Plan Review Details - Permit 01091662
Plan Review Stops For Permit 01091662
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-13 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2001-11-13 Time 18:49 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 21:16 Rev Time 0.00
Received By dpalmer Date 2001-10-09 Time 21:16 Sent To  
Notes
2001-10-09 00:00:00**************** UNSAT **************
  
 1)NOTE:PLEASE CALRIFY EQUIP GROUNDING
 METHOD BETWEEN FIRST MEANS OF
 DISCONNECTAND PANEL(S). EQUIPMENT
 GROUNDING
 CONDUCTORS ARE TO BE SIZED BY 250-122.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 MISSING ONE ON LOWER-LEVEL.
  
  
 4)NOTE: PLEASE NOTE OUTLETS MISSING FOR
 KITCHEN ISLAND. PER 210-52-C-2.(GFI)
  
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6)NOTE: PLEASE NOTE MISSING WHIRLPOOL
 ON PANEL SCHEDULE/LOAD CALCS.
  
 7)NOTE: PLEASE CLARIFYGROUNDING AT
 DETACHED GARAGE PER 250-32
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-11-19 Cont ID  
Sent By pkrauss Date 2001-10-10 Time 12:23 Rev Time 0.40
Received By pkrauss Date 2001-10-10 Time 12:23 Sent To  
Notes
2001-10-10 00:00:00 
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE PLANS WITH MECHA
 NICAL PERMIT APPLICATION.
  
 1.INDICATE IF THE A.C. SYSTEM WILL BE
 NEW OR EXISTING.
  
 2.MANUFACTURER DATA ON AHU AND
 CONDENSER UNIT.
  
 3.SHOW SIZING OF DUCTWORK AND GRILLS.
  
 4.CFM DISTRIBUTION.
  
 5.LOCATION OF THE AHU AND C.U.
  
 6.CHIMNEY SHALL COMPLY WITH CHAPTER
 8 OF THE 1997 SMC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-15 Cont ID  
Sent By kstevens Date 2001-11-15 Time 18:00 Rev Time 0.50
Received By kstevens Date 2001-11-15 Time 18:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-16 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 18:49 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-10-16 00:00:00PLUMBING PLAN REVIEW,DENIED
 CODE REFERENCE SPC-94 SEC 104.3
 (1) SHT A-4 GUEST SUITE ABOVE GARAGE,
 PROVIDE ISOMETRIC OF DWV SYSTEM AND TIE-
 IN TO SANI SEWER.
 (2A) SHT A-5 SHOW LOCATION OF SINK AT
 REAR PORCH ON FLAT PLAN.
 (B) ISOMETRIC DOES NOTMATCH FLAT PLAN,
 MIN PIPE SIZE FOR SHOWER 2".
 MIN PIPE SIZE FOR BATH TUB 1-1/2"
 ISOMETRIC NOT ACCEPTABLE, RECOMMEND YOU
 HAVE A PLUMBER, MAKE THE DRAWING.
 (3)IF NO BACKFLOW PREVENTER ON WATER
 SERVICE, RPZV WILL BE REQUIRED.
 LOCAL ORDINANCE. #2893-95
 END OF COMMENTSPAUL SCHMITZ
 561-659-8096X8233

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-11-19 Cont ID  
Sent By jgomez Date 2001-11-19 Time 13:19 Rev Time 3.00
Received By jgomez Date 2001-11-19 Time 13:19 Sent To  
Notes
2001-11-19 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
 2-PROVIDE PRODUCT APPROVAL FOR:
 A)"DUROCK" MATERIAL USED AS WALL AND
 ROOF SHEATHING MATERIAL.
 B)FRENCH DOORS, INCLUDING DRAWINGS.
 C)18' WIDE GARAGE DOOR THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY ENG'R
 D)ENTRY DOORS.
 3-PROVIDE STRUCTURAL GARAGE BUCK DETAIL
 AND SPECIFY THE DESIGN PRESSURES
 CALCULATED FOR GARAGE DOOR OPENING.
 SEC. 1606 SBC 1997.
 4-SPECIFY THE SOIL BEARING VALUE ON THE
 TEST BORING REPORT AS REQUIRED BY
 SEC. 1804.2.7 OF CITY AMENDMENTS TO
 SBC 1997.
 TEST BORING REPORT TO HAVE ORIGINAL
 SEAL, SGNATURE AND DATE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-11-16 Cont ID  
Sent By jgomez Date 2001-11-16 Time 13:18 Rev Time 2.50
Received By jgomez Date 2001-11-16 Time 13:18 Sent To  
Notes
2001-11-16 00:00:00CHECKLIST:
 1-ENGINEER'S NOTE ON SHEET A-3 IS NOT
 ACCEPTABLE. HE IS DELEGATING WORK THAT
 IS HIS RESPONSIBILITY AS PROFESSIONAL
 OF RECORD. HE'S THE ONE RESPONSIBLE
 FOR THE DESIGN OF THE STRUCTURE AND
 HE IS THE ONE RESPONSIBLE TO CHECK THE
 EXISTING CONDITIONS IN ORDER TO
 ASSURE THAT EXISTING STRUCTURE IS
 CAPABLE OF RESISTING THE ADDITIONAL
 LOADS.
 NOTE: SEE COMMENTS ON PLANS ON
 ADDITIONAL NOTES AND REVISE AS REQ'D.
 2-PAY IMPACT FEES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2001-10-30 Cont ID  
Sent By jgomez Date 2001-10-30 Time 10:22 Rev Time 4.00
Received By jgomez Date 2001-10-30 Time 10:22 Sent To  
Notes
2001-10-30 00:00:00CHECKLIST:
 1-NEED TO RECORD NOTICE OF COMMENCEMENT
 WITH THE COURHOUSE.
 2-AFTER ORIGINAL DRAWINGS ARE REVISED,
 PLEASE BRING THEM TO PALM BEACH COUNTY
 TO PAY IMPACT FEES. BRING STAMPED
 DRAWINGS AND PAID RECEIPT.
 3-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM IS INCOMPLETE:
 A)INDICATE EXPOSURE CONDITION.
 B)REVISE THE IMPORTANCE FACTOR: SEE
 ASCE 7-95 TABLE 6-2.
 C)ENGINEER DIDN'T SIGN THE FORM.
  
