Plan Review Details - Permit 01091365
Plan Review Stops For Permit 01091365
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-07-16 Cont ID  
Sent By jwitmer Date 2002-07-16 Time 11:35 Rev Time 1.00
Received By jwitmer Date 2002-07-16 Time 11:34 Sent To  
Notes
2002-07-16 00:00:00 
 REVISION 7/11/02OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-05-16 Cont ID  
Sent By jwitmer Date 2002-05-16 Time 16:28 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-05-16 00:00:00REVISIONS 4/25/02 OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-01-24 Cont ID  
Sent By jwitmer Date 2002-01-24 Time 12:42 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-01-03 Cont ID  
Sent By btrobaug Date 2002-01-23 Time 13:17 Rev Time 2.00
Received By jwitmer Date 2002-01-03 Time 07:14 Sent To  
Notes
2002-01-03 00:00:00BUILDING PLAN REVIEW
 PLANS UNCHANGED FROM FIRST REVIEW
 FOR COMMENTS SEE FIRST REVIEW!!!!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-18 Cont ID  
Sent By pkrauss Date 2001-12-31 Time 14:06 Rev Time 4.00
Received By jwitmer Date 2001-10-18 Time 07:06 Sent To  
Notes
2001-10-18 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01091365
 300 34TH ST
 CONT: WAYNE HETZEL BUILDING
 PHONE: (561) 881-2108
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS TO STANDARD BUILDING
 CODE
 1)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 A)- WINDOWS INDICATE WHICH KDI WINDOW
 SYSTEM THAT YOU ARE USING? ONLY THE
 KDI 2000 WINDOW SYSTEM IS TESTED
 FOR LARGE MISSLE IMPACT TESTING!
 IF A KDI WINDOW SYSTEM OTHER THAN
 THE "2000" SERIESIS INSTALLED,
 STORM SHUTTERS WILL BE REQUIRED.
 B)- OUT SWING FRENCH DOORS; WILL RE-
 QUIRE STORM SHUTTERS.
 C)- IN SWING FRENCH DOORS; NEW REPORT
 REQUIRED, EXPIRED
 D)- SKYLIGHT: MISSING PRODUCT APPROVAL
 REPORT, GLAZED OPENING WILL REQUIRE
 LARGE MISSLE IMPACT RESISTANCE TEST
 ING OR STORM SHUTTERS.
 E)- STORM SHUTTERS: A KEY DIAGRAPM &
 INSTALLATION SCHEDULE IS ALSO RE-
 QUIRED, A SAMPLE IS ATTACHED.
  
 2)- STAIRS: WINDERS, SBC 1007.8.1.
 A MINIMUM TREAD DEPTH OF 6" AT THE
 NARROW EDGE & SHALL HAVE A MINIMUM
 TREAD DEPTH OF 11" AT A POINT 12"
 FROM THE NARROW EDGE.
  
 3)-SHEET A511 (DETAIL 1) :
 A)- CEILING LINE/ TRUSS LINE MISSING
 FIRE BLOCKING
 B)- 2ND FLOOR WOOD NAILER AT BEAM,
 REQUIRED TO BE PRESSURE TREATED
  
 4)- SHEET A511 (DETAIL 3) :
 A)- CAANTILEVERED BALCANY- THE BEAM IN-
 DICATES THE SIZE OF THE STEEL, BUT
 NOT THE SIZE OR FREQUENCY OF HOOPS &
 STIRRUPS.
 B)- GAURDRAIL TO COMPLY WITH 1015.3,
 OPENINGS 4"
 C)- MISSING FIRE STOPPING CEILING LEVEL
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096X 8412

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-01-23 Cont ID  
Sent By btrobaug Date 2002-01-23 Time 13:17 Rev Time 1.00
Received By btrobaug Date 2002-01-23 Time 12:19 Sent To B
Notes
2002-01-23 00:00:00*****************PROVISO!***************
 1) INDICATE SIZE OF SERVICE MAST ON
 RISER DIAGRAM.
 2) INDICATE WIRE SIZE OF SERVICE
 ENTRANCE CONDUCTOR ON RISER DIAGRAM.
 3) PROVIDE A G.F.I. AT THE CONDENSOR
 LOCATION PER 210-63.SEE PLAN.
 4) INCLUDE BREAKER SIZE ON PANEL
 SCHEDULE.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-12-19 Cont ID  
Sent By dpalmer Date 2001-12-19 Time 12:50 Rev Time 0.00
Received By dpalmer Date 2001-12-19 Time 12:38 Sent To P
Notes
2001-12-19 00:00:00*****************NOTE *************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
  
