| Plan Review Stops For Permit 01091708 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-01-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-01-07 |
Time |
12:15 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2002-01-07 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2002-01-07 00:00:00 | PRODUCT APPROVAL CHECKLIST: | | | 1-FRENCH DOOR SITE SPECIFIC PRODUCT | | | APPROVAL: | | | A)MANUFACTURER'S ENGINEER TO PROVIDE | | | ORIGINAL SIGNATURE AND OFFICE ADDRESS | | | & PHONE NUMBER AS REQUIRED BY CHAPTER | | | 471 FLORIDA STATUTES WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. | | | B)USE CITY SAMPLE (ATTACHED) WHEN | | | SUBMITTING INFORMATION FOR SITE | | | SPECIFIC PRODUCT APPROVAL. | | | C)PROFESSIONAL ENGINEER OF RECORD NEED | | | TO SIGN, SEAL & DATE THIS SPECIFIC | | | PRODUCT APPROVAL FORM AS WELL. | | | -INCLUDE ALL HIS INFORMATION AS REQ'D | | | BY CHAPTER 471 FLORIDA STATUTES. | | | -SPECIFY LOCATION. THIS IS A SITE | | | SPECIFIC INSTALLATION. | | | D)CLARIFY WHY THE 2X WOOD BUCK IS NOT | | | STRUCTURAL. SEE SECTION 4.2 OF PRODUCT | | | APPROVAL INFORMATION SUBMITTED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-12-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-12-07 |
Time |
14:04 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2001-12-07 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2001-12-07 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE AO. NEED THE ELEVATION | | | CERTIFICATE. | | | 2-NEED ADDITIONAL SOIL BORINGS FOR EACH | | | STRUCTURE AS RECOMMENDED ON THE PRE- | | | LIMINARY SOIL TEST REPORT. | | | 3-PROVIDE PRODUCT APPROVAL FOR FRENCH | | | DOORS ASSEMBLIES AS SHOWN ON PLANS IF | | | OPTION IS SELECTED. | | | 4-PROVIDE MANUFACTURER'S CERTIFICATION | | | FOR TWO HOUR FIRE RATED CONCRETE BLOCK | | | ACCORDING TO THE BLOCK'S EQUIVALENT | | | THICKNESS AND AGGREGATES USED. SEE | | | SECTION 709.3 SBC 1997. | | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS UNDER A SEPARATE PERMIT. | | | | | | | | | NOTES: | | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | | PERMIT #01091708. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01091708, 01091723, 01091730 AND | | | 01091719. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-11-07 |
Time |
13:11 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-11-07 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2001-11-07 00:00:00 | CHECKLIST: | | | 1-SEE COMMENTS BY PLUMBING. REVISE | | | ORIGINAL DRAWINGS TO AVOID DELAYS AND | | | ADDITIONAL FEES. | | | 2-NEED TO RECORD N.O.C. | | | 3-NEED ADDITIONAL SOIL BORINGS FOR EACH | | | STRUCTURE AS RECOMMENDED ON THE PRE- | | | LIMINARY SOIL TEST REPORT. | | | 4-PROVIDE PRODUCT APPROVAL FOR: | | | -GARAGE DOOR PRODUCT APPROVAL WAS | | | DELETED BY SBCCI. | | | -WINDOW MULLIONS. | | | 5-CLEARLY INDICATE ON PLANS OPTIONS TO | | | BE BUILT AND PROVIDE PRODUCT APPROVAL | | | OR DELETE OPTIONS. | | | 6-OWES ADDITIONAL FEES. PLEASE BRING | | | BACK PAID RECEIPTS. | | | 7-PROVIDE MANUFACTURER'S CERTIFICATION | | | FOR 2 HOUR FIRE RATED CONCRETE BLOCK | | | SPECIFYING HOW IT COMPLIES WITH SEC. | | | 709.3 SBC 1997 ACCORDING TO THE | | | EQUIVALENT THICKNESS AND AGGREGATES | | | USED. | | | 8-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS OR APPLY FOR SEPARATE PERMIT. | | | | | | | | | | | | NOTES: | | | -DRAWINGS TO BE FILED UNDER PERMIT # | | | 01091708. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01091708, 01091723, 01091730 AND | | | 01091719. | | 2001-11-06 00:00:00 | CHECKLIST: | | | 1-SEE COMMENTS BY PLUMBING. REVISE | | | ORIGINAL DRAWINGS TO AVOID DELAYS AND | | | ADDITIONAL FEES. | | | 2-NEED TO RECORD NOTICE OF COMMENCEMENT. | | | 3- |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-09-23 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-23 |
Time |
09:17 |
Rev Time |
0.25 |
| Received By |
btrobaug |
Date |
2002-09-23 |
Time |
08:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-10-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-23 |
Time |
22:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-23 |
Time |
22:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-12-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-06 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-06 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2001-12-06 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | 2) BUILDING ADDRESSES REQUIRED. | | | 3) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 4) ELECTRIC POWERED SMOKE DETECTORS | | | REQUIRED. | | | 5) EGRESS WINDOWS TO COMPLY WITH | | | BUILDING AND FIRE CODE REGULATIONS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-29 |
Time |
16:24 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-01-29 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2002-01-29 00:00:00 | MECH REV PERMIT 01091749 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-10-08 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2001-10-08 |
Time |
07:20 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2001-10-08 |
Time |
07:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-12-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-01 |
Time |
06:46 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-12-01 |
Time |
06:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-10-17 |
Time |
18:35 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-17 00:00:00 | SEE REVIEW NOTES UNDER P 01091719 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-02 |
Time |
14:50 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|