Plan Review Details - Permit 01091473
Plan Review Stops For Permit 01091473
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2001-10-18 Cont ID  
Sent By lmartine Date 2001-10-18 Time 13:47 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-10-22 Cont ID  
Sent By dpalmer Date 2001-10-22 Time 11:47 Rev Time 0.00
Received By dpalmer Date 2001-10-22 Time 11:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 22:38 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 22:38 Sent To  
Notes
2001-10-01 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT REQUIREMNETS
 PER ART;517 NEED TO BE SHOWN ON PLANS.
  
 2)NOTE: PLEASE NOTE THAT ALL NEW DEVICES
 NEED TO HAVE BRANCH CIRCUIT #`S SHOWN
 ON PLANS AND TO HAVE SUBMITTED PANEL
 SCHEDULES. PLEASE SHOW ALL EXISTING
 W/ AND "E".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE QUESTIONS, PLEASE
 CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-10-18 Cont ID  
Sent By lmartine Date 2001-10-18 Time 13:48 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-10-22 Cont ID  
Sent By mcarsill Date 2001-10-22 Time 13:41 Rev Time 0.00
Received By mcarsill Date 2001-10-22 Time 13:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-11 Cont ID  
Sent By mcarsill Date 2001-10-11 Time 14:48 Rev Time 0.00
Received By mcarsill Date 2001-10-11 Time 14:48 Sent To  
Notes
2001-10-11 00:00:00IT HAS BEEN EXPLAINED TO THIS WRITER
 THAT THE BUILDING IS A MIXED OCCUPANCY
 CONTAINING THREE SEPARATE OCCUPANCIES,
 TENANT 1 WAS EXPLAINED AS BUSINESS,
 TENANT 2 WAS EXPLAINED AS STORAGE,
 AND TENANT 3 INDUSTRIAL. NO MECHANICAL
 OR HVAC INFORMATION PROVIDED WITH
 PLANS.
 TENANT # 1
 A) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 TENANT # 2
 A) NO EMERGENCY LIGHTING SHOWN.
 B) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 TENANT # 3
 A) NO INFORMATION ON SEPARATION WALL
 FOR BETWEEN TENANT # 2 AND TENANT # 3.
 B) NO EMERGENCY LIGHTING SHOWN.
 C) SPRAY BOOTH CANNOT BE APPROVED
 BECAUSE NOT ENOUGH INFORMATION HAS
 BEEN PROVIDED. MAKE-UP AIR, DISCHARGE
 OF EXHAUST DUCT ON RAILROAD EASEMENT,
 REQUIRED 3 FOOT SEPARATION DISTANCE FROM
 SPRAY BOOTH. BOOTH GOING TO BE
 GROUNDED?
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-10-26 Cont ID  
Sent By pkrauss Date 2001-10-26 Time 09:17 Rev Time 0.25
Received By pkrauss Date   Time   Sent To  
Notes
2001-10-26 00:00:00INSUFFICIENT INFORMATION FOR MECH
 REVIEW MECHANICAL PULLED FROM MASTER.
 ADDITIONAL FEES AND PERMIT FOR MECH
 REQUIRED. PLANS REQUIRED WITH MECH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status I Date 2001-10-22 Cont ID  
Sent By ndenmark Date 2001-10-22 Time 08:47 Rev Time 0.33
Received By ndenmark Date 2001-10-22 Time 08:47 Sent To  
Notes
2001-10-22 00:00:00INSUFFICIENT INFORMATION FOR REVIEW
  
 NO INFO PROVIDED FOR MECHANICAL OR
 HVAC. SUBMIT PLANS AND PERMIT PRIOR TO
 WORK
 PROVIDE SPECS AND PLANS ON SPRAY BOOTH
 PRIOR TO ANY WORK BEING DONE ON THE
 SPRAY BOOTH.
 SPRAY BOOTH REQUIRES SEPARATE PERMIT AND
 PLANS
 SUPPRESSION SYSTEM FOR SPRAY BOOTH
 REQUIRES SEPARATE PERMIT AND PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status I Date 2001-10-10 Cont ID  
Sent By pkrauss Date 2001-10-10 Time 12:15 Rev Time 0.45
Received By pkrauss Date 2001-10-10 Time 11:59 Sent To  
Notes
2001-10-10 00:00:00 
 INSUFFICIENT INFORMATION FOR MECHANICAL
 REVIEW. PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 1.INDICATE WILL A.C. SYSTEM BE NEW OR
 OR EXISTING.
  
 2.SHOW SIZING OF DUCTWORK AND GRILLS.
  
 3.CFM DISTRIBUTION.
  
 4.MANUFACTURER DATA ON A.C. SYSTEM.
  
 5.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 6.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
  
 ADDITIONAL PLANS AND PERMITS FOR SPRAY
 BOOTH AND FIRE SUPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status N Date 2001-10-18 Cont ID  
Sent By lmartine Date 2001-10-18 Time 13:48 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2001-10-18 Cont ID  
Sent By lmartine Date 2001-10-18 Time 13:48 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***