  
 PLEASE MAKE CORRECTIONS AND SUBMIT FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-09 Cont ID  
Sent By dpalmer Date 2001-10-09 Time 21:53 Rev Time 0.00
Received By dpalmer Date 2001-10-09 Time 21:53 Sent To  
Notes
2001-10-09 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NO LOAD CALCS/
 PANEL SCHEDULES/ RISER DIAGRAMS ETC
 WERE SUBMITTED? 220-3-C1/215-5 310-16,,
 ,,,
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE SHOW SWITCHING OF EGRESS LIGHTING
 FOR STAIRWAY.?
 ELECTRICAL PLANS NEED TO SHOW STAIRS
  
 5)NOTE: PLEASE SHOW SINKL LOCATIONS FOR
 BATHS SO OUTLET LOCATIONS MEET 210-52D
  
 6)NOTE: PLEASE NOTE DEDICATED
 ELECTRICALSPACE FOR PANEL SHOWN IN
 STORAGE ROOM
 IN A SF RESIDENCE. ALSO SEE 384-7
 IGNITIBLE MATERIALS.
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 CLARIFY SPACING IN "NEW GUEST BR"
 ALSO EGRESS LIGHTING? 210-70
  
 8)NOTE: PLEASE NOTE MISSING NEW CU FOR
 A/C ON ELECTRICAL PLAN WITH DISCONNECTS
 PER 440-11
  
 9) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 10)NOTE: PLEASE NOTE EGRESS FROM BATH
 TO OUTSIDE W/ NO EGRESS LIGHTING
 CONTROL-S? 210-70
  
 11)NOTE: PLEASE NOTE CIRCUITS BEING
 SHOWN FOR DRYER AND WATER HEATER IN
 LAUNDRY ROOM BUT NOT FOR WASHER? PER
 210-52-F. PLEASE CLARFIY-EXISTING IN
 OTHER LOCATION?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-07-11 Cont ID  
Sent By hmoser Date 2002-07-11 Time 17:53 Rev Time 0.50
Received By hmoser Date 2002-07-11 Time 17:53 Sent To  
Notes
2002-07-11 00:00:00PASS/PROVISO
 NEED MODEL NUMBER OF EVAP.COIL FOR
 FINAL INSPECTION
 H.M. 7/11/02

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-01-24 Cont ID  
Sent By pkrauss Date 2002-01-24 Time 11:21 Rev Time 0.20
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-12-31 Cont ID  
Sent By pkrauss Date 2001-12-31 Time 14:03 Rev Time 0.40
Received By pkrauss Date 2001-12-31 Time 13:46 Sent To B
Notes
2001-12-31 00:00:00*******************DENIED***************
  
  
 SEE ELETRICAL PLAN REVIEW NOTE #9 AND
 #10.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-10 Cont ID  
Sent By pkrauss Date 2001-10-10 Time 14:00 Rev Time 0.45
Received By pkrauss Date 2001-10-10 Time 14:00 Sent To  
Notes
2001-10-10 00:00:00 
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.EXISTING DUCTWORK - WHAT SIZE, IS
 THIS DUCTWORK BEING TIED INTO NEW
 5 TON SYSTEM?WHAT WAS THE SIZE OF
 THE OLD SYSTEM.
  
 2.LOCATION OF THE 5 TON SYSTEM, IF
 INSTALLED IN THE ATTIC SHALL HAVE
 AN ACCESS OPENING NO LESS THAN 22"
 X 36" CONTINUOUS FROM OPENING TO THE
 EQUIPMENT.SHALL HAVE AN ACCESSIBLE
 DISCONNECT SWITCH, A 110-120 VOLT
 A/C GROUNDING TYPE CONVENIENCE OUT-
 LET AND A LIGHT ON THE SERVICE SIDE
 OF THE EQUIPMENT CONTROLLED BY A
 SWITCH AT THE ACCESS OPENING.
  
 3.AXUILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION BY MEANS OF A FLOAT
 SWITCH OR SEPARATE DRAIN TERMINATING
 AT CONSPICUOUS POINT TO SERVE AS AN
 ALARM THAT THE REGULAR DRAIN IS
 RESTRICTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-12-29 Cont ID  
Sent By jleech Date 2001-12-29 Time 09:56 Rev Time 0.33
Received By jleech Date 2001-12-29 Time 09:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-12-19 Time 13:44 Rev Time 0.33
Received By kstevens Date 2001-10-10 Time 18:36 Sent To  
Notes
2001-10-10 00:00:00DENIED
 REFERENCE: SPC-94 - SEC 104.2.1
  
 PLEASE SUBMIT A SANITARY RISER DIAGRAM
 THAT SHOWS ALL PIPES SIZES AND VENTING
 FOR PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2001-10-04 Cont ID  
Sent By sgraham Date 2001-10-04 Time 12:59 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***