETRATING | | | ONLY ONE FLOOR MAY BE PROTECTED BY | | | INSTALLING A LISTED FIRE DAMPER WHERE | | | THE FLOOR IS PIERCED IN LIEU OF AN | | | ENCLOSURE. | | | | | | OUTSIDE AIR CALCULATIONS ONLY INDICATE | | | OFFICE AREAS AND STORAGE AREAS.THERE | | | IS NO "STORAGE AREA" INDICATED ON THE | | | FLOOR PLAN.ONLY 2 PRIVATE OFFICES, A | | | WORKROOM AND CONSULATION.PLEASE | | | REVISE OUTSIDE AIR CALCULATIONS TO | | | REFLECT ALL AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-02-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-04 |
Time |
13:53 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2002-02-04 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2002-02-04 00:00:00 | REVISION PASSED - NO TOILET IN ROOM | | | JUST SINK (LAV). |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-01-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-03 |
Time |
10:50 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-01-03 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2002-01-03 00:00:00 | PASSED/PROVISO | | | REFERENCE: SPC-94-FACBC-97 | | | | | | REVISED PLANS SHOWING COMPLIANCE FOR | | | ADAPTABLE BATHROOM REQUIRED BEFORE FIRST | | | INSPECTION. | | | | | | KSTEVENS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-20 |
Time |
13:50 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-12-20 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2001-12-20 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT A1.0 TOILET ROOM SHALL BE ADAPT- | | | ABLE. 30" REQUIRED FROM C/L OF W/C TO | | | C/L OF LAV. LAV TO BE 15" OFF WALL TO | | | C/L. 63" FINISH OPENING REQUIRED FOR | | | THESE REQUIREMENTS. 5' OPENING SHOWN. | | | | | | 2) SHT A1.0 DOOR SHALL NOT SWING INTO | | | CLEAR FLOOR SPACE OF LAV. DOOR MUST | | | MUST SWING OUT OF TOILET ROOM. FACBC SEC | | | 422.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-11-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-11-02 |
Time |
18:59 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-11-02 |
Time |
18:58 |
Sent To |
|
|
| Notes |
| 2001-11-02 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PAGE A1.0 TOILET ROOM. PLEASE SUBMIT | | | DETAILS TO SHOW COMPLIANCE WITH FACBC-97 | | | SEC. 4.22. SHOW CLEAR FLOOR SPACE SEC | | | 4.22.3, W/C TO BE 1'6" OFF WALL, LAV TO | | | BE 1'3" OFF WALL. SHOWER TO COMPLY WITH | | | SEC 4.21 PLEASE SHOW DETAILS. | | | 2) PAGE A1.0 & PAGE P-1. FLOOR DRAIN | | | REQUIRED IN TOILET ROOM AND SHALL BE | | | EQUIPPED WITH A TRAP PRIMER. SPC SEC | | | 409.4.1.1 | | | 3) PAGE P-2 GENERAL NOTES #16. AIR | | | CHAMBERS SHALL COMPLY WITH SPC 607.8.3 | | | AND BE RECHARGEABLE AND ACCESSIBLE. ALSO | | | THEY ARE A "QUICK FIX" AND WATER HAMMER | | | ARRESTORS SHOULD BE USED. THEY SHALL BE | | | SIZED AND LOCATED PER MANU. INSTALL. IN- | | | STRUCTIONS AND WH-PDI 201, CLOSE TO FIX- | | | TURE. | | | 4) PAGE P-1 KEYNOTES #'S 12 & 13. SEPAR- | | | ATE PERMIT REQUIRED FOR GAS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-17 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-17 |
Time |
09:56 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|