Plan Review Details - Permit 01091387
Plan Review Stops For Permit 01091387
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-12-27 Cont ID  
Sent By rbrown Date 2002-12-27 Time 16:24 Rev Time 0.00
Received By rbrown Date 2002-12-27 Time 16:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-08-29 Cont ID  
Sent By btrobaug Date 2002-12-17 Time 12:12 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-08-07 Cont ID  
Sent By dpalmer Date 2002-08-07 Time 16:07 Rev Time 0.00
Received By dpalmer Date 2002-08-07 Time 16:07 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-08-29 Cont ID  
Sent By lmartine Date 2002-08-29 Time 18:08 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2002-08-29 Cont ID  
Sent By lmartine Date 2002-08-29 Time 18:08 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-17 Cont ID  
Sent By btrobaug Date 2002-12-17 Time 12:12 Rev Time 0.00
Received By btrobaug Date 2002-12-17 Time 12:12 Sent To B
Notes
2002-12-17 00:00:00TO LUIS./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-10-28 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 14:08 Rev Time 0.00
Received By btrobaug Date   Time   Sent To P
Notes
2002-10-28 00:00:00TO "P" IN BOX./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-10-29 Cont ID  
Sent By pkrauss Date 2002-10-29 Time 08:42 Rev Time 0.10
Received By pkrauss Date 2002-10-29 Time 08:42 Sent To  
Notes
2002-10-29 00:00:00PERMIT & FEES TRANSFERED PER DEAN
 RUNNELS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-09-27 Cont ID  
Sent By pkrauss Date 2002-09-27 Time 08:20 Rev Time 0.20
Received By pkrauss Date 2002-09-27 Time 08:20 Sent To  
Notes
2002-09-27 00:00:00MECHANICAL PERMIT 01091387
 MECHANICAL PERMIT REQUIRED.MECHANICAL
 PERMIT SUBMITTED WITH ORIGINAL BUILDING
 PERMIT APPLICATION IS DATED 9-26-01 &
 THE MECHANICAL CONTRACTOR (DUAL AIR)
 WAS NOT SIGNED ON AT THAT TIME.THE
 MECHANICAL PERMIT WAS SIGNED 7-16-02,
 THEREFORE ADDITIONAL FEES ARE REQUIRED
 FOR MECHANICAL PERMIT.PLANS SUBMITTED
 ARE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-02-20 Cont ID  
Sent By pkrauss Date 2001-10-05 Time 11:47 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
2001-10-05 00:00:00NO PLANS SUBMITTED

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-10-29 Cont ID  
Sent By pschmitz Date 2002-10-29 Time 08:23 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-10-29 00:00:00REVISION OIL SEPERATOR, CAR WASH. PES

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-09-19 Cont ID  
Sent By btrobaug Date 2002-10-28 Time 14:08 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-09-19 00:00:00PLUMBING PLAN REVIEW, DENIED, SPC-94
 (1) SEC 301.11 CONNECTION TO SEWER
 SYSTEM, CAR WASH DRAIN REQUIRED TO BE
 CONNECTED TO THE SANITARY SEWER SYSTEM.
 CONTACT RODNEY COMPO ENVIROMENTL COMPLI-
 ANCE 561-837-4074 FOR SIZE AND TYPE OF
 TRAP.SEC 1004 INTERCCEPTORS AND SEPER-
 ATORS WHERE REQUIRED.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS561-659-8096X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-08-29 Cont ID  
Sent By kstevens Date 2002-08-29 Time 14:31 Rev Time 0.00
Received By kstevens Date 2002-08-29 Time 14:30 Sent To  
Notes
2002-08-29 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT AM-61 HDCP W/C DETAIL SHOWS 19"-
 20", PER SEC 4.16.3 THE HEIGHT OF WATER
 CLOSETS SHALL BE 17" TO 19" MEASURED
 FROM THE TOP OF THE TOILET SEAT. (FIG.
 29(B). ALSO SEE DETAIL ON SHT AMP-61.
 PLEASE CHANGE DETAILS.
 2) SHT AMP-61 SANITARY RISER DIAGRAM, A
 2-WAY CLEANOUT IS REQUIRED WHERE THE
 SLOP SINK EXITS THE BLDG NEAR THE JUNCT-
 ION OF THE BLDG DRAIN & SEWER.
 3) SHT AMP-61 DOMESTIC WATER RISER DIA-
 GRAM, AIR CHAMBERS ARE A QUICK FIX AND
 REQUIRE AN ACCESS PANEL AND SHALL BE
 PROVIDED WITH AN ACCESSIBLE MEANS FOR
 RESTORING THE AIR. APPROVED WATER HAMMER
 ARRESTORS DO NOT REQUIRE EITHER ACCESS
 OR SERVICE. IF W.H.A'S ARE USED THEY
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF THE
 DROPS AS SHOWN FOR AIR CHAMBERS.
 4) WATER HEATER SHALL HAVE A SHIPS LADD-
 ER AND A WORKING PLATFORM INSTALLED TO
 MAKE THE WATER HEATER READILY ACCESSIBLE
 OR PUT WATER HEATER ON FLOOR.
 5) IF THE WATER HEATER IS INSTALLED ON
 THE PLATFORM THEN A PAN IS REQUIRED WITH
 A 1" PAN DRAIN. PLEASE SUBMIT DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-08-29 Cont ID  
Sent By lmartine Date 2002-08-29 Time 18:08 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***