Plan Review Details - Permit 01091293
Plan Review Stops For Permit 01091293
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2001-09-26 Cont ID  
Sent By mamini Date 2001-09-26 Time 15:19 Rev Time 5.00
Received By mamini Date 2001-09-26 Time 15:19 Sent To  
Notes
2001-09-26 00:00:00PASSED:
 1. RESPONSES TO THE PREVIOUS REVIEW
 COMMENTS DATED 7-31-01 SATISFACTORY,
 PLANS REVISED PER REVIEW COMMENTS.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2001-09-26 Cont ID  
Sent By mcarsill Date 2001-09-26 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2001-09-26 Time 15:48 Sent To  
Notes
2001-09-26 00:00:001) WET FIRE HYDRANTS ARE TO BE PROVIDED
 WITH CONSTRUCTION. A LETTER SUBMITTED
 BY ERIC COOPER OF SCHAFER, FAGAN
 INDICATES"FIRE HYDRANTS WILL BE PROVIDED
 PRIOR TO CONSTRUCTION OF THE MODELS."
 PLEASE BE ADVISED THAT WET FIRE
 HYDRANTS ARE REQUIRED WHEN THE
 RESIDENTIAL BUILDINGS ARE UNDER
 CONSTRUCTION NOT JUST THE MODELS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910