| Plan Review Stops For Permit 01091347 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-29 |
Time |
13:46 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2001-11-29 |
Time |
13:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-17 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-10-17 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-10-17 00:00:00 | THE TITLE SHEET CITES THE "LATEST | | | EDITION" OF THE STANDARD BUILDING CODE. | | | THE CITY AND STATE, CURRENTLY INVOKE | | | THE 1997 EDITION.PLEASE REVISE AND | | | ENSURE COMPLIANCE AS NECESSARY. | | | | | | SECTION 6/A8.5 SHOWS PT LUMBER.IT | | | SHOULD BE FRT.SEE SBC 609.2.1. | | | | | | SECTIONS 9 & 10/A8.5 HAVE A NOTE "FASTEN | | | TO STRUCTURE ABOVE".PROVIDE SPECIFIC | | | CONNECTION DETAILS.SEE SBC 104.2. | | | | | | SBCT705.1.2 REQUIRES DOORS #419A AND | | | #420A TO BE FIRE RATED. | | | | | | PLEASE PROVIDE A SEATING PLAN.SEE SBC | | | 1003.1.2. | | | | | | SHOW THE FIRE EXIT HARDWARE FOR THE | | | STAIR DOORS.SEE SBC 1021.2.1 | | | | | | NOTE THE GRADE FOR THESE CLASSROOMS AS | | | 3RD OR GREATER.SEE SBC 1021.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2001-12-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-18 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-18 |
Time |
12:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-11-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-11-26 |
Time |
21:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-11-26 |
Time |
21:24 |
Sent To |
|
|
| Notes |
| 2001-11-26 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | | FROM FIRST REVIEW WERE ADDRESSED. | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER 215-5,220-10,220-3,220-10.220-11, | | | 220-13 ETC. | | | PLEASE NOTE ALL CONTINUOUS LOADS ARE TO | | | BE SHOWN AT 125%.215-2,3/ 230-42 | | | | | | 3)NOTE: PLEASE SHOW/CLARIFY GROUNDING | | | OF TRANSFORMER 250-30. | | | | | | 4)NOTE: PLEASE CLARIFY LOAD ON EXISTING | | | "MDP". PLANS SHOW ADDING A LARGE LOAD. | | | PLEASE SHOW. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
21:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-01 |
Time |
21:59 |
Sent To |
|
|
| Notes |
| 2001-10-01 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT NO RISER | | | DIAGRAM WAS SUBMITTED TO SHOW HOW THE | | | PANELS ARE BEING FED? WHERE,HOW,EXISTING | | | ???? | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED. PLEASE | | | NOTE THAT LOAD CALCS NEED TO BE SHOWN | | | PER 220. SQ FT ETC ETC. CONTINUOUS LOADS | | | KVA? ETC. | | | | | | 3)NOTE: PLEASE NOTE THAT THE ELECTRICAL | | | ROOM SHOWS TRANSFORMER, BUT NOTHING | | | SHOWN ON A ONE-LINE DIAGRAM. | | | PLEASE SUBMIT A ONE-LINE WITH THE ABOVE | | | INFORMAITON FOR REVIEW. | | | | | | PLEASE SUBMIT FOR REVIEW ALL OF THE | | | ABOVE INFORMATION. IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-29 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2001-12-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-10 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-10 |
Time |
12:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-09-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-09-26 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-09-26 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2001-09-26 00:00:00 | 1) PLEASE INDICATE THE GRADE LEVELS | | | PLANNED FOR THE FOURTH FLOOR. | | | PLEASE BE ADVISED THAT CERTAIN | | | RESTRICTIONS APPLY TO GRADE | | | LEVELS ABOVE THE SECOND FLOOR. | | | 2) NO FIRE SPRINKLER PLANS PROVIDED | | | WITH DRAWINGS. | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM EQUIPMENT | | | ADDITION. | | | 4) NO INTERIOR FINISH INFORMATION | | | PROVIDED FOR WALLS AND CEILINGS. | | | 5) PANIC HARDWARE WILL BE REQUIRED SINCE | | | CAPACITIES OF THE FOURTH FLOOR EXCEEDS | | | 100 PERSONS. | | | 6) NOTES SECTION INDICATES DUCT SMOKE | | | DETECTORS WILL BE INSTALLED IN SUPPLY. | | | NORMALLY DUCT SMOKE DETECTORS IN UNITS | | | UNDER 2000 CFM ARE INSTALLED IN THE | | | RETURNS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2001-12-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-18 |
Time |
12:17 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2001-12-18 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2001-12-18 00:00:00 | | | | PROVISO:EXHAUST DUCTS FROM BATHROOMS | | | INTO EXISTING VERTICAL CHASE, | | | SHALL COMPLY WITH 1997 SMC | | | 610.1.3 #2, WHERE BRANCH DUCTS | | | CONNECT TO RETURN RISERS IN | | | WHICH THE AIR IS UPWARD AND | | | SUBDUCTS AT LEAST 22" LONG ARE | | | CARRIED UP INSIDE THE RISER AT | | | EACH INLET. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2001-12-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-05 |
