Plan Review Details - Permit 01091426
Plan Review Stops For Permit 01091426
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-16 Cont ID  
Sent By btrobaug Date 2002-07-11 Time 11:10 Rev Time 0.00
Received By jwitmer Date 2002-05-15 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-03 Cont ID  
Sent By btrobaug Date 2002-05-03 Time 10:44 Rev Time 3.50
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-03 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01091425
 222 GREGORY RD
 CONT: MEN AT WORK
 TEL: 585-9152
 CEL: 707-6967
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1) PRODUCT APPROVAL REPORT99-0128.01
 IS FOR OUTSWING ALUMINIUM FRENCH DOORS.
 A SINGLE OR PAIR OF DOORS ONLY! PRODUCT
 LIMITATIONS 3.1 STATES THAT IT IS FOR
 A SINGLE DOOR OR PAIR OF DOORS ONLY, THE
 PRODUCT DESCRIPTION ALSO REFLECTS STRICT
 COMPLIANCE WITH TECH DRAWINGS # 971.
 UNLESS A STRUCTURAL MEMBER IS INTRODUCED
 BETWEEN THE PAIR OF DOORS AND SIDE LITES
 SEPERATING THE 2 ELEMENTS THIS REPORT
 SHALL NOT BE USED FOR THIS APPLICATION.
 IF A STRUCTURAL MEMBER IS USED TO SEPERA
 TE THE 2 ELEMENTS A REPORT SHALL BE REQU
 IRED FOR THE SIDELITE ELEMENTIF IT EX-
 CEEDS THE LIMITAATION FOR REPORT#
 99-0218.01 ALREADY SUPPLIED. NOTE SIDE
 LIGHT SHALL BE TEMPERED GLASS!
 2) TRUSS ENGINEERING: THE DESIGN CERTI-
 FICATION SHEET INDICATES A MEAN ROOF
 HEIGTH OF 29'-3", THE TRUSS ENGINEERING
 SHEETS INDICATE MULTIPLE HEIGTHS!!!!!
 SBC 1606.2.2.1 WIND PRESSURE MIXING OF
 COEFFICIENTS & DYNAMIC PRESSURES FROM
 DIFFERENT SOURCES SHALL NOT BE PERMITTED
 A SINGLE MEAN ROOF HEIGTH IS TO BE USED
 FOR THE ENTIRE STRUCTURE, NOT THE
 VARIOUS MEAN ROOF HEIGTH OF THE VARIOUS
 TRUSSES. TRUSS ENGINEERING TO BE CALCULA
 TED WITH THE WORST CASE MEAN ROOF HEIGTH
 3) DISCREPANCY BETWEEN A-4,A-7 & THE
 TRUSS ENGINEERING LAYOUT SHEET. CABANA
 ROOM, SHEET A-4 & THE TRUSS LAY OUT
 SHEET FROM A-1 INDICATE A WALL BELOW THE
 TRUSS ALONG THE BACK WALL. A-7 INDICATES
 THE USE OF A GIRDER TRUSS. SINCE A-7 IS
 DESIGNED FROM THE ARCH HE IS NOT SPECIF-
 FYING THE CONNECTION THINKING TRUSS/
 GIRDER CONNECTIION WHICH IS SPECED FROM
 THE TRUSS ENG. THE TRUSS ENG LAYOUT
 SHEET THIS WALL SHOWS UP AS A WALL, THE
 TRUSS ENGINEER NOT SPECIFYING THE CONNEC
 TION TRUSS TO BEAM!!!
 BOTTOM LINE NO ANCHOR IS DETAILED.
 4) TRUSS ENG CUT SHEETS WG1 THREE MEMBER
 GIRDER NEEDS ATTENTION?TRUSS ENG SHEET
 INDICATES A UPLIFT VALUE OF 15,167 LBS
 AND A REACTION VALUE OF 24,614 / 32"=
 769 LBS / INCH.*****EXCEEDS CRUSHING
 VALUES*****
 5) CONTRACTOR TO SUBMIT PLANS TO PALM
 BEACH COUNTY FOR IMPACT FEE ASSESSMENT!
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-29 Cont ID  
Sent By jwitmer Date 2001-10-29 Time 16:04 Rev Time 5.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-10-29 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01091425
 222 GREGORY RD
 CONT: MEN AT WORK CONST
 TEL: 585-9152
 CELL: 707-6967
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- PRODUCT APPROVAL 99-0128.01:
 SWD-101 OUTSWING FRENCH DOORS 3.0 LIMIT-
 TATIONS, SINGLE UNIT, OR PAIR OF DOORS,
 REPORT NOT TESTED WITH SIDELITES! SEE
 GREAT ROOM.
  
