| Plan Review Stops For Permit 01091302 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2001-10-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-01 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-01 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2001-10-01 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | BE DRAWN TO BE CLEAR ON ALL ELECTRICAL | | | WORK BEING DONE.104.2.7 | | | | | | 2)NOTE: PLEASE NOTE THAT NO LOAD | | | CALCULATIONS WERE SUBMITTED SHOWING NEW | | | LOADS BEING ADDED TO EXISTING. | | | 215-5 | | | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2001-10-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-10-04 |
Time |
08:23 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-10-04 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2001-10-04 00:00:00 | PROVISO ON PLAN, ATTIC ACCESS. |
|
|
|