Time |
12:08 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2001-12-05 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2001-12-05 00:00:00 | *******************DENIED*************** | | | | | | | | | RESPONSE TO COMMENTS DATED 10/15/01 | | | INDICATE "MISSING SHEETS ADDED".PLANS | | | DO NOT REFLECT ANSWERS TO ANY OF THE | | | COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-15 |
Time |
10:26 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2001-10-15 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2001-10-15 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 3.PROVIDE A FIRE DAMPER DETAIL. | | | NOTE, FIRE DAMPERS SHALL COMPLY WITH | | | UL 555 AND SHALL BEAR THE LABLE OF | | | AN APPROVED TESTING AGENCY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 EXT. | | | 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2001-12-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-19 |
Time |
10:49 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-12-19 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2001-12-19 00:00:00 | PASSED/PROVISO | | | | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR FIXTURES, NOT IN CEILING AS SHOWN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2001-12-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-18 |
Time |
12:42 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-12-18 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2001-12-18 00:00:00 | DENIED | | | REFERENCE: SPC-94-FABCB-97 | | | | | | 1) COMMENT #3 FROM PREVIOUS REVIEW NOT | | | ADDRESSED. AIR CHAMBERS STILL SHOWN, AND | | | WATER HAMMER ARRESTORS NOT LOCATED PER | | | MANUFACTURES INSTRUCTIONS AND PDI-WH 201 | | | PLEASE SEE COMMENT #3 FROM PREVIOUS RE- | | | VIEW. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-12-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-03 |
Time |
16:22 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-12-03 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2001-12-03 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHTS A5.1 - A5.4, MINIMUM FACILITIES | | | CALL FOR 2 DRINKING FOUNTAINS. HI/LOW | | | DOES NOT CONSTITUTE 2 DRINKING FOUNTAINS | | | BECAUSE IT IS JUST ONE FIXTURE AND TWO | | | ARE REQUIRED. ONE MORE DRINKING FOUNTAIN | | | IS REQUIRED PER SPC TABLE 407. | | | 2) SHT A5.4 DETAIL #1 ENLARGED FLOOR | | | PLAN. CLEAR FLOOR SPACE FOR URNAL NOT | | | SHOWN. HDCP SPACE FOR URNAL SHOWS 2'6" | | | FROM WALL TO CENTER OF DIVIDER. 30" IS | | | REQUIRED FOR CLEAR FLOOR SPACE. | | | 3) SHT M-2 PLUMBING NOTES #13. AIR CHAM- | | | BERS REQUIRE ACCESS PANELS AND SHALL BE | | | RECHARGEABLE PER SPC SEC 607.8.3. WATER | | | HAMMER ARRESTORS ARE RECOMMENDED AND FOR | | | APPROVED ARRESTORS NO ACCESS IS REQUIRED | | | ALSO THE WATER HAMMER ARRESTORS SHALL BE | | | SIZED AND LOCATED, (CLOSE TO FIXTURE IN | | | AN EFFECTIVE RANGE - NOT AT TOP OF DROP | | | AS SHOWN ON RISER DIAGRAM) PER MANUFACT- | | | URE INSTALLATION INSTRUCTIONS AND WH-PDI | | | 201. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-22 |
Time |
11:00 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2001-10-22 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2001-10-22 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) CALCULATIONS FOR MINIMUM FIXTURES PER | | | SPC-94 TABLE 407 INDICATE MORE FIXTURES | | | ARE REQUIRED. 271 PERSONS REQUIRE 6 MALE | | | AND 6 FEMALE W/C'S REQUIRED. ALSO 2 | | | DRINKING FOUNTAINS ARE REQUIRED. | | | 2) PAGE A9.3, DETAIL #3 HDCP W/C TO BE | | | 1'6" TO CENTER OF W/C OFF WALL AND HDCP | | | LAV TO BE 2'10" AFF. PLEASE INDICATE | | | THIS ON PLANS. | | | 3) PAGE A9.3 DETAIL #6 & #9 HDCP W/C TO | | | BE 1'6" OFF WALL TO CENTER OF W/C, AND | | | LAV TO BE 2'10" AFF MAX. | | | 4) PLEASE PROVIDE AN ARCHITECTUAL FLOOR | | | PLAN FOR MENS & WOMENS BATHROOMS WITH | | | ALL DEMENSIONS. SHOW CLEAR FLOOR SPACE | | | FOR ALL HDCP FIXTURES AND SHOW DEMENS- | | | IONS FOR ALL STALLS, AND URNAL STALLS. | | | 5) PAGE M1, SANITARY RISER DIAGRAM RE- | | | QUIRED. SHOW ALL PIPE SIZES. SHOW TIE-IN | | | TO EXISTING SANT. AND VENT THRU ROOF OR | | | TIE-IN TO EXISTING. | | | 6) PAGE M1, WATER RISER DIAGRAM REQUIRED | | | SHOW ALL PIPE SIZES AND LOCATION AND | | | SIZE OF WATER HAMMER ARRESTORS. LOCATION | | | SHALL BE BY MANUFACTURE INSTALLATION IN- | | | STRUCTIONS AND WH-PDI 201. AIR CHAMBERS | | | ARE A "QUICK FIX" AND SHOULD NOT BE USED | | | BUT IF THEY ARE THEY SHALL COMPLY WITH | | | SPC-94 607.8.3 AND BE ACCESSIBLE AND RE- | | | CHARGEABLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-11-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-11-29 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|