 4-THIS PROPERTY IS LOCATED ON FLOOD ZONE
 A-5. PROVIDE SURVEY SHOWING EXISTING
 FINISH FLOOR ELEVATIONS TO VERIFY THAT
 LOWEST FLOOR IS 6" ABOVE THE BASE
 FLOOD ELEVATION. SEC. 12-22(B)(1) OF
 CITY CODE.
 5-PROVIDE SITE PLAN SHOWING LOCATION OF
 GARAGE IN RELATION TO PROPERTY LINE TO
 CHECK FOR TABLE 600 SBC 1997.
 6-PROVIDE COMPLETE FASTENING SPECS FOR
 ATTACHMENT OF NEW PORTION OF CHIMNEY
 TO EXISTING ONE.
 -ALSO, CHIMNEY DETAIL/SECTION DOESN'T
 MATCH THE ONE SHOWN ON EXT. ELEVATIONS
 -PROVIDE PRODUCT APPROVAL AND SPECS FOR
 "DUROCK" MATERIAL USED AS WALL AND
 ROOF SHEATHING MATERIAL.
 7-REVISE GENERAL NOTES. THEY SAY THAT
 THE DESIGN CRITERIA IS SSTD 10-97, BUT
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM SEALED BY THE ENGIN'R
 USES ASCE 7-95 FOR 150 MPH WIND LOAD.
 SSTD 10-97 IS NOT A BUILDING CODE. IT
 IS A DESIGN PRESCRIPTIVE METHOD USED
 WHEN THE DESIGNER IS NOT A REGISTERED
 ARCHITECT OR ENGINEER.
 8-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SECTION 2405.2 SBC 1997.
 9-PROVIDE,2 COPIES,PRODUCT APPROVAL FOR:
 A)SPANISH TILE.
 B)FRENCH DOORS.
 C)SINGLE HUNG WINDOWS.
 D)ENTRY DOORS.
 E)UL LISTING AND SPECS FOR BBQ.
 F)GARAGE DOORS.
 10-PROVIDE PRODUCT APPROVALS FOR STORM
 SHUTTERS.
 -PROVIDE KEY PLAN AND COMPLETE INSTALL-
 ATION SCHEDULE AS PER CITY SAMPLE.
 -CLEARLY IDENTIFY ON PRODUCT APPROVALS
 SPECIFIC MOUNTING CONDITIONS AND
 ANCHORS TO BE USED.
 11-PROVIDE SMOKE DETECTORS BY STAIRS OF
 FLORIDA ROOM. SEC. 905.2 SBC 1997.
 12-SPECIFY CONNECTORS AT TOP AND BOTTOM
 OF NEW 2X4 COLUMNS AT KITCHEN AREA.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 13-SEE SECTION 1007 OF SBC 1997 AND
 PROVIDE ALL INFORMATION MISSING FOR
 STAIRS, RAILINGS, ETC.
 -SEE SECTION 2305 SBC 1997 AND PROVIDE
 THE SPECS FOR FIREBLOCKING.
 14-PROVIDE COMPLETE SECTION/DETAIL THRU
 MASTER BEDROOM BALCONY. INCLUDE SPECS
 FOR GUARDRAILS AS REQUIRED BY SECTIONS
 1015 AND 1608.2 SBC 1997.
 15-PROVIDE BORING TEST. SEC. 104.2.2 OF
 CITY AMENDMENTS TO SBC 1997 AND
 GENERAL NOTES ON SHEET A-4.
 16-PROVIDE ATTIC ACCESS AT MASTER BEDRM
 AND GUEST SUITE. SEC. 2309.6 SBC 1997
 17-REVISE ENERGY CALCULATIONS:
 -USE FORM 600A-97, NOT 600A-93.
 -SPECIFY SIZE OF CEILING FANS ON ELEC.
 PLANS FOR MASTER BEDROOM, FAMILY ROOM
 AND GUEST SUITE IF USING THE CEILING
 FAN CREDIT ON ENERGY CALCULATIONS.
 SEE TABLE 6-6 OF FLORIDA ENERGY CODE
 FOR BUILDING CONSTRUCTION, 1997 ED.
 18-SEE PLANS FOR ADDITIONAL COMMENTS,
 INCLUDING THOSE BY THE OTHER TRADES.
  
 NOTE: PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS TO EXPEDITE THE REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-10-11 Cont ID  
Sent By sgraham Date 2001-10-11 Time 11:00 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-10-11 00:00:00GUEST SUITE MUST NOT BE USED AS A RENTAL
 NO STOVE ALLOWED IN THE GUEST SUITE

Review Stop Z ZONING
Rev No 1 Status F Date 2001-10-04 Cont ID  
Sent By sgraham Date 2001-10-04 Time 12:01 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-10-04 00:00:00NEED CORRECT
 NEED CORRECT SURVEY