| Plan Review Stops For Permit 01091318 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-01-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-01-07 |
Time |
13:20 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2002-01-07 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2002-01-07 00:00:00 | PRODUCT APPROVAL CHECKLIST: | | | 1-FRENCH DOOR SITE SPECIFIC PRODUCT | | | APPROVAL: | | | A)MANUFACTURER'S ENGINEER TO PROVIDE | | | ORIGINAL SIGNATURE AND OFFICE ADDRESS | | | & PHONE NUMBER AS REQUIRED BY CHAPTER | | | 471 FLORIDA STATUTES WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. | | | B)USE CITY SAMPLE (ATTACHED) WHEN | | | SUBMITTING INFORMATION FOR SITE | | | SPECIFIC PRODUCT APPROVAL. | | | C)PROFESSIONAL ENGINEER OF RECORD NEED | | | TO SIGN, SEAL & DATE THIS SPECIFIC | | | PRODUCT APPROVAL FORM AS WELL. | | | -INCLUDE ALL HIS INFORMATION AS REQ'D | | | BY CHAPTER 471 FLORIDA STATUTES. | | | -SPECIFY LOCATION. THIS IS A SITE | | | SPECIFIC INSTALLATION. | | | D)CLARIFY WHY THE 2X WOOD BUCK IS NOT | | | CONSIDERED STRUCTURAL. SEE SECTION 4.2 | | | OF PRODUCT APPROVAL INFO. SUBMITTED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2001-12-04 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-12-04 |
Time |
10:49 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-12-04 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2001-12-04 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE AO: NEED THE ELEVATION | | | CERTIFICATE. | | | 2-NEED ADDITIONAL SOIL BORINGS FOR EACH | | | STRUCTURE AS RECOMMENDED ON THE PRE- | | | LIMINARY SOIL TEST REPORT. | | | 3-PROVIDE PRODUCT APPROVAL FOR FRENCH | | | DOORS AS SHOWN ON PLANS IF OPTION | | | IS SELECTED. | | | 4-PROVIDE MANUFACTURER'S CERTIFICATION | | | FOR TWO HR FIRE RATED CONCRETE BLOCK | | | ACCORDING TO THE BLOCK EQUIVALENT | | | THICKNESS AND AGGREGATES USED. SECTION | | | 709.3 SBC 1997. | | | 5-PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS UNDER A SEPARATE PERMIT. | | | | | | | | | NOTES: | | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | | PERMIT #01091318. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01091318, 01091320, 01091322, 01091324, | | | 01091326 AND 01091328. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-27 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-10-27 |
Time |
13:09 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2001-10-27 |
Time |
13:09 |
Sent To |
|
|
| Notes |
| 2001-10-27 00:00:00 | CHECKLIST: | | | 1-SEE COMMENTS BY PLUMBING. CORRECT | | | ORIGINAL DRAWINGS TO AVOID DELAYS. | | | 2-NEED RECORDED NOTICE OF COMMENCEMENT. | | | 3-WILL NEED ADDITIONAL SOIL BORINGS FOR | | | EACH STRUCTURE AS RECOMMENDED ON THE | | | PRELIMINARY SOIL TEST REPORT. | | | 4-PROVIDE PRODUCT APPROVAL FOR: | | | A)GARAGE DOORS: ONE SUBMITTED WAS | | | DELETED FROM SBCCI LISTING. | | | B)WINDOW MULLIONS. | | | | | | 5-CLEARLY INDICATE ON PLANS OPTIONS TO | | | BE BUILT AND PROVIDE PRODUCT APPROVALS | | | OR CROSS OUT OPTIONS ON PLANS. | | | 6-OWES ADDITIONAL FEES FOR UPDATED VALUE | | | AND RADON FEES. PLEASE PAY ATTACHED | | | RECEIPTS AND BRING PAID RECEIPTS. | | | 7-PROVIDE CERTIFICATION FOR TWO HR FIRE | | | RATED CONCRETE BLOCK THAT COMPLIES W/ | | | SECTION 709.3 SBC 1997 ACCORDING TO | | | THE EQUIVALENT THICKNESS. | | | 8-PROVIDE COMPLETE INFORMATION FOR STORM | | | PANELS OR APPLY FOR A SEPARATE PERMIT. | | | | | | | | | NOTES: | | | -DRAWINGS AND COMMENTS TO BE FILED UNDER | | | PERMIT #01091318. | | | -THESE COMMENTS APPLY TO PERMIT #S: | | | 01091318, 01091320, 01091322, 01091324, | | | 01091326 AND 01091328. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-05-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-02 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-02 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2001-10-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-09 |
Time |
22:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-09 |
Time |
22:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2001-10-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-17 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-17 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2001-10-17 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | 2) BUILDING ADDRESSES REQUIRED. | | | 3) ELECTRIC POWERED SMOKE DETECTORS | | | REQUIRED. | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 5) EGRESS WINDOWS TO COMPLY WITH | | | BUILDING AND FIRE CODES. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-03-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-26 |
Time |
15:59 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-12-04 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2001-12-04 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2001-12-04 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2001-12-04 00:00:00 | APPROVED BY HAROLD MOSER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2001-12-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-12-01 |
Time |
08:12 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2001-12-01 |
Time |
08:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-10-02 |
Time |
17:09 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2001-10-02 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2001-10-02 00:00:00 | PLUMBING DENIED; | | | 1.FHA DIMENSIONS FOR W/C ARE NOT 19". | | | PLEASE MAKE CHANGE TO MASTER PLANS. | | | 2.PAGE 2 SANITARY FISER DIAGRAM. OPT. | | | L.T. REQUIRES A VENT. PLEASE MAKE | | | CHANGES TO MASTER PLANS. | | | PLUMBING PLAN REVIEW BY; | | | JLEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2001-10-02 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-10-02 |
Time |
14:45 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|