Plan Review Details - Permit 01091470
Plan Review Stops For Permit 01091470
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-19 Cont ID  
Sent By lsmith Date 2001-11-19 Time 10:21 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-15 Cont ID  
Sent By lsmith Date 2001-10-15 Time 09:50 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
2001-10-15 00:00:00*************BUILDING UNSAT*************
  
 SBC 104.2.2
  
 1. PER SEC. 515.29 FLA. STATE STATUTES
 SPECIFY ON PLANS METHOD OFCOMPLIANCE
 TO ISOLATE POOL FROM ACCESS TO HOME.
 2. CONTRACT TO VERIFY VALUE OF JOB.
  
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-14 Cont ID  
Sent By dpalmer Date 2001-11-14 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2001-11-14 Time 13:25 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 18:31 Sent To  
Notes
2001-10-10 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NO WIRE SIZES
 ARE SHOWN ON WIRING DIAGRAM FOR PUMP/
 LTS ETC.
  
 2)NOTE: PLEASE SUBMIT SPEC SHEETS FOR
 HEATER.
  
 PLEASE CORRECT AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-15 Cont ID  
Sent By dpalmer Date 2001-11-14 Time 13:25 Rev Time 0.33
Received By kstevens Date 2001-11-15 Time 19:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-09-29 Cont ID  
Sent By kstevens Date 2001-09-29 Time 00:10 Rev Time 0.33
Received By kstevens Date 2001-09-29 Time 00:10 Sent To  
Notes
2001-09-29 00:00:00DENIED
  
 UNIFORM COUNTYWIDE SWIMMING POOL AND SPA
 CODE. PLEASE COMPLY WITH SECTION 39. A
 VALVE SHALL BE INSTALLED ON ALL SUCTION
 LINES OF THE SWIMMING POOL OR SPA. NONE
 ARE SHOWN ON THE PIPING DIAGRAM. PLEASE
 SHOW VALVES ON PIPING DIAGRAM.
  
 PLEASE SUBMIT REQUIRED MANUFACTURE INFOR
 MATION FOR GAS WATER HEATER. SHOW BTU'S
 AND LISTING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-09-28 Cont ID  
Sent By sgraham Date 2001-09-28 Time 11:32 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***