 2)- PRODUCT APPROVAL, WINDOWS: MISSING
 MULLION REPORT FOR WINDOWS.
  
 3)- SSHEET A-1:
 A) MISSING COLUMN INFORMATION, ACI
 530-95 LATERAL TIES 5.9.1.6.
 B) SBC 104.2.2* THE PLANS INDICATE A
 COMBINATION OF POURED COLUMNS & BEAMS
 HOOPS VS. GROUTED MASONARY & BOND
 BEAMS, WHICH IS TO BE USED? PUMP MIX
 OR GROUT? WHAT STRENGTH?
 C) INFO FOR THE SPIRAL STAIRS?
 D) LOFT: INDICATE THE LANDINGS FOR THE
 2ND 3RD FLOOR.
 E) LOFT: SEPERATION OF LOFT & OPEN AREA
 WALL OR GAURDRAIL?
  
 4)- SHEET A-2 INDICATES A 2ND & 3RD
 FLOOR, SBC TABLE 600 TYPE VI-1 HR
 PROTECTED, OR TYPE VI UNPROTECTED/
 SPRINKLERED ( FOOTNOTE H) GIVES ALLOW
 ANCES FOR A 3RD FLOOR (SPRINKLERED).
 GIVE THE FLOOR CEILING 1 HR RATING
 ASSEMBLIES OR SUPPLY THE FIRE SPRINK-
 LER PLANS.
  
 5)- SHEET A-3
 A) FIRST FL ELEVATION INDICATES A 12'
 X 6' WINDOW, IS THERE A BEAM AS
 DIPICTED?
 B) 2ND / 3RD FLOOR MISSING HEADER INFOR
 MATION, SBC 2308.3.1. HEADERS2308.3.2
 THE NUMBER OF JACK STUDS REQUIRED,
 AND THE TYPE OF CONNECTOR REQUIRED
 FOR UPLIFT?
 C) BALCONY; MISSING FLASHING DETAIL FOR
 THE LIGHTWEIGHT CONCRETE?
 D) DETAIL FOR THE ANCHORING OF GAURD-
 RAIL.
 E) MISSING INFORMATION, 2X12 THE STRAP-
 PING FOR THTE TOP PLATE AND FLOOR
 JOIST?
  
 6)- SHEET A-4:
 A) DISCREPANCY: THE PLANS INDICATE A
 HAND FRAMED VAULT VS TRUSS LAYOUT
 T-10.
 B) DISCREPANCY: CUT SECTIONS A/B ARE
 FLIPPED.
 C) SBC 104.2.2. HURRICANE ANCHOR SCHED-
 ULE, SHOW LOCATION, DIRECTION, &
 MAGNITUDE OF THE LOADS TO BE RESIST-
 ED.
 D) THE DESIGN CERTIFICATION SHEET INDI-
 CATES A HEIGTH OF 29'-3" VS TRUSS
 ENGINEERING MULT HEIGTHS.
 SBC 1606.2.2.1 WIND PRESSURE MIXING
 OF COEFFICIENTS & DYNAMIC PRESSURES
 FROM DIFFERENT SCOURCES SHALL NOT
 BE PERMITTED.
 E) SEC A BUILT UP GIRDER INDICATE TYPE
 OF ANCHORS TO BE SUPPLIED FOR
 UPLIFT & REACTION. *** REACTION
 24,614LBS @ 33 SQ IN = 745 LBS/ IN.
 EXCEEDS CRUSHING VALUES
 F) WALL SECTION "B" IS MISSING THE
 FIRE STOPPING 2305.1.4(5)
 G) GREAT ROOM- DETAIL FOR GABLE ENDS
 HOW WILL END WALLS TIE IN? DIAPHRAM?
  
 7)- PLEASE PROVIDE A ROOF NAILING
 SCHEDULE AS PER SBC 2306.1*.
  
 PLANS ARE INCOMPLETE ENOUGH TO DO A
 THROUGH PLAN REVIW
 BUILDING PLAN REVIW
 JIM WITMER
 (561) 659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2002-05-16 Cont ID  
Sent By jwitmer Date 2002-05-16 Time 13:37 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-05-02 Cont ID  
Sent By btrobaug Date 2002-05-02 Time 13:01 Rev Time 0.00
Received By btrobaug Date 2002-05-02 Time 11:32 Sent To B
Notes
2002-05-02 00:00:00~~~~~~~~~~~~~~~~~~UNSAT!~~~~~~~~~~~~~~~~
  
 1} PLEASE REDRAW THE CHANGES THAT WERE
 MADE IN PENCIL TO MAKE THEM A PERMINENT
 PART OF THE DOCUMENT.
  
