Plan Review Details - Permit 01091347
Plan Review Stops For Permit 01091347
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-11-29 Cont ID  
Sent By jwitmer Date 2001-11-29 Time 13:46 Rev Time 4.00
Received By jwitmer Date 2001-11-29 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-10-17 Cont ID  
Sent By hpiskura Date 2001-10-17 Time 14:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-10-17 00:00:00THE TITLE SHEET CITES THE "LATEST
 EDITION" OF THE STANDARD BUILDING CODE.
 THE CITY AND STATE, CURRENTLY INVOKE
 THE 1997 EDITION.PLEASE REVISE AND
 ENSURE COMPLIANCE AS NECESSARY.
  
 SECTION 6/A8.5 SHOWS PT LUMBER.IT
 SHOULD BE FRT.SEE SBC 609.2.1.
  
 SECTIONS 9 & 10/A8.5 HAVE A NOTE "FASTEN
 TO STRUCTURE ABOVE".PROVIDE SPECIFIC
 CONNECTION DETAILS.SEE SBC 104.2.
  
 SBCT705.1.2 REQUIRES DOORS #419A AND
 #420A TO BE FIRE RATED.
  
 PLEASE PROVIDE A SEATING PLAN.SEE SBC
 1003.1.2.
  
 SHOW THE FIRE EXIT HARDWARE FOR THE
 STAIR DOORS.SEE SBC 1021.2.1
  
 NOTE THE GRADE FOR THESE CLASSROOMS AS
 3RD OR GREATER.SEE SBC 1021.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-12-18 Cont ID  
Sent By dpalmer Date 2001-12-18 Time 12:01 Rev Time 0.00
Received By dpalmer Date 2001-12-18 Time 12:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-11-26 Cont ID  
Sent By dpalmer Date 2001-11-26 Time 21:24 Rev Time 0.00
Received By dpalmer Date 2001-11-26 Time 21:24 Sent To  
Notes
2001-11-26 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FIRST REVIEW WERE ADDRESSED.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 215-5,220-10,220-3,220-10.220-11,
 220-13 ETC.
 PLEASE NOTE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125%.215-2,3/ 230-42
  
 3)NOTE: PLEASE SHOW/CLARIFY GROUNDING
 OF TRANSFORMER 250-30.
  
 4)NOTE: PLEASE CLARIFY LOAD ON EXISTING
 "MDP". PLANS SHOW ADDING A LARGE LOAD.
 PLEASE SHOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-10-01 Cont ID  
Sent By dpalmer Date 2001-10-01 Time 21:59 Rev Time 0.00
Received By dpalmer Date 2001-10-01 Time 21:59 Sent To  
Notes
2001-10-01 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT NO RISER
 DIAGRAM WAS SUBMITTED TO SHOW HOW THE
 PANELS ARE BEING FED? WHERE,HOW,EXISTING
 ????
  
 2)NOTE: PLEASE ALSO NOTE THAT NO LOAD
 CALCULATIONS WERE SUBMITTED. PLEASE
 NOTE THAT LOAD CALCS NEED TO BE SHOWN
 PER 220. SQ FT ETC ETC. CONTINUOUS LOADS
 KVA? ETC.
  
 3)NOTE: PLEASE NOTE THAT THE ELECTRICAL
 ROOM SHOWS TRANSFORMER, BUT NOTHING
 SHOWN ON A ONE-LINE DIAGRAM.
 PLEASE SUBMIT A ONE-LINE WITH THE ABOVE
 INFORMAITON FOR REVIEW.
  
