| Plan Review Stops For Permit 01091289 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-08-12 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-08-12 |
Time |
11:41 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-12 00:00:00 | REVSION |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2002-07-16 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2002-07-16 |
Time |
16:13 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-16 00:00:00 | | | | NOT APPROVED | | | --- -------- | | | | | | | | | 1] | | | SUBMIT STANDARD WALL DETAIL FOR | | | INTERIOR PARTITIONS. | | | | | | 2] | | | PROVIDE SPECIFICATIONS FOR NEW | | | STOREFRONT SYSTEM. | | | | | | 3] | | | EXPLAIN EXISTING WALL BETWEEN AEROBICS | | | AND FUTURE ROOMS. [WALL WAS NOT SHOWN ON | | | ORIGINAL DRAWINGS]. | | | | | | 4] | | | SEPERATE ELECTRICAL PERMIT IS REQUIRED. | | | | | | | | | | | | LUIS MARTINEZ | | | 659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-01-25 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-01-25 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-01-25 00:00:00 | PLANS DATED 1/11/02 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-01-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-01-03 |
Time |
12:26 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2001-10-29 |
Time |
17:44 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2001-10-29 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 01091289 | | | 500 VILLAGE BLVD | | | BREAKING GROUND CONT | | | TEL: (904) 388-1350 | | | | | | 1)- LEFT SIDE OF PLAN NOTE TO REMOVE | | | AND ADD NEW ADA RAMP. RAMP TO COMPLY | | | WITH FL ACC CODE 4.8-4.8.5. THE RAMP IS | | | TO BE MADE FROM THE SAME BUILD TYPE MATE | | | RIAL AS BUILD. TYPE 5 CONST? | | | | | | 2)- RAMP #9 ALSO TO COMPLY WITH FL ACC | | | 4.8-4.8.5. INDICATE THE RISE /RUN SLOPE | | | | | | 3)- NOTE #8 STOREFRONT GLASS, ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 4)- WHAT ISTHIS TO BE USED FOR?18,560SF | | | ASSEMBLY OCCUPANCY, SHOW EGRESS REQUIRE- | | | MENTS, DOORS,RAMPS TRAVEL DISTANCE. | | | | | | 5)- APPLICATION INDICATES FINISHES? | | | INDICATE CODE COMPLIANCE FOR SBC TABLE | | | 803.3. | | | | | | 6)- PLANS INDICATE JUICE BAR, SHOW | | | COMPLIANCE WITH FL ACC CODE5.1 COUNTERS. | | | | | | 7) INDICATE EGRESS DOORS,SWING WIDTH | | | | | | 8)- GUARDRAILS SBC 1015.1-5/ 1608.2. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-01-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-01-22 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-01-22 |
Time |
15:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-12-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-12-28 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-12-28 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2001-12-28 00:00:00 | ************** UNSAT **************** | | | | | | | | | 1)NOTE: PLEASE NOTE THAT APPLICATION | | | ANDFRONT COVER SHEET OF PLANS MENTION | | | ELECTRICAL WORK TO BE DONE AND TO SEE | | | E-SHEETS? PLEASE NOTE THAT THERE ARE | | | STILL NO E-SHEETS IN THE SET? | | | | | | PLEASE SUBMIT PLANS FOR REVIEW OR HAVE | | | APPLICATION CAHNGED AND FRONT COVER | | | SHEET.THE ELECTRICAL CONTRACTOR MAY | | | SUBMIT PLANS AND APPLICATION AT A LATER | | | DATE, BUT PLEASE MAKE THE ABOVE CHANGES | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-10-15 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-10-15 |
Time |
07:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-10-15 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2002-07-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-25 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-25 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2002-01-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-01-15 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-01-15 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2001-12-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-12-19 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-12-19 