| Plan Review Stops For Permit 01091398 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-02-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-02-13 |
Time |
19:47 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2002-02-13 |
Time |
19:47 |
Sent To |
|
|
| Notes |
| 2002-02-13 00:00:00 | TRUSS DRAWINGS REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-12-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-12-06 |
Time |
12:04 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-12-06 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2001-12-06 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE AO. NEED THE ELEVATION | | | CERTIFICATE. | | | 2-NEED ADDITIONAL SOIL BORINGS FOR EACH | | | STRUCTURE AS RECOMMENDED ON THE PRE- | | | LIMINARY SOIL TEST REPORT. | | | 3-PROVIDE PRODUCT APPROVAL FOR FRENCH | | | DOORS ASSEMBLIES AS SHOWN ON PLANS IF | | | OPTION SELECTED. | | | 4-PROVIDE MANUFACTURER'S CERTIFICATION | | | FOR TWO HOUR FIRE RATED CONCRETE BLOCK | | | ACCORDING TO THE BLOCK'S EQUIVALENT | | | THICKNESS AND AGGREGATES USED. SEE | | | SECTION 709.3 SBC 1997. | | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS UNDER A SEPARATE PERMIT. | | | 6-TRUSS DRAWINGS: | | | -UPDATE ALL GENERAL TRUSS DETAILS. USE | | | ASCE 7-95 FOR 140MPH, NOT ASCE 7-93. | | | SEE COMMENTS ON TRUSS DRAWINGS. | | | | | | | | | | | | NOTES: | | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | | PERMIT #01091398. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01091398, 01091400, 01091403 AND | | | 01091405. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-11-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-11-06 |
Time |
16:36 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-11-06 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2001-11-06 00:00:00 | CHECKLIST: | | | 1-SEE COMMENTS BY PLUMBING. REVISE | | | ORIGINAL DRAWINGS TO AVOID DELAYS AND | | | ADDITIONAL FEES. | | | 2-NEED TO RECORD NOTICE OF COMMENCEMENT. | | | 3-NEED ADDITIONAL SOIL BORINGS FOR EACH | | | STRUCTURE AS RECOMMENDED ON THE PRE- | | | LIMINARY SOIL TEST REPORT. | | | 4-PROVIDE PRODUCT APPROVAL FOR: | | | A)GARAGE DOORS PRODUCT APPROVAL WAS | | | DELETED FROM SBCCI LISTING. | | | B)WINDOW MULLIONS. | | | 5-CLEARLY INDICATE ON PLANS OPTIONS TO | | | BE BUILT AND PROVIDE PRODUCT APPROVALS | | | OR CROSS OUT THE OPTIONS. | | | 6-OWES ADDITIONAL FEES FOR UPDATED VALUE | | | AND RADON FEES. PLEASE PAY ATTACHED | | | RECEIPTS AND BRING PAID RECEIPTS. | | | 7-PROVIDE CERTIFICATION FOR TWO HR FIRE | | | RATED CONCRETE BLOCK THAT COMPLIES W/ | | | SECTION 709.3 SBC 1997. | | | | | | NOTE: | | | THIS CERTIFICATION IS GIVEN BY THE | | | MANUFACTURER ACCORDING TO THE CONCRETE | | | BLOCK EQUIVALENT THICKNESS AND TYPE | | | OF AGGREGATES USED. | | | 8-PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS OR APPLY FOR A SEPARATE PERMIT. | | | | | | | | | NOTES: | | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | | PERMIT # 01091398. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01091398, 01091400, 01091403 AND | | | 01091405. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-09-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-09-11 |
Time |
15:59 |
Rev Time |
0.25 |
| Received By |
btrobaug |
Date |
2002-09-11 |
Time |
15:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-08-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-08-22 |
Time |
15:48 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-08-22 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2002-08-22 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | | | NOTE: PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-10 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-10 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-10-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-17 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-17 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2001-10-17 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING,AND AFTER CONSTRUCTION. | | | 2) BUILDING ADDRESSES REQUIRED. | | | 3) ELECTRIC POWERED SMOKE DETECTORS | | | REQUIRED. | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 5) EGRESS WINDOWS TO COMPLY WITH | | | BUILDING AND FIRE CODE REQUIREMENTS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-01-29 |
Time |
15:40 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-01-29 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2002-01-29 00:00:00 | MECH REV PERMIT 01091482 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-10-03 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2001-10-03 |
Time |
19:17 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2001-10-03 |
Time |
19:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-12-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-01 |
Time |
06:26 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-12-01 |
Time |
06:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-10-02 |
Time |
17:53 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-02 00:00:00 | SEE REVIEW NOTES UNDER 01091400 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-02 |
Time |
14:52 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|