Plan Review Details - Permit 01091467
Plan Review Stops For Permit 01091467
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-12-05 Cont ID  
Sent By jwitmer Date 2001-12-05 Time 10:22 Rev Time 0.15
Received By rbrown Date 2001-12-05 Time 10:22 Sent To  
Notes
2001-12-05 00:00:00PROVISO (1) - FLOOR LOAD AFFIDAVIT FILED
 WITH APPLICATION.
2001-11-20 00:00:00PROVISO:
 1) - SBC 106.4.2 STORAGE AND
 FACTORY-INDTRIAL OCCUPANCIES. IT SHALL
 BE THE RESPOLITY OF THE OWNER, AGENT,
 PROPRIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT
 ARCHITECT OR ENGINEER IN CMPUTING THE
 SAFE LOAD CAPACITY. ALL
 SUCHCOMPUTATIONS SHALL BE ACCOMPANIED
 BY AN AFFIDAVIT FROM THE ARCHITECT OR
 ENGINEER STATING THE SAFE ALLOWABLE
 FLOOR LOAD ON EACH FLOOR IN POUNDS PER
 SQUARE FOOT UNIFORMLY DISTRIBUTED.THE
 COMPUTATIONS AND AFFIDAVIT SHALL BE
 FILED AS A PERMANENT RECORD OF THE
 BUILDING DEPARTMENT. 2) - ADDITIONAL
 INFORMATION REQUIRED.REVISED DETAIL
 4/A3 IS NOT SHOWN ON SHEET A2 AS
 APPLYING TO THE EXISTING STAIRCASE
 LOCATION.WHAT TYPE OF MATERIAL WILL
 BE USED AS INFILL AT THIS LOCATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-23 Cont ID  
Sent By jwitmer Date 2001-10-23 Time 15:24 Rev Time 4.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-10-23 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01091467
 3500 45TH ST SUITE 18
 CONT: HUMMUT CONSTRUCTION
 TEL: 965-9911
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 1)- SBC 503.2.3.2: MEZANINE VS A 2ND FL:
 WHEN THE FLOOR AREA IS OVER 1/3 THE
 FLOOR AREA OF THE ROOM IT IS LOCATED IN,
 THE AREA IS CONSIDERED A SECOND STORY
 WITHIN THE ENCLOSED SPACE.
  
 2)- THE NEW SECOND FLOOR STORAGE AREA
 WILL NOT NEED TO MEET THE VERTICAL
 ACCESSIBILITY REQUIREMENTS, EXCEPTION
 TO STORAGE AREAS, CHANGE OF USE WILL
 ENVOKE FLORIDA ACCESSIBILITY REQUIREMENT
  
 3)- SBC 104.2.2 ADDITIONAL INFORMATION
 REQUIRED? INFILL OF EXISTING STAIRS
 WITH WHAT TYPE OF MATERIAL?
  
 4)- SBC 1604.1 THE PLANS SHALL INDICATE
 WHAT THE LIVE LOAD FLOOR LOADS ARE
 DESIGNED FOR, SECOND FLOOR LIGHT 125LBS
 /FT OR HEAVY 250 LBS/FL?
  
 5)- SBC* STORAGE & FACTORY OCCUPANCIES:
 IT SHALL BE THE RESPONSIBILITY OF THE
 OWNER, AGENT, PROPRIETOR OR OCCUPANT OF
 GROUP S & GROUP F OCCUPANCIES, OR ANY OC
 CUPANCY WHERE EXCESSIVE IS LIKELY TO
 OCCUR, TO EMPLOY A COMPETENT ARCHITECT
 OR ENGINEER TO COMPUTE THE SAFE LOAD
 CAPACITY. ALL SAFE LOAD COMPUTATIONS
 SHALL BE ACCOMPANIED BY AN AFFIDAVIT
 FROM THE ARCHITECT OR ENGINEER STATING
 THE SAFE ALLOWABLE FLOOR LOAD ON EACH
 FLOOR IN POUND PER SQUARE FOOT UNIFORMLY
 DISTRIBUTED. THE COMPUTATIONS AND AFFIDA
 VIT SHALL BE FILED AS A PERMANENT RECORD
 OF THE BUILDING DEPARTMENT.
  
 6)- SBC*106.4.3 SIGNAGE REQUIRED:
 IN EVERY BUILDING WHERE A PART OF THE
 BUILDING IS USED FOR STORAGE,THE SAFE
 FLOOR LOADS AS REVIEWED BY THE BUILDING
 OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DESIGN WHICH SHALL BE
 SUPPLIED AND SECURELY AFFIXED BY THE
 OWNER IN A CONSPICUOUS PLACE FOR EACH
 STORY TO WHICH IT RELATES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-02-12 Cont ID  
Sent By dpalmer Date 2002-02-12 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2002-02-12 Time 18:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-11-16 Cont ID  
Sent By dpalmer Date 2001-11-16 Time 16:04 Rev Time 0.00
Received By dpalmer Date 2001-11-16 Time 16:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 21:48 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 21:48 Sent To  
Notes
2001-10-01 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT OUTLET SPACING
 FOR OFFICE/STORAGE AREAS NEED TO MEET
 LOCAL AMENDMENTS,210-50. PLEASE SEE
 STORAGE AREAS UPSTAIRS.
  