 2} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
 3RD FLOOR.
  
 3} ONE SET OF PLANS HAS NO SEAL ON A5
 OR A6.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-14 Cont ID  
Sent By dpalmer Date 2002-03-14 Time 06:49 Rev Time 0.00
Received By dpalmer Date 2002-03-14 Time 06:49 Sent To P
Notes
2002-03-14 00:00:00****************** UNSAT **************
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 SEE NFPA-72 2-5-2.1.3
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 PLEASE NOTE, NO PANEL SCHEDULE SUBMITTED
 OR LOAD CALCULATIONS.220-3-C-1/215-5
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 STILL MISSING IN MANY LOCATIONS.
 PLEASE CLARFIY"FIXTURES"? SHOWN ON 3RD
 FLOOR LEVEL. LIGHTS? HOW ARE THEY
 CONTROLLED?
  
 4) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 5) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
 PLEASE CLARIFY FOR AHU#2 SHOWN ABOVE
 BATH ROOM?
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE NOTE KITCHENCOUNTERTOP
 RECEPT SPACING FOR PENINSULAR.PLEASE
 SEE 210-52-C-3 AND 4.
  
 8) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 MISSING IN BOTH SMALL BATHS DOWNSTAIRS.
 PLEASE NOTE GFI IN SM.BATH 210-8.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-19 Cont ID  
Sent By dpalmer Date 2001-10-19 Time 16:12 Rev Time 0.00
Received By dpalmer Date 2001-10-19 Time 16:12 Sent To  
Notes
2001-10-19 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
  
 6) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
 7) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 8)NOTE: PLEASE NOTE MISSING OUTLET FOR
 HALLWAY(S) 210-52H
  
 9)NOTE: PLEASE NOTE MISSING DISCONNECT
 FORA/C CU 440-11
  
 10)NOTE: PLEASE SHOW ALL BATHS AS GFI/
 GFI PROTECTED. 210-8
  
 11)NOTE: PLEASE NOTE MISSING OUTLET FOR
 BATH(S) PER 210-52D
  
 12)NOTE: PLEASE NOTE MISSING OUTLETS
 FOR KITCHEN COUNTERSPACE PER 210-52-C-3
  
 13)NOTE: PLEASE NOTE MISSING MEANS OF
 EGRESS LIGHTING FOR STAIRS? 210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-03-30 Cont ID  
Sent By hmoser Date 2002-03-30 Time 11:23 Rev Time 0.50
Received By hmoser Date 2002-03-30 Time 11:23 Sent To  
Notes
2002-03-30 00:00:00NO PLANS,ENERGE CALCS,NO MANUAL J
 H.M.3/30/02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-25 Cont ID  
Sent By pkrauss Date 2001-10-25 Time 10:19 Rev Time 0.40
Received By pkrauss Date 2001-10-25 Time 10:11 Sent To  
Notes
2001-10-25 00:00:00*******************DENIED***************
  
 PLEASE NOTE, ARCHITECTS TITLE BLOCK HAS
 NO SEAL, SIGNATURE OR DATE.IF TITLE
 BLOCK IS ON THE PLAN IT IS REQUIRED TO
 BE SEALED, SIGNED AND DATED.
  
  
 PLEASE SUBMIT THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.LOCATION OF EXISTING AHU RETURN AIR
 GRILL.
  
 2.INDICATE SIZE AND LOCATION OF ANY
 NEW DUCT ADDED TO THE EXISTING
 AHU.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED AS PER 1997
 SMC 304.8.6.1.
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-03-30 Cont ID  
Sent By dpalmer Date 2002-03-14 Time 06:49 Rev Time 0.33
Received By jleech Date 2002-03-30 Time 10:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-24 Cont ID  
Sent By kstevens Date 2001-10-24 Time 21:08 Rev Time 0.33
Received By kstevens Date 2001-10-24 Time 21:08 Sent To  
Notes
2001-10-24 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) PLEASE NOTE THAT THE CABANA SHOWER IS
 NOT VENTED PROPERLY. SHOWER SHOULD BE
 TAKEN OFF BETWEEN W/C AND LAV NOT OFF
 DRAIN THAT PICKS UP UPSTAIRS BATHROOM.
 PLEASE SHOW EXISTING LAUNDRY FIXTURES ON
 SANITARY RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377.

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-02 Cont ID  
Sent By sgraham Date 2001-10-02 Time 14:55 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***