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2001-12-19 00:00:00 | 1) PLANS DO NOT INDICATE EMERGENCY | | | LIGHTING OR ILLUMINATED EXIT SIGNS. | | | 2) NO INTERIOR FINISH CLASSIFICATION | | | PROVIDED WITH PLANS. | | | 3) PLEASE PROVIDE MORE DETAILS ON | | | MOVABLE WIRE ENCLOSURE SHOWN ON | | | PAGE A-2. | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER REMODEL. | | | 5) NO ELECTRICAL OR HVAC DRAWINGS | | | SUBMITTED WITH PLANS. | | | 6) PLEASE PROVIDE A PROPOSED | | | FITNESS EQUIPMENT PLANNED FOR THE ROOM. | | | 7) PLEASE INDICATE OCCUPANT LOAD,AND | | | TRAVEL DISTANCES TO EXIT ON THE PLANS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2001-10-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2001-10-04 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2001-10-04 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2001-10-04 00:00:00 | 1) WHAT WILL THE SPACE BE USED FOR | | | AFTER RENOVATIONS ARE COMPLETE. | | | 2) AFTER STAIRS ARE REMOVED AND THE | | | DOOR OPENING IS CLOSED ON THE EAST SIDE, | | | A SINGLE MEANS OF EGRESS WILL BE | | | PRESENT. TWO SEPARATE MEANS OF EGRESS | | | WERE PRESENT PRIOR TO PLAN SUBMITTAL, | | | WHAT ALLOWS THE CLOSURE OF THIS EXIT | | | WAY. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2001-12-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2001-12-20 |
Time |
12:14 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2001-12-20 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2001-12-20 00:00:00 | | | | NO MECHANICAL PLANS SUBMIT FOR REVIEW. | | | PLEASE PROVIDE PLANS WITH MECHANICAL | | | PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-01-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-31 |
Time |
15:15 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2002-01-31 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2002-01-31 00:00:00 | PASSED/PROVISO | | | | | | WATER HAMMER ARRESTORS SHALL BE LOCATED | | | NEAR FIXTURES NOT AT TOP OF DROP AS | | | SHOWN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-01-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-01-07 |
Time |
17:14 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-01-07 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2002-01-07 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHT P-1 ALL SIGNED AND SEALED PLANS | | | SHALL HAVE ALL SHEETS SIGNED AND SEALED | | | AND ARE REQUIRED TO HAVE A TITLE BLOCK | | | ON THEM. | | | | | | 2) SHT P-1 WATER RISER DIAGRAM AIR CHAM- | | | BERS SHALL BE ACCESSIBLE AND RECHARGEA- | | | BLE PER SPC SEC 607.8.3. SEE ATTACHED | | | SHEET FOR APPROVED AIR CHAMBERS. APPROV- | | | ED WATER HAMMER ARRESTORS DO NOT REQUIRE | | | ACCESS AND ARE RECOMMENDED. SIZE AND | | | LOCATION PER PDI-WH 201 IN AN EFFECTIVE | | | RANGE CLOSE TO LAST FIXTURE NOT AT TOP | | | OF DROP. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2001-10-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2001-10-29 |
Time |
13:04 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2001-10-29 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2001-10-29 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PLEASE SUBMIT CALCULATIONS FOR MINI- | | | MUM FIXTURES PER SPC-94 TABLE 407. SHOW | | | ALL EXISTING TOILET ROOMS WITH ALL THE | | | DEMENTIONS FOR ROOMS, STALLS, DOOR SIZE | | | ECT. 1ST AND 2ND FLOORS | | | 2) SHOW NEW TOILET ROOMS WITH ALL DEMEN- | | | TIONS, CLEAR FLOOR SPACES, GRAB BAR DE- | | | TAILS ECT. SHOW COMPLIANCE WITH ALL SEC- | | | TIONS OF FACBC-97 SECTIONS. SHOW DETAILS | | | 3) URNALS TO COMPLY WITH FACBC SEC 4.18 | | | PLEASE SHOW DETAILS. | | | 4) FLOOR DRAINS ARE REQUIRED PER SPC SEC | | | 409.4.1.1 AND SHALL HAVE TRAP PRIMERS. | | | 5) PLEASE SUPPLY A SANITARY AND WATER | | | RISER DIAGRAM FOR DEMO AND NEW WORK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-03-12 |
Time |
08:09 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2001-10-15 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2001-10-15 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|