 2)NOTE: PLEASE INCLUDE FEEDS/GOING TO
 EXISTING PANELS ON RISER DIAGRAM.
  
 3)NOTE: PLEASE NOTE THAT EXISTING PANELS
 ARE SHOWN IN NEW ELECTRICAL ROOM AND
 NEW PANELS GOING INTO OFFICE AREA.PLEASE
 PLACE NOTE ON PLANS (E-1) THAT AREA
 INFRONT OF NEW ELECTRICAL EQUIPMENT TO
 BE LABELED AND REMAIN DEDICATED
 ELECTRICAL SPACE PER 110-26.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE AREANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-11-14 Cont ID  
Sent By mcarsill Date 2001-11-14 Time 10:26 Rev Time 0.00
Received By mcarsill Date 2001-11-14 Time 10:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-10-02 Cont ID  
Sent By mcarsill Date 2001-10-02 Time 09:37 Rev Time 0.00
Received By mcarsill Date 2001-10-02 Time 09:37 Sent To  
Notes
2001-10-02 00:00:001) PLEASE INDICATE WHAT THE SPACE WILL
 BE USED FOR.
 2) PLEASE INDICATE OCCUPANCY LOADS.
 3) PLEASE PROVIDE A LIFE-SAFETY PLAN.
 4) ARE THERE ANY FIRE SPRINKLERS PRESENT
 5) CLEARLY IDENTIFY TENANT
 SEPARATIONS.
 6) IS THERE ONLY ONE SINGLE MEANS OF
 EGRESS PROVIDED FROM THE FIRST FLOOR.
 7) WHAT IS THE MEZZANINE GOING TO BE
 USED FOR.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2001-10-15 Cont ID  
Sent By ndenmark Date 2001-10-15 Time 13:56 Rev Time 0.33
Received By ndenmark Date 2001-10-15 Time 13:56 Sent To  
Notes
2001-10-15 00:00:00NOTE:
 SEPARATE MECHANICAL PERMIT REQUIRED FOR
 FREEZER. SUBMIT PLANS AT TIME OF PERMIT
 APPLICATION FOR FREEZER PRIOR TO
 BEGINING ANY WORK ON FREEZER.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-02-25 Cont ID  
Sent By kstevens Date 2002-02-25 Time 07:47 Rev Time 0.50
Received By kstevens Date 2002-02-25 Time 07:47 Sent To  
Notes
2002-02-25 00:00:00REVISION OK - ADD F.S. AND MOVE HAND
 SINK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-18 Cont ID  
Sent By pschmitz Date 2001-11-18 Time 14:25 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-11-18 00:00:00PLUMBING PLAN REVIEW,PROVISO SHT P-1,2
 SPC-94,SEC 921.4 COMBINATION WASTE& VENT
 SEPERATE PLANS & PERMIT FOR GAS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 7 V

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-22 Cont ID  
Sent By kstevens Date 2001-10-22 Time 16:28 Rev Time 1.50
Received By kstevens Date 2001-10-22 Time 16:28 Sent To  
Notes
2001-10-22 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES PER SPC TABLE 407. EXIST-
 ING HDCP TOILET ROOM DOES NOT MEET CODE.
 2) GREASE TRAP TO BE SIZED AND LOCATED
 BY UTILITY DEPT REG. SEWER TREATMENT
 DEPT. PLEASE CONTACT RODNEY COMPO (561)
 837-4074. WASTE ORD. 2938-96
 3) PAGE P-1 NO DRY HORIZONTAL VENTS FOR
 SANT. SPC SEC 906.2.1
 4) PAGE P-1/P-2 3 COMPARTMENT SINK TO
 DRAIN INDIRECTLY TO A FLOOR SINK. SPC
 SEC 804.1
 5) PAGE P-2 SEPARATE PERMIT FOR GAS RE-
 QUIRED. SEE ATTACHED SHEET FOR PERMIT
 APPLICATION REQUIREMENTS. PLEASE SUBMIT
 INFORMATION AT TIME OF PERMIT APPLICAT-
 ION.
 6) PAGE P-2 WATER HEATER DETAIL. T & P
 VALVE DISCHARGE FULL SIZE, & PAN DRAIN
 LINE (1") SHALL RUN OUTSIDE TO 6" ABOVE
 GRADE OR TO A FLOOR SINK WITH TRAP PRIM-
 ER.
 7) PAGE P-2 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS SHALL BE INSTALLED PER
 MANUFACTURE INSTALLATION INSTRUCTIONS &
 WH-PDI 201. THEY SHALL BE IN AN EFFECT-
 IVE RANGE OF THE FIXTURE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377