 PLEASE SUBMIT FOR REVIEW ALL OF THE
 ABOVE INFORMATION. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2001-11-29 Cont ID  
Sent By jwitmer Date 2001-11-29 Time 13:45 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-12-10 Cont ID  
Sent By mcarsill Date 2001-12-10 Time 12:57 Rev Time 0.00
Received By mcarsill Date 2001-12-10 Time 12:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-09-26 Cont ID  
Sent By mcarsill Date 2001-09-26 Time 16:14 Rev Time 0.00
Received By mcarsill Date 2001-09-26 Time 16:13 Sent To  
Notes
2001-09-26 00:00:001) PLEASE INDICATE THE GRADE LEVELS
 PLANNED FOR THE FOURTH FLOOR.
 PLEASE BE ADVISED THAT CERTAIN
 RESTRICTIONS APPLY TO GRADE
 LEVELS ABOVE THE SECOND FLOOR.
 2) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM EQUIPMENT
 ADDITION.
 4) NO INTERIOR FINISH INFORMATION
 PROVIDED FOR WALLS AND CEILINGS.
 5) PANIC HARDWARE WILL BE REQUIRED SINCE
 CAPACITIES OF THE FOURTH FLOOR EXCEEDS
 100 PERSONS.
 6) NOTES SECTION INDICATES DUCT SMOKE
 DETECTORS WILL BE INSTALLED IN SUPPLY.
 NORMALLY DUCT SMOKE DETECTORS IN UNITS
 UNDER 2000 CFM ARE INSTALLED IN THE
 RETURNS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-12-18 Cont ID  
Sent By pkrauss Date 2001-12-18 Time 12:17 Rev Time 0.45
Received By pkrauss Date 2001-12-18 Time 12:14 Sent To  
Notes
2001-12-18 00:00:00 
 PROVISO:EXHAUST DUCTS FROM BATHROOMS
 INTO EXISTING VERTICAL CHASE,
 SHALL COMPLY WITH 1997 SMC
 610.1.3 #2, WHERE BRANCH DUCTS
 CONNECT TO RETURN RISERS IN
 WHICH THE AIR IS UPWARD AND
 SUBDUCTS AT LEAST 22" LONG ARE
 CARRIED UP INSIDE THE RISER AT
 EACH INLET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-12-05 Cont ID  
Sent By pkrauss Date 2001-12-05 Time 12:08 Rev Time 0.40
Received By pkrauss Date 2001-12-05 Time 11:51 Sent To  
Notes
2001-12-05 00:00:00*******************DENIED***************
  
  
 RESPONSE TO COMMENTS DATED 10/15/01
 INDICATE "MISSING SHEETS ADDED".PLANS
 DO NOT REFLECT ANSWERS TO ANY OF THE
 COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2001-10-15 Cont ID  
Sent By pkrauss Date 2001-10-15 Time 10:26 Rev Time 0.50
Received By pkrauss Date 2001-10-15 Time 10:09 Sent To  
Notes
2001-10-15 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2.
  
 3.PROVIDE A FIRE DAMPER DETAIL.
 NOTE, FIRE DAMPERS SHALL COMPLY WITH
 UL 555 AND SHALL BEAR THE LABLE OF
 AN APPROVED TESTING AGENCY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-12-19 Cont ID  
Sent By kstevens Date 2001-12-19 Time 10:49 Rev Time 0.50
Received By kstevens Date 2001-12-19 Time 10:49 Sent To  
Notes
2001-12-19 00:00:00PASSED/PROVISO
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR FIXTURES, NOT IN CEILING AS SHOWN.

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-12-18 Cont ID  
Sent By kstevens Date 2001-12-18 Time 12:42 Rev Time 0.50
Received By kstevens Date 2001-12-18 Time 12:42 Sent To  
Notes
2001-12-18 00:00:00DENIED
 REFERENCE: SPC-94-FABCB-97
  
 1) COMMENT #3 FROM PREVIOUS REVIEW NOT
 ADDRESSED. AIR CHAMBERS STILL SHOWN, AND
 WATER HAMMER ARRESTORS NOT LOCATED PER
 MANUFACTURES INSTRUCTIONS AND PDI-WH 201
 PLEASE SEE COMMENT #3 FROM PREVIOUS RE-
 VIEW.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-12-03 Cont ID  
Sent By kstevens Date 2001-12-03 Time 16:22 Rev Time 1.00
Received By kstevens Date 2001-12-03 Time 16:22 Sent To  
Notes
2001-12-03 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHTS A5.1 - A5.4, MINIMUM FACILITIES
 CALL FOR 2 DRINKING FOUNTAINS. HI/LOW
 DOES NOT CONSTITUTE 2 DRINKING FOUNTAINS
 BECAUSE IT IS JUST ONE FIXTURE AND TWO
 ARE REQUIRED. ONE MORE DRINKING FOUNTAIN
 IS REQUIRED PER SPC TABLE 407.
 2) SHT A5.4 DETAIL #1 ENLARGED FLOOR
 PLAN. CLEAR FLOOR SPACE FOR URNAL NOT
 SHOWN. HDCP SPACE FOR URNAL SHOWS 2'6"
 FROM WALL TO CENTER OF DIVIDER. 30" IS
 REQUIRED FOR CLEAR FLOOR SPACE.
 3) SHT M-2 PLUMBING NOTES #13. AIR CHAM-
 BERS REQUIRE ACCESS PANELS AND SHALL BE
 RECHARGEABLE PER SPC SEC 607.8.3. WATER
 HAMMER ARRESTORS ARE RECOMMENDED AND FOR
 APPROVED ARRESTORS NO ACCESS IS REQUIRED
 ALSO THE WATER HAMMER ARRESTORS SHALL BE
 SIZED AND LOCATED, (CLOSE TO FIXTURE IN
 AN EFFECTIVE RANGE - NOT AT TOP OF DROP
 AS SHOWN ON RISER DIAGRAM) PER MANUFACT-
 URE INSTALLATION INSTRUCTIONS AND WH-PDI
 201.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2001-10-22 Cont ID  
Sent By kstevens Date 2001-10-22 Time 11:00 Rev Time 1.00
Received By kstevens Date 2001-10-22 Time 11:00 Sent To  
Notes
2001-10-22 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) CALCULATIONS FOR MINIMUM FIXTURES PER
 SPC-94 TABLE 407 INDICATE MORE FIXTURES
 ARE REQUIRED. 271 PERSONS REQUIRE 6 MALE
 AND 6 FEMALE W/C'S REQUIRED. ALSO 2
 DRINKING FOUNTAINS ARE REQUIRED.
 2) PAGE A9.3, DETAIL #3 HDCP W/C TO BE
 1'6" TO CENTER OF W/C OFF WALL AND HDCP
 LAV TO BE 2'10" AFF. PLEASE INDICATE
 THIS ON PLANS.
 3) PAGE A9.3 DETAIL #6 & #9 HDCP W/C TO
 BE 1'6" OFF WALL TO CENTER OF W/C, AND
 LAV TO BE 2'10" AFF MAX.
 4) PLEASE PROVIDE AN ARCHITECTUAL FLOOR
 PLAN FOR MENS & WOMENS BATHROOMS WITH
 ALL DEMENSIONS. SHOW CLEAR FLOOR SPACE
 FOR ALL HDCP FIXTURES AND SHOW DEMENS-
 IONS FOR ALL STALLS, AND URNAL STALLS.
 5) PAGE M1, SANITARY RISER DIAGRAM RE-
 QUIRED. SHOW ALL PIPE SIZES. SHOW TIE-IN
 TO EXISTING SANT. AND VENT THRU ROOF OR
 TIE-IN TO EXISTING.
 6) PAGE M1, WATER RISER DIAGRAM REQUIRED
 SHOW ALL PIPE SIZES AND LOCATION AND
 SIZE OF WATER HAMMER ARRESTORS. LOCATION
 SHALL BE BY MANUFACTURE INSTALLATION IN-
 STRUCTIONS AND WH-PDI 201. AIR CHAMBERS
 ARE A "QUICK FIX" AND SHOULD NOT BE USED
 BUT IF THEY ARE THEY SHALL COMPLY WITH
 SPC-94 607.8.3 AND BE ACCESSIBLE AND RE-
 CHARGEABLE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2001-11-29 Cont ID  
Sent By jwitmer Date 2001-11-29 Time